Chapter 9 Tables And Annex C Flashcards

1
Q

Maximum conductor fill rate for all types of conduit over 24 inches in length with over two conductors including cellular concrete raceway is

A

Chapter 9 table 1

40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In electrical tubing nipple is defined as tubing blank or less in length and may be filled to a maximum percentage of the total available internal square inch area of the tubing

A

Chapter 9 table 4

24” and 60%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How many number 8THHW compact conductors can be placed inside 1 inch EMT trade size conduit

A

Annex c table C1 A

6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What size RMC pipe is needed for the total square inch area include installation of four number 8PHHN and six number 10 THHN wires

A

Table 5 and table 4

1 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many number 10 RHW conductors can be placed inside a 1 inch ENT pipe

A

Annex c table c2

10

How well did you know this?