BAL-003 Flashcards
Balancing power is provided by the ___ energy stored as ___ inertial energy in the rotating mass of the generator.
kinetic
inertial
___ response and ___ response occur when there’s a loss of generation to counter the frequency change.
Load
Governor
Load Response (Load dampening)
Occurs when drop in frequency causes motor frequency to drop, reducing motor load. 1% drop in frequency results in 3% drop of motor load. 1% drop in frequency causes 2% drop total load.
Governor Response
Generation response inversely to direction of frequency change through governor action. 3-4 second delay.
What is the largest contributor to frequency response?
Governor Response
What does the governor regulate?
Primary mover
How do you find governor droop?
Net frequency change/60Hz
What does the Governor Droop allow?
Parallel operations of many different size generators
Generators respond to frequency disturbances in ___ to their size if they have ___ Governor Droop.
proportion
the same
How do you calculate MW change per frequency change using Governor droop?
Ratio: max MW change/max frequency change = x MW/frequency change
The Governor deadband’s frequency change is ___.
0.036Hz
In addition to Governor response, the ___ will pulse generators to increase generation in the event of frequency ___.
AGC
drop
Frequency Response Obligation (FRO) is calculated ___ based on the Balancing Authority’s percentage of the ___ and ___ in the Interconnection it belongs to.
Annually
generation
load
Define Frequency Response Measure (FRM)
Median of all Frequency Responses observed for the frequency deviation events identified by NERC for the previous year.
BAL-003 ensures that BA’s frequency response is sufficient to maintain Interconnection Frequency Response ___ or ___ than the Interconnection Frequency Response Obligation.
equal to
more negative