CP- Containment hydrogen purge Flashcards
What are the two subsystems of the CP system? Purposes?
Refueling Purge Subsystem – provides ventilation air for personnel comfort when the plant is shutdown during refueling operations and maintenance
Power Access Purge Subsystem – provides ventilation air to allow operator access for limited periods during power operation. Also used to control pressure in the containment by periodically venting a portion of the containment air to the plant vent
What provides cooling in the Refuel Purge AHU and how is it controlled?
Normal Chilled Water
Automatically controlled to maintain inlet air temperature at a preset value
When does the WC system provide cooling to the Power Access Purge AHU?
When outside temperature is too high
How does Instrument Air interact with the CP system?
Provides air for the operation of dampers, valves, controllers, and air operated containment isolation valves in the CP system
How is the system affected by a loss of IA?
Air operated dampers and valves fail closed, which will cause associated AHUs, AFU, supply or exhaust fans to trip
When is the Refueling Purge Supply AHU operated and where is it located?
Only in Mode 5 or 6
Located on the Aux Building roof
How does the Power Access Purge Supply AHU handle outside temperature being too low?
Electric heating coils are energized
Where is the Power Access Purge Supply AHU controlled from? Where is it located?
Control Room
aux. building roof
Why is there a heater installed up stream of the Power Access Purge Normal Exhaust AFU?
To maintain humidity low to prevent damage to the charcoal filter down stream
Concerning the Power Access Purge Normal Exhaust AFU, what is the purpose of the charcoal filter and second HEPA filter?
Charcoal filter removes fission product gases (mainly iodine) by adsorption
Second HEPA filter removes any carbon dust emitted from the charcoal filters
Which radiation monitors continuously monitor Purge discharge flow to the plant vent?
RU-37 and RU-38
What happens if monitors RU-37 and RU-38 detect excessive radiation?
Initiate a CPIAS and stop the purge
What will stop a containment purge besides RU-37 and Ru-38 detecting radiation?
CIAS
The Power Access Purge has what two modes?
Venting or depressurization mode
Power Access Purge mode
When would I use Venting mode?
Utilized to depressurize the containment atmosphere during normal power operation or prior to power access purge