Complete the following statement, “On the same circuit, do not mix convectors with?
Freestanding cast-iron radiators
Where a building trap is installed, a fresh air inlet shall be installed on the building drain upstream of the trap:
- as close as possible to the trap
- within 1.2m of the trap
IR thermometer size ratio equals 10:1, at 1/8 a meter away, the spot size will be?
10:1 = Distance (D) : Spot (S)
Ex: 1m (D) => 0.1m (S)
How many Fixture Units are you allowed to drain into a sows if the stack was to act as a relief vent?
6 FU
The formula to calculate USGPM when the BTU heat requirement is known is?
Delta T x 60 x 8.33
the max number of Fixture Units that may be connected to a horizontal branch off a 2” stack that passes through 5 storeys is?
6 FU
(question 25 on DWV exam)
Max number of Fixture Units that may be connected to 3” stack of 60m in developed length is?
102 FU
(question 26 on DWV exam)
What method of heat transfer does a fin tubed baseboard utilize in a heating room?
- Convection –> convection currents
(Convection is mostly used) - Conduction –> via aluminum / copper fins
(very little radiation)
In testing a 5 storey (15 m) stack with water, the pressure at the base of the stack on the gauge would read:
147 kPa
(Q 36 DWV exam)
Thermistors are what?
are more sensitive to small temperature change
Have a quick response time
(a resistance sensor that changes its resistance in non-linear way)
Heat intensity is measurable with?
a degree fahrenheit
(Temperature)
Any vent pipe shall extend vertically above the flood level rim of a fixture:
to adjust above the flood level rim before connecting to another vent
Where is the ideal location for a pump on boiler?
Immediately downstream of the point of no pressure change
What fixture is popular in Europe that is designed for washing genitals?
Bidet
A vertical pipe means what?
45 degrees from the vertical
What independent, self-funded organized group oversees safe installation system equipment including gas across BC?
TSBC (technical safety BC)
A roof vent terminal terminating into open air shall be located at a distance not less than?
3.5m away from any window, door or other opening
A vent shall be installed to protect the base of every soil or waste stack that passes through more than?
4 storeys
Total fall of a fixture drain from the trap weir to the vent fitting shall not exceed?
two times the diameter of the pipe
What is the most common temp drop used in heating (in celsius)
11 C (20 F)
Also called design temp difference (delta T)
The max length of an offset on a 4” sows serving as a wet vent is?
max 2.5m
(Q 38 DWV exam)
Rate of discharge through 1/4 fixture outlet pipe is called?
Fixture Unit
Max permitted length 3/8 supplied tube for fixture?
Cold water supply for toilet–> 1/2” (13mm) copper or PEX supply pipe w/ 3/8” (9.5mm) flexible tube or hose.
Fixture supply tubes: 3/8” OD and 30” in length
pg 109 C-1
In the production of fixtures, what material is most difficult to form?
Stainless steel
A 2” trap not listed in table 2.4.9.3 has a hydraulic load of?
3 FU
(question 24 on DWV exam)
DMM (digital multi-meter): to measure amperage requires meter to be connected (to what or how?)
Requires connecting the meter in series w/ the circuit being tested.
(Have to disconnect a wire from terminal / connection of the test leads bn wire end / terminal it was removed from. becomes part of the circuit)
Max water temp permitted in bathtub or shower head?
49 C
(120 F)
What is the min length of a trap arm serving a lavatory?
2 1/2”
- find fixture outlet pipe size and code states length = min twice the size of fixture drain. (2.5.6.3 - a)
(Q 40 DWV exam)
A kitchen sink with a domestic type garbage disposal unit installed on it has a hydraulic load of?
1 1/2 FU
(question 23 on DWV exam)