Chapter 2 Wiring And Protection Flashcards
A 240 V boat hoist receptacle Hass to be
210.8C
GFI protected
Non-dwelling unit receptacles installed in/on the _____ shall be GFI protected
210.8B
Rooftops, outdoors, sinks
What is the minimum rating for a laundry circuit in a single-family dwelling
210.11 C2
220.12 J
220.52 B
20 A 1500 W
A receptacle on an individual branch circuit can be rated for what percent
210.22
100%
Branch circuits_____ Or larger supply only non-lighting loads
210.23D
50 A
What type of lampholder shall be connected to a load in excess of 20 A
210.24
Heavy duty
The laundry outlet shall be installed within how many feet of the designated appliance location
210.50 C
6 feet
Receptacle outlet in the floor shall not be counted as part of the required number of wall receptacle outlets unless located within how many inches of the wall
210.52.A3
18 inches
What is the minimum number of small appliance circuits free single-family dwelling
210.52B1
Two circuits
Other than countertop appliances what type of device is allowed to utilize the small appliance circuit in a single-family dwelling
210.52B1 and b2
Refrigerator, Clocks, cooking equipment
Receptacle outlets show me installed so that no point along the wall line of a kitchen countertop is more than_____ inches measured horizontally from a receptacle outlet in that space
24”
What is the minimum length of a countertop in a kitchen that requires the installation of a receptacle
210.52C1
12 inches
Island countertops with a minimum dimension of 12 wide by 24 deep must have at least____ receptacle outlets
210.52C2
One
18 feet of shell window requires how many receptacles above window
210.62
2
What is the maximum distance from a rooftop unit that the rooftop GFI service receptacle shall be located
210.63
25 feet
A conference room is 250 ft.² and has 12 1/2 foot wall. How many floor receptacles are needed
322 ft.² or less is one outlet
1
Does a vehicle garage door require illumination under the illuminated entryway rule
210.70 A2
Man door
Service door
No
General branch circuit lighting load prehospital shall be calculated at_____ watts per square foot
220.12
Two watts per square foot