Chapter 3 wiring Methods And Materials Flashcards

1
Q

The minimum distance in the edge of a stud must be from the edge of a hole for NM cable is

A

300.4A2

Inch and a quarter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When direct burial exits the ground what shall it be enclosed in

A

300.5D 1-4

Raceway 

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

At what rated voltage does direct burial cable have to be shielded

A

310.10 F

2,000v

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the smallest size conductor you can run in parallel

A

310.10h1

1/0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the minimum size wire I need to supply a 100 amp single phase 3 wire main service on a mobile home

A

4 awg copper

310.15b7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the overcurrent protection for eight number 12 THHN conductors in a half inch pipe

A

310.15 B3 a

20 a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A single-family dwelling has a 100 amp service. What size feeder will be required to supply a 75 amp electric space heater and a 25 AMP air conditioner

A

310.15 B 16

Number 2 copper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the minimum size THW conductor that can be used to supply a 200 amp a single phase commercial building

A

310.15 B 16

3/0 copper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What type of conductor is rated for direct burial

A

310.104A

340.10

UF

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When using a round box where conductors Orkin nectars requiring the use of lock nuts or bushings are to be connected to a part of the box can they be connected

A

314.2

Side of the box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Type NM cable shall be approved for installing under the lower edges of a joist in crawlspace is if the wire is at least 3-_____awg

A

8

 334.15 C

Or 2-#6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the required free space in a junction box for a number 10 conductor

A

314.16 B

2 1/2 in.³

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the maximum number of number 14 conductors allowed in a 4” x 2 in an 8 inch metal octagon trade size box

A

314.16 A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Type NM cable shall be secured how many inches from a non-metallic box if there is no clamp

A

314.17 C

8 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A fixture box Shall be independently supported if the fixture weighs more than how many pounds

A

314.27 a2

50 pounds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Floor boxes must be made of what

A

UL listed

17
Q

What is the maximum distance from a panel that a type M I cable must be secured

A

332.30

6 feet

18
Q

What is the temperature rating for the conductor of type NM cable

A

334.80

60°C

19
Q

What type of cable is not approved for service entrance cable 

A

340.12

UF

20
Q

10 feet of Equipment grounding conductor cannot be made of what

A

348.20A
250.118.7b

FMC

21
Q

What is the maximum distance between supports for a 1 inch rigid PVC

A

352.30

3 feet

22
Q

What is the expansion rate of 250 feet of PVC that goes from a temperature change of -20 Fahrenheit to 80 Fahrenheit

A

352.44

10.15

23
Q

Type RTRC shall be permitted to be unsupported where the raceway is not more than______ Long and remains in unbroken links and terminated in an outlet box

A

355.30a

3 feet

24
Q

What is the maximum number of conductors allowed in an auxiliary gutter

A

366.22 a

30

25
Q

What is found in chapter 3

A

Anything dealing with raceways; distance between support, termination point, Installation is found here.

Ampacity tables

393 Low voltage suspended ceiling power distribution system