Box and Raceway Sizing Flashcards
True or False: When sizing boxes, conductors, clamps and support fittings are required to be counted in order to select the proper size box.
True.
True or False: Conductors that originate inside the box or that are spliced within the box are counted as one for each conductor.
False. Conductors that originate OUTSIDE the box or that are spliced within the box are counted as one for each conductor.
True or False: Conductors unbroken within the box, less than 12 inches in length, that pass through the box without splicing or terminating are counted as two for each conductor.
False: Conductors unbroken within the box, less than 12 inches in length, that pass through the box without splicing or terminating are counted as ONE for each conductor.
True and False: Conductors that originate within the box and do not leave the box such as bonding jumpers and pigtails are not counted
True.
True or False: Conductors from a domed luminaire (fixture) that terminate within the box are not counted.
True.
True or False: When sizing device and junction boxes, the insulation of the conductors are required to be taken into consideration.
False. They are NOT to be taken into consideration.
What volume (unit of measurement) is required for individual conductor(s)?
Cubic inches and or cubic centimeters, no matter what the insulation characteristics of the conductor(s) is/are
How do you determine the volume, in cubic inches, of a box?
Multiply length x width x depth of the box
A box measures 6 inches x 6 inches and is 4 inches deep. The volume is ______
144 cubic inches
6 x 6 x 4 = 144 cubic inches
What table # is used to determine the MIN size outlet box required for a given number of conductors, OR when determining the MAX number of conductors permitted in an outlet box when all conductors in the box are the SAME SIZE
314.16
Determine the MAX number of size 12 AWG THWN conductors permitted in a 4 x 1 1/2 in square box.
7
8
9
10
=9
The right hand side of the Table 314.16 under 12 column shows nine conductors permitted in the box
Of the following listed, which one of the boxes is the MIN required to house 3 size 12 AWG THWN/THHN conductors and 3 size 12 AWG conductors?
4 x 1 1/2 in octagon
4 x 2 1/4 in octagon
4 x 1 1/2 in square
4 x 2 1/4 in square
= 4 x 1 1/2 in octagon
Table 314.16
permits 6 size 12 AWG conductors in a 4 4 x 1 1/2 in octagon box
True or False: Table 314.16 shall apply where no fittings or devices, such as cable clamps, luminaire studs, hickeys, receptacles, switches or dimmers, are enclosed in the box.
True.
True or False: (Cable clamps) one or more internal cable clamps present in the box are counted as one conductor for each type of fitting, based on the largest conductor in the box.
True.
True or False: (Support fittings) One or more luminaire (fixture) studs and/or hickeys in the box are counted as one conductor for each type of fitting, based on the smallest conductor in the box.
False. Support fittings) One or more luminaire (fixture) studs and/or hickeys in the box are counted as one conductor for each type of fitting, based on the LARGEST conductor in the box.
True or False: (Devices) For each yoke or strap containing one or more device present in the box, they are to be counted as a single wire, based on the largest conductor connected to the device.
False. (Devices) For each yoke or strap containing one or more device present in the box, they are to be counted as TWO WIRES, based on the largest conductor connected to the device.
True or False: Equipment grounding conductors - one or more equipment grounding conductors or bonding jumpers contained in a box are to be counted as two conductors, based on the largest equipment grounding conductor or bonding jumper in the box.
**Where an additional set of isolated equipment grounding conductors are in the box, they are to be counted as one conductor, based on the largest equipment grounding conductor in the additional set.
False. Equipment grounding conductors - one or more equipment grounding conductors or bonding jumpers contained in a box are to be counted as ONE conductor, based on the largest equipment grounding conductor or bonding jumper in the box.
This is true:
**Where an additional set of isolated equipment grounding conductors are in the box, they are to be counted as one conductor, based on the largest equipment grounding conductor in the additional set.
A device box contains 2 internal clamps, 2 equipment grounding conductors, 1 bonding jumper, and one duplex receptacle. The number of conductors permitted in the box is to be reduced by _________ conductors.
3
4
5
6
=4
clamps: 1 wire
receptacle: 2 wires
equip.ground & bond wires 1 wire
= 4 wires
Determine which one of the following listed outlet boxes in the MIN size required to enclose the following conductors:
6 size 12 AWG conductors
2 size 14 AWG conductors
1 size 14 AWG equipment grounding conductors
4 x 1 1/2 in octagon
4 x 1 1/2 in square
4 x 2 1/4 in square
4 1/4 x 1 1/2 in square
= 4 x 1 1/2 in square
size 12 AWG = 2.25 cu. in. x 6
size 14 AWG = 2.00 cu. in. x 2
size 14 AWG equipment grounding x 1
3.5
4.0
+2.0
=19.5 cubic inches
Table 3.14
requires a 4 x 1 1/2 inch square box having a volume of 21 cubic inches.
True or False: Pull and junction boxes are to be sized by the raceway entering the box and NOT by the size of the conductors contained in the box when enclosing conductors of size 4 AWG or larger.
True.
True or False: In straight pulls, the length of the box shall not be less than ten times the trade diameter of the largest raceway entering the box.
False. In straight pulls, the length of the box shall not be less than EIGHT (8) times the trade diameter of the largest raceway entering the box.
Determine the MIN length of a pull box that has a trade size of 31/2 in. conduit entering at each end, and containing conductors of size 250 kcmil, when a straight pull of the conductors is to be made.
21 in
24 in
28 in
32 in
=28 in
3.5 in (conduit) x 8 = 28 inches
True or False: When splices, angle, and u pulls are made, the distance between each raceway entry inside the box and opposite wall of the box shall not be less than six times the trade size of the raceway in a row.
True.