Type AC cable is permitted in _____ installations.

A

Exposed/Concealed work, cable trays, dry locations, embedded in plster finnish on brick or other masonry (except wet/damp locations) run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture of dampness.

320

Armored cable : Type AC

320.10 Uses Permitted

Type AC cable shall be permitted as follows

(1) For feeders and branch circuits in both exposed and concealed work
(2) In cable trays
(3) In dry locations
(4) Embedded in plaster finish on brick or other masonry, except in damp or wet locations.
(5) To be run or fished in air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Armored cable shall not be installed _____.

A

Where subject to physical damage, in damp or wet locations, In air voids of masonary block or tile walls where such walls are exposed or subject to excessive moisture or dampness, where exposed to corrosive fumes or vapors, Embedded in plaster finish on brick or other masonry in damp or wet locations.

320

Armored cable: AC Type

320.12

Uses Not permitted

(1) Where subject to physical damage
(2) In damp or wet locations
(3) In air voids of masonary block or tile walls where such walls are exposed or subject to excessive moisture or dampness
(4) Where exposed to corrosive fumes or vapors
(5) Embedded in plaster finish on brick or other masonry in damp or wet locations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Exposed runs of type AC cable can be installed on the underside of joists where supported at each joist and located so they are not subject to physical damage.

True or False

A

True

320

AC Cable : Type AC

320.15

Exposed Work

Exposed runs of cable, except as provided in 300.11(A), shall closely follow the surface of the building finsih or of running boards. Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Type AC cable installed through, or parallel to, framing members shall be portected against physical damage from penetration by screws or nails.

True or False

A

True

320
AC cable : Type AC

  1. 23 (B)
  2. 23 In Accesible Attics.

(B) Cable installed Parallel to framing members.

Where the cable is installed parallel to the sides of rafters, studs, or floor joists, neither guard strips nor running boards shall be required, and the installation shall also comply with 300.4(D).

300

Wiring methods

  1. 4(D)
  2. 4 Protection Against Physical Damage.

(D) Cables and Raceways Parallel to Framing Members and Furring strips.
In both exposed and concealed locations, where a cable or raceway type wiring method is installed parallel to framing members, such as joists, rafters, or studs, or installed parallel to furring strips, the cable or raceway shall be installed and supported so that the nearest outside surface of the cable or raceway is not less than 1 1/4 inch from the nearest edge of the framing member or furring strips where nails or screws are likely to penetrate. where this distance cannot be maintained, the cable or raceway shall be protected from penetration by nails and screws by a steel plate, sleeve, or equibalent at least 1/16 of inch thick.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When Type AC cable is run across the top of a floor joist in an attic without permanent ladders or stairs, substantial guard strips within _____ of the scuttle hole, or attic entrance, shall protect the cable.

A

6 Feet

320

AC Cable : Type AC

  1. 23(A)
  2. 23

In Accesible Attics

(A) Where Run Across the Top of Floor Joists.

Where run across the top of floor joists, or within 7 feet of floor or floor joists across the face of rafters or studding, in attics and roof spaces that are accesible, the cable shall be protected by substantial guard strips that are at least as high as the cable. Where this space is not accessible by permanent stairs or ladders, protection shall only be required within 6 feet of the nearest edge of the scuttle hole or attic entrance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When armored cable is run parallel to sides of rafters, studs, or floor joists in an accesible attic, the cable shall be protected with running boards.

True or False

A

False

320
AC cable : Type AC

  1. 23 (B)
  2. 23 In Accessible Attics.

(B) Cable installed Parallel to framing members.

Where the cable is installed parallel to the sides of rafters, studs, or floor joists, neither guard strips nor running boards shall be required, and the installation shall also comply with 300.4(D).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Type AC cable can be supported and secured by _____.

A

Staples, Cable ties, Straps, hangers, or similar fittings.

320

Armored Cable : Type AC

320.30(A)

320.30
Securing and supporting

(A) General

Type AC cable shall be supported and secured by staples, cable ties, straps, hangers, or similar fittings, designed and installed so as not to damage the cable.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Type AC cable shall be secured at intervals not exceeding 4 1/2 feet within ____ of every outlet box, cabinet, conduit body or fitting.

A

12 inches

320

Aromored cable: Type AC

  1. 30 (B)
  2. 30 Securing and supporting

(C) Securing

Unoless otherwise provided, Type AC cable shall be secured withing 12 inches of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 4 1/2 inches where installed on or across framing members.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Type AC cable installed horizontally through wooden or metal framing memebers are considered supported where support doesn’t exceed _____.

A

4 1/2 feet

320

Armored cable: Type AC

  1. 30(C)
  2. 30 Securing and Supporting.

(C)Supporting. Unless otherwise provided, Type AC cable shall be supported at intervals not exceeding 4 1/2 feet.

Horizontal runs of Type AC cable installed in wooden or metal framing members or similar supporting means shall be considered supported where such support does not exceed 4 1/2 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Armored cable used to connect recessed luminaires or equipment within an accesible ceiling can be unsecured for lengths up to ____.

A

6 feet

320

Armored Cable : Type AC

  1. 30(D)(3)
  2. 30

Securing and supporting

(D) Unsupported Cable

(3) Is not more than 6 feet in length from the last point of cable support to the point of connection to a luminaire(s) or other electrical equipment and the cable and point of connection are within an accesible ceiling. For the purposes of this section, Type AC cable fittings shall be permitted as measn of cable support.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At Type AC cable terminations a(n) ______ shall be provided.

A

Fitting ( or box design ) that protects the conductors from abrasion, an insulating cbushing between the conductors and the cable armor.

320

AC cable : Type AC

320.40

Boxes and fittings.

At all points where the armor of AC cable terminates, a fitting shall be provided to protect wires from abraasion, unless the design of the outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an insulating bushing or its equivalent protection shall be provided between the conductors and the armor. The connector or clamp by which the Type AC cable is fastened to boxes or cabinets shall be of such design that the insulating bushing or its equivalent will be visible for inspection. Where change is made from Type AC cable to other cable or raceway wiring methods, a box, fitting, or conduit body shall be installed at junction points as required by 300.15.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Type AC cable installed in thermal insulation shall have conductors that are rated at 90 C. The ampacity of the cable in this application shall be base on ______.

A

60 C conductors

320

Armored Cable : Type AC

  1. 80(A)
  2. 80

Conductor Ampacities

(A) Thermal Insulation

Type AC cable installed in thermal insulation must have conductors rated 90 C. The ampacity rating at 90 C can be used for conductor ampacity adjustement and/ or correction, but the adjusted ampacity must not exceed the 60 C ampacity listed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly