Ch. 5 Quiz Flashcards

1
Q

propane tank must be __ft. away from a source of ignition

A

10ft.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

propane tank must be __ft. away from an air intake

A

10ft.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

propane tank must be __ft. from an opening of a building

A

5ft.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

1st stage regulator is responsible for… (LP)

A

variance in tank pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

inlet pressure of 1st stage regulator (LP)

A

20 - 80 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

outlet pressure of 1st stage regulator (LP)

A

10 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

2nd stage regulator is responsible for… (LP)

A

variance in down stream pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

inlet pressure of 2nd stage regulator (LP)

A

10 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

outlet pressure of 2nd stage regulator (LP)

A

11 - 14” w.c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

max lockup pressure

A

120% of the 2nd stage regulator’s outlet pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

bounce of 2nd stage regulator can be up to..

A

1” of w.c (.5 up or .5 down)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

the allowable pressure drop for 2nd stage regulator

A

.5” w.c

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

pressure available @ appliance

A

No more than .5” w.c less than 2nd stage outlet’s pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What code covers first and second stage regulators (LP)

A

NFPA 58

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

NFPA 58 states what about single stage regulation

A

single stage regulation shall not be installed in fixed piping systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

what is required when the supply pressure is higher than what the appliance is designed for

A

Vent Limiter ( line gas pressure regulator)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

inlet of 1st stage regulator pressure

A

usually 20 - 80 but less than 312 psi

18
Q

rubber diaphragm in a regulator senses..

A

gas pressure

19
Q

the lever actuator and seat disk do what…

A

meter the amount of gas

20
Q

what does the spring in a regulator do..

A

controls the flow of gas

21
Q

foreign material between inlet nozzle and seat disk causes …

A

no lockup and creeping (lg rise over 5 min)

22
Q

a relief valve is required on..

A

final stage gas regulators

23
Q

what does the vent of the final stage regulator do

A

vents excessive gas pressure

24
Q

obstruction of regulator vent causes what?

A

prevention of excessive pressure relief and prevention of diaphragm

25
regulator vents shall prevent what
``` water from entering (face down) insects (screen) foreign materials (paint) ```
26
regulator vent shall terminate __ft from source of ignition (LP)
5'
27
regulator vent shall terminate __ft from source of ignition (NAT)
4'
28
when terminating a reg vent from indoors to outdoors vent must terminal how?
90 degrees vent down with screen installed
29
gas meters must be readily accessible for...
examination reading replacement maintenance
30
gas meters must be identified by..
metal tag or other perm. means of designating the building or part of building it supplies
31
3 factors that determine how much a customer should be billed
heat content - (sgs knows the blend) inlet pressure - (meter adjusted at install) temperature - (meter/sgs adjust meter for temp)
32
meter set (meter & reg combo) located __ ft from opening
at least 3’
33
what shall not be used in gas piping systems
cast iron
34
what kind of black iron shall be used
min. sched 40
35
when will plastic tubing be used..
outside underground only
36
pvc used on outdoors regulator vents shall be what
UV resistant (electricians PVC)
37
when metallic piping is used outdoors what must be done?
protected usually paint
38
what kinds of teflon tape can be used as a thread joint compound?
blue monster or other approved material (UL listed)
39
Four acceptable means of joining metallic pipe
Threaded Flanged Brazed (excess of 1,000) Welded
40
largest size pipe that can be threaded without approval from ahj is..
4 inches
41
When pipe is over 4 inches the two methods of joining are
Flanged and welded