The type of gauge that is commonly used to indicate steam pressure inside a boiler is the ______gauge
a. Safety
b. Gauge glass
c. Bourdon tube
d. Directly attached
c
The lowest visible part of the water gauge glass will be above the ________recommended by the manufacturer.
a. Middle try cock
b. Fire line
c. Top of the firetubes
d. Lowest permissible water level
d
The blowoff connection on a boiler is made:
a. just below the feedwater inlet
b. At the lowest permissible water level
c. At the lowest point of the boiler
d. Just below the safety valve connection
c
During a safety valve pop test on a steam boiler
a. A 5th Class Power Engineer is authorized to put jumper wires on the electrical terminals of the pressure controllers
b. There should not be more than 75% of the safety valve set point on the boiler
c. The safety valve is acceptable providing it opens within plus-or-minus 20% of its setpoint
d. The steam discharge and feedwater supply valves should be closed
d
The type of gauge that is commonly used to indicate steam pressure inside a boiler is the ______gauge
a. Directly attached
b. Bourdon tube
c. Safety
d. Gauge glass
b
One purpose of a vent valve on a steam boiler:
a. Verify the boiler water level
b. Allow flue gases to pass up the chimney
c. Relieve pressure in case of over-firing
d. Allow air to escape when the boiler is being filled
d
One main purpose of a water column is to:
a. Provide more water volume in the boiler
b. Bring the gauge glass closer to the operator
c. Ensure that the water level is above the Lowest Permissible Water Level
d. Reduce turbulence in the gauge glass
d
To protect against an over-pressure failure, all steam boilers must be equipped with one or more:
a. Safety valves
b. Combustion controllers
c. Pressure controllers
d. Vent valves
a
On a steam boiler, the feedwater connection must be made:
a. With a stop valve close to the boiler and a check valve between the stop valve and the boiler
b. At the lowest point of the boiler
c. With a check valve close to the boiler and a stop valve between the check valve and the boiler
d. Above the lowest permissible water level
c
Main boiler stop valves should be:
a. Outside stem & yoke globe valves
b. Plug valves
c. Outside stem & yoke gate valves
d. Slow opening valves
c
On a high pressure steam boiler fitted with a quick opening and a slow opening blowdown valve set, the proper blowdown operation sequence is:
a. Operate with the quick opening valve open at all times so that you can blowdown with the slow opening valve
b. Open the slow opening valve, then open the quick opening valve
c. Crack open each valve starting with the quick, then fully open both valves starting with the quick
d. Open the quick opening valve, then open the slow opening valve
d
Try cocks are:
a. A secondary means of determining the boiler water level
b. Not allowed on water tube boilers
c. A secondary means of blowing down the boiler
d. A primary means of determining the boiler water level
a
A siphon protects the steam pressure gauge from:
a. Corrosion
b. High temperature of steam
c. Over-pressure
d. Vacuum
b
A pressure gauge can most accurately be calibrated by using:
A. A test gauge comparator
B. A dead weight tester
C. Another pressure gauge
D. The Inspector’s test gauge
E. Hydraulic comparator
b
A valve commonly used as a boiler stop valve is the _____ valve.
A. Needle
B. Gate
C. Butterfly
D. Plug
E. Ball
b