Conductor ampacity and sizing Flashcards
True or False: The definition of ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its watts rating.
False: True or False: The definition of ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its TEMPERATURE rating.
When determining the ampacity of a conductor, or sizing of a conductor, there are several factors that needed to be taken into consideration?
The ambient temperature
Insulation rating
The # of current carrying conductors contained in a raceway
Rating of the terminations
The environment the conductor will be subject to and voltage drop
What is the table that lists various types of insulated conductors, allowable ampacitites?
Table 310.104
What table lists the ampacity values for copper, aluminum conductors.
Table 310.15
What is normal operating temperature for conductors?
Temps between 30’ C or 86’F
The left half of Table 310.15 is copper conductors or copper clad or aluminum conductors?
Left = Copper.
Right is the copper clad or aluminum conductors
What happens when conductors are subject to ambient temperatures above 86 dec F?
The resistance of the conductors increase proportionately. The greater the elevated ambient temperature, the greater the resistance.
True or False: Some conductors are dual rated?
True: THHW is rated 75 deg. C. for wet locations and 90 deg. C for dry locations.
True or False: The greater the elevated ambient temperature, the greater the resistance.
True
True or False: When resistance of a conductor increases the ampacity of the conductor decreases.
True
When a size 3 AWG copper conductor, with THW insulation, in installed in an area where the ambient temperature in 114 deg. F, the wire has an allowable ampacity of ________
100 amperes
75 amperes
82 amperes
58 amperes
75 amperes
100 amperes x .75 amperes
To solve this problem, locate the wire size on the left side of the table. (Table 310) and look to the right under the copper THW column, with a temperate rating of 75’C, Note the ampacity of the wire is 100 amperes at normal operating temperature. Then, we apply the values as shown in table 310. Look to the right side of the table where the temperature is show ‘F and find the ambient temperature. Next we follow that line to the left where the line intersects with the 75’ C col. Finally, to find the allowable ampacity of the conductor, multiply the two values together.
When a size 1/0 AWG THWN aluminum conductor is installed in an ambient temperature 45’C, the conductor has an allowable ampacity of ______.
100
90
98
104
=98
98 amperes
1/0 THWN aluminum ampacity before derating =120 amperes
120 amperes x .82 (correction factor) = 98.4 amperes
First, we find the wire size which has an ampacity of 120 amperes, Table 310.15 Then we find the ambient temperature, on the left portion of Table 310.15, and go to the right under the THWN aluminium col. to find the correction factor .82. Next, multiply the two values together.
What formula should be used when sizing conductors for a given load located in an area with an elevated ambient temperature?
Required ampacity = load/correction factor
Table 310.15
Where a 100 ampere load is to be supplied with THWN copper conductors in an area where the ambient temperature will reach 110 deg’F, size THWN conductors are required to serve the load.
1 AWG
2 AWG
3 AWG
1/0 AWG
= 1 AWG
Required ampacity= 100amps/.82 = 122 amperes
Table 310.15 indicates 1 AWG copper conductors with an ampacity of 130 amperes, should be selected. To cross reference:
130 amperes x .82 (correction factor) = 107 amperes
Conductors must be sized to the lowest temperature rating of the wire, circuit breakers, terminal or device.
Today, most terminations are rated at 60 deg. C or 75 deg. C
The load on a size 6 AWG THHN copper conductor is limited to _____ where connected to a circuit breaker with a termination rated at 60’C
75 amperes
65 amperes
60 amperes
55 amperes
= 55 amperes
Table 310.15 lists the ampacity of size 6 AWG, copper, 60’C rated conductors to be 55 amperes.
The load, in amperes, on a size 6 AWG THHN copper conductor is permitted to be no more than ______ where connected to a fusible disconnect switch with terminals rated at 75’C.
75 amperes
65 amperes
60 amperes
55 amperes
=65 amperes
Table 310.15 lists the ampacity of size 6 AWG copper 75’C rated conductors to be 65 amperes.
Many circuit breakers and disconnect switches now have dual ratings marked 60/75 deg. C
Many conductors now are dual rated such as THWN/THHN. The ampacity rating is based on the THWN 75 deg. C values, but the derating factor(s) may be based on the THHN 90 deg. C values.
The allowable ampacity of types NM, NMC, NMS, cable shall be in accordance with the 60 deg. C conductor temperature rating. The 90’ deg. C. rating shall be permitted to be used for ampacity derating purpoes, provide the final ampacity does not exceed that for a 60’ deg C rated conductor 334.80
A size 12/2 AWG w/ ground copper NM cable is to be installed in an attic of a dwelling where the ambient temperature is 125’ F. Determine the ampacity of the cable
- 8 amperes
- 5 amperes
- 6 amperes
- 4 amperes
=22.8 amperes
Ampacity of 12 AWG at 90 deg. C before derating = 30 amperes
30 amperes x .76 (temperature correction) = 22.8 amperes
Under this condition, the ampacity of 22.8 amperes is NOT permitted, because this value is more than the 20 ampere rating of the 12 AWG conductors at the 60 deg. C temperature rating
A size 10/3 AGW w/ground copper NM cable is to be installed in the crawl space of a dwelling where the ambient temperature is 100 deg. F. Determine the ampacity of the cable.
- 6 amperes
- 4 amperes
- 3 amperes
- 0 amperes
=30 amperes
Ampacity of 10AWG at 90 deg. C before derating = 40 amperes
40 amperes x .91 (temp correction) =36.4 amperes
Under this condition the ampacity of 36.4 amperes is NOT permitted, because this value is more than the 30 ampere rating of 10 AWG conductors at the 60 deg. C rating.
True or False: When there are more than 3 current-carrying conductors in a raceway or cable, the ability of the conductors to dissipate heat is increased.
False: When there are more than 3 current-carrying conductors in a raceway or cable, the ability of the conductors to dissipate heat is REDUCED.
True or False: When a 3 current carrying conductor in a raceway or cable is longer than 24 inches, the allowable ampacity of each conductors shall be reduced.
True: When there are more than 3 current-carrying conductors in a raceway or cable, the ability of the conductors to dissipate heat is increased.