Heating and power boiler clearances?
With manhole 84”
Without manhole 36”
Power boiler clearance?
36”
Boilers bottom open clearance, how much clearance?
12”
When does an electric boiler require 2 blow down?
When the nominal water content exceeds 100 gallons
What is the minimum size of a heating boiler blow down?
3/4” is the minimum. But…
If the capacity does not exceed 25 gallons 3/4”
Exceeding 25 gallons - falls under table 3.7.7.2 and is based on min required safety valve capacity.
Up to 500 - 3/4" 501-1,250 - 1 1251-2500 - 1 1/4 2501-6000 & 1 1/2 6001+ - 2
Power boiler min feed water piping size
1/2” up to 100 sq ft
3/4” greater than 100 SQ ft
Minimum and max safety relief valve size for a steam heating boiler?
What about HWH, HWS, and potable hot water heaters?
Steam - 1/2” to 4”
HW H/S greater than 15,000 BTU/hr - 3/4” to 4”
HW H/S up to 15,000 BTU/hr - should be 1/2”
Potable water heaters - T&P at least 3”