At what pressure will the standby hot well pump automatically start?
130# U1
110# U2
What pressure will automatically start the standby condensate booster pump?
325#
What is the tech spec for the CST minimum level?
182,000gal. This allows for 9hrs steaming through the PORV’s or 2hrs then cool down to mode 4.
When do we overboard and why?
When we are on aux feed. This is because we are taking a suction on the CST not the hot wells.
What is the biggest loss of condensate inventory?
Blowdown.
What is the power supplies to the hot well pumps?
Middle 1-1A / 2-2A
South 1-1C / 2-2C
North 1-1D / 2-2D
Why did we remove fuses from CMO-55 and where are they stored?
So we don’t drain the CST on a hot smart short. They are located in the SM office.
What is the power supplies to the condensate booster pumps?
Middle – 1-1A / 2-2A
South-1-1C / 2-2C
North-1-1D /2-2D
If you isolate a string of low pressure heaters what is the flow through the bypass?
20% goes through the bypass CRV-224, 80% goes through the In service string.