Boilers Flashcards

1
Q

no visible level in visible gauge glass

A

turn off flame to prevent further damage.
blow down the guage glass to confirm the low level.
if still low shut down boiler, let it cool down before further investigation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

safety valve lifting

A

there is too much pressure in the boiler, check the pressure guage, check the guage glass, operate the easing gear on both safety valves to make sure they are fully open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

excessive smoking during firing

A

incorrect fuel to air ratio. so first check the air damper to make sure that the damper positioning is correct for the amount of fuel. check the fuel pressure is correct for the amount of air, and finally check that the fuel temperature is correct for atomisation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

excessively high chloride content of boiler water

A

identify the source, isolate the source. possibly condenser. do blow down tests, refill with clean uncontaminated water. retest to check if the source of contamination was correct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

four test that can be done on the boiler water

A

chloride
P alkalinity
Total alkalinity
Phosphate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

high level

A

boiler will cut out more often

will cause priming where water is carried over into the steam line, also water hammering.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

low level

A

boiler has to run for longer, boiler efficiency drops as it has to run for longer to produce steam

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

low low level

A

causes over heating, it will also lead to high thermal stress

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

blow down of the guage glass

A
close water and steam
open drain
open steam
close steam
open water
close water and drain
open water allow to fill 
open steam
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

four reasons for the boiler feed pump failing to maintain boiler water level

A

blow down valve open
hot well low level
faulty feed valve
water locking, water has turned into steam and it can not be pumped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

how do you start up a boiler

A

fill with water
check safeties e.g. flame failure, high level low level
purge boiler
start up slowly to prevent thermal shock
at 1 bar close vent to keep efficency in the boiler
steam should be coming out of vent before closing
build up the water pressure

when shutting down open vent again to prevent vaccum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

8 boiler mountings

A
feed water valve
main steam stop valve
pressure guage
blow down valve
scum valve
2 safety valves
2 guage glasses
sample cocks
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

2 consequences of not treating boiler water

A

scaling

corrosion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

four circumstances where fuel supply to the burners would be cut off

A

low level alarm
high pressure alarm
flame Eye failure
failure to purge loss of control of dampener

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

water level indicators mounted on the boiler?

A

guage glasses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

two reasons for two gauge glasses are fitter

A

redundancy

ensure true reading