CONTROLS Flashcards

1
Q

Because most induction motors require additional starting torque _________ are implemented.

A

Start windings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Shaded-pole motors can most easily be identified by

A

A heavy copper band

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The primary application for shaded-pole motors would be

A

When low start torque is required

When low run torque is required

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

One of the most popular motors used in the HVAC industry with moderate starting torque and good running efficiency is the _________ motor.

A

Permanent split capacitor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Identify the most rugged and reliable motor used in the industry which operates without the assistance of start components

A

Three phase-motor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Identify the difference between a three pole contactor and a three pole magnetic starter

A

A magnetic starter has an overload circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

In identifying the common, start, run terminals of a split phase motor; terminal A to B = 10 ohms, terminal A to C = 3 ohms, and terminal B to C = 7 which terminal is common

A

Terminal C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Electronically commutated motors alter the output drive speed. This is accomplished by altering

A

Electrical frequency

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

To safely test a motor capacitor a technician should

A

Discharge the capacitor with a resistor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a compressor with an internal motor overload opens, what should the technician do before condemning the compressor

A

Allow the compressor to cool down

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

An air conditioning system uses a 24 volt control thermostat to maintain room temperature. The same system also utilizes a low pressure switch.
What is the most likely purpose of this low pressure switch?

A

To cycle the compressor off if the system runs low on

charge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A roof top air conditioning system with a defective condenser fan motor would be protected by

A

A high pressure safety cut out switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A roof top air conditioner operating with a pressure type fan control maintains a minimum head pressure

A

During low ambient conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When adding central air conditioning to an existing heating system a fan relay center control (or fan relay) may need to be added, this relay would be controlled by which thermostat lead?

A

G- Green

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

To prevent room temperature “overshoot” most HVAC room thermostats employ a

A

Heat anticipator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Solenoid valves are

A

Magnetically controlled

17
Q

A potential magnetic relay is controlled by the back electromotive force created by

A

The start winding

18
Q

After a defrost timer control initiates a defrost period the defrost cycle may terminate by means of

A

Time, pressure, or temperature

19
Q

A solid state starting relay is employed with fractional horse power compressors. after the motor starts the relay

A

Increases in resistance disconnecting the start winding

20
Q

When troubleshooting a capacitor-start-capacitor- run motor and the technician finds the start capacitor and the run capacitor defective the technician must also check the operation of

A

Potential magnetic relay

21
Q

Most low voltage HVAC room thermostats can adjust temperature over shooting, this adjustment would be a function of

A

Heat anticipator

22
Q

A current sensing lockout relay is an overload device that senses the current draw of the compressor through the ______________

A

Lockout loop

23
Q

When diagnosing the compressor contactor coil a proper resistance reading would be

A

45 OHMS

24
Q

The best method to test the condition of the contacts in a compressor contactor would be

A

Visual inspection

25
Q

When troubleshooting a fuse with a volt meter a reading of line voltage across both ends of the fuse would indicate the fuse is

A

Open

26
Q

Application: Residential air conditioning system
Type of Equipment: Gas furnace with air-cooled condensing unit
Complaint: No cooling
Symptoms:
1. Correct line voltage to furnace and condensing unit.
2. Thermostat calling for cooling.
3. Condensing unit receiving 24 volts.
4. All safety controls in condensing circuitry are closed.
5. Contactor coil resistance reading is 0 ohms.

A

Shorted contactor coil

27
Q

Application: Residential conditioned air system
Type of Equipment: Fan coil unit air-cooled condensing unit
Complaint: No cooling
Symptoms:
1. Correct line voltage to furnace and condensing unit.
2. Thermostat calling for cooling.
3. Compressor contactor closed.
4. Compressor and condenser fan motor extremely hot.
5. Condenser fan motor resistance readings are C to R = 6 ohms. C to S + 28 ohms, and R to S =34 ohms.
6. Compressor run capacitor in good condition.
7. Compressor motor and bearings in good condition.
8. Condenser fan blade turns with ease.
9. Condenser fan turning slower than normal until overload cuts out.

A

Defective condenser fan motor capacitor

28
Q

Application: Residential conditioned air system
Type of Equipment: Packaged air conditioner
Complaint: No cooling, no indoor fan operation
Symptoms:
1. Line voltage available to unit.
2. Closing of thermostat fan switch causes no action.
3. Voltage at terminals C to R on unit low-voltage terminal board is 0 volts.

A

Open transformer circuit