DC Flashcards
Loss of S016
- Main Generator PCB’s fail to open (4 mins to manually open)
- Station Service 4160VAC loads DO NOT auto transfer (NO CONTROL POWER)
- RCIC not available
- Rx Scrams and Recirc Pumps Trip (>27.6% RTP)
- RFP’s can not be tripped from MCR
Loss of S017
- Control power is lost to BOTH ASD bkrs (neither pump can be tripped from the MCR, shutdown button still functions)
- HPCI is not available and all indication for DC power loads are lost
- No fast transfer of 4160 VAC E/F/G
- C32-R606C – “C” GEMAC RWL Indicator lost
- C32-R605C – “C” GEMAC Pressure Indicator lost
- C32-R603C – “C” Steam Flow Indicator lost
- C32-R604C – “B” Feed Flow Indicator lost
- Lose ECCS cabinets P926 & P928
Loss of S001
• RCIC not available
• Rx Instruments similar to R22-S016
• Loss of control power to 4160 ‘A’ and ‘B’ supply breakers
• Loss of control power to 600 ‘C’
• Loss of RFPT A Control Power. RFPT 2A will not trip manually or automatically due to loss of power to its trip circuit.
- SS Bus Fast Tx lost
Loss of S002
- HPCI not available
- Rx Instruments similar to R22-S017
- Loss of control power to 4160 ‘A’, ‘B’, ‘C’, and ‘D’ feeder breakers
- Loss of control power to 600 ‘D’
- Have to use ASD stop push buttons. Cant use switch in MCR
- Trip logic for B31-F031 (recirc pump discharge valve)
Loss of S003
- Control power is lost to the Exciter Field Breaker, however, the breaker remains closed
- Loss of control power to 4160 ‘C’ and ‘D’ supply breakers
- Loss of control power to 600 ‘A’, ‘B’, ‘AA’, and ‘BB’
- Loss of RFPT B Control Power
- RFPT & Main Turbine Trip Relays
- Loss of Fast Transfer Logic for 4160VAC A/B/C/D
- Lose generator runbacks
Loss of S004
- ‘A’ EDG will not auto or manual start
- ‘A’ EDG output breaker will not tie
- ARI will not initiate (S005 on U1)
- RHR ‘A’ and ‘D’ cannot be started from the MCR
- CS ‘A’ will not auto start
- Loss of control power to 4160 ‘E’
- Loss of control power to RHRSW C, PSW C, RHR D, CRD A
Loss of S005
Loss of U1 ARI
1B EDG Start Logic and Brkr control
Loss of S006
- ‘C’ EDG will not auto to manual start
- ‘C’ EDG output breaker will not tie
- RHR ‘B’ and ‘C’ will not auto start
- RHRSW ‘B’ and ‘D’ cannot be started from the MCR
- CS ‘B’ will not auto start
- Loss of control power to 4160 ‘G’
- Loss of control power to PSW D, RHR C, CRD B
Purpose
Prove uninterruptible power to key components
Battery Limits
125/250 - 3 sets for 2-4hrs
24/48 - 3 sets for 8hrs
Vital AC - 2hrs
Float Charge
Battery Charger voltage output = battery voltage
Equalize Charge
Battery Charger voltage output slightly > battery voltage
Indication of a ground
Requires a minimum of 19,000 ohms