Bacnet Flashcards
What does BACnet stand for?
Building Automation and Control Network
BACnet is a communication protocol for building automation and control networks.
What type of cable is required for BACnet IP connections to the CORE Unit Controller?
CAT5 or CAT6 cable.
What does the CORE Unit Controller BACnet interface allow?
Communication between the CORE Unit Controller and a BACnet MS/TP or IP network.
What is the device profile that the CORE Unit Controller BACnet interface communicates with?
BACnet Application Specific Controller (B-ASC) device profile.
What certification does the CORE Unit Controller BACnet interface hold?
Certified to ANSI/ASHRAE 135-2008 and is BTL Listed.
How can you pair the Lennox® CORE Service App to the CORE Unit Controller?
The app can discover the CORE Unit Controller if within 50 feet and displays units by signal strength.
What is the first step to enable the BACnet interface on the CORE Unit Controller?
Use the CORE Service App and go to RTU MENU > SETUP > INSTALL.
What is a common integration guideline for the CORE Unit Controller?
This device does not support Change of Value (COV).
List two recommended objects for writing generic applications for single-zone integration.
- AO102 (Outdoor Air Min Pos Control)
- AO104 (Occupancy Scheduler Control)
What should be done every 2 minutes to the Network Inputs?
Write to the Network Inputs (AO111-113).
What are the recommended objects for reading unit status?
- AI232 (Unit Status)
- AI239 (Space Temperature)
- AI240 (Discharge Air Temperature)
- AI244 (Outside Air Damper)
- AI250 (Supply Fan Status)
What is the maximum number of devices that can be included per MS/TP network segment?
32 CORE Unit Controller BACnet® interfaces.
What is the maximum cable length for BACnet MS/TP without a repeater?
4000 ft.
When should a 120 ohm resistor be used in BACnet MS/TP connections?
At the end of a daisy-chain configuration.
What is the recommended baud rate for BACnet MS/TP?
38.4 kbps.
What should be avoided to minimize communication compatibility problems?
BACnet gateways or BACnet devices that are NOT BTL listed.
Fill in the blank: The operating temperature range for the CORE Unit Controller is _______.
−40F to 155F.
True or False: The CORE Unit Controller BACnet interface requires Lennox proprietary software to function.
False.
What is the device Max_Master property for the CORE Unit Controller?
127.
What is the purpose of the CORE Service App in relation to the CORE Unit Controller?
To enable the BACnet interface and configure settings.
What is a key configuration step for BACnet MS/TP?
Set the BACnet MAC Address unique for each CORE Unit Controller on the network.
What is the maximum baud rate recommended for BACnet units?
9.6K
How many Lennox BACnet units and devices per router are recommended for higher baud rates?
20 Lennox BACnet units and 30 devices per router
What does Lennox recommend regarding the use of repeaters in BACnet networks?
Lennox does not recommend the use of repeaters due to noise amplification.