Chapter 3 wiring Methods And Materials Flashcards
The minimum distance in the edge of a stud must be from the edge of a hole for NM cable is
300.4A2
Inch and a quarter
When direct burial exits the ground what shall it be enclosed in
300.5D 1-4
Raceway 
At what rated voltage does direct burial cable have to be shielded
310.10 F
2,000v
What is the smallest size conductor you can run in parallel
310.10h1
1/0
What is the minimum size wire I need to supply a 100 amp single phase 3 wire main service on a mobile home
4 awg copper
310.15b7
What is the overcurrent protection for eight number 12 THHN conductors in a half inch pipe
310.15 B3 a
20 a
A single-family dwelling has a 100 amp service. What size feeder will be required to supply a 75 amp electric space heater and a 25 AMP air conditioner
310.15 B 16
Number 2 copper
What is the minimum size THW conductor that can be used to supply a 200 amp a single phase commercial building
310.15 B 16
3/0 copper
What type of conductor is rated for direct burial
310.104A
340.10
UF
When using a round box where conductors Orkin nectars requiring the use of lock nuts or bushings are to be connected to a part of the box can they be connected
314.2
Side of the box
Type NM cable shall be approved for installing under the lower edges of a joist in crawlspace is if the wire is at least 3-_____awg
8
 334.15 C
Or 2-#6
What is the required free space in a junction box for a number 10 conductor
314.16 B
2 1/2 in.³
What is the maximum number of number 14 conductors allowed in a 4” x 2 in an 8 inch metal octagon trade size box
314.16 A
10

Type NM cable shall be secured how many inches from a non-metallic box if there is no clamp
314.17 C
8 inches
A fixture box Shall be independently supported if the fixture weighs more than how many pounds
314.27 a2
50 pounds