Article 110 Flashcards
In judging equipment for approval, considerations such as the following shall be evaluated:
110.3 Examination, Identification, Installation, and Use of Equipment
- Examination
- Suitabilit
- Mechanical Strength
- Wirebending and connection space
- Electrical insulation
- Heating effects under normal conditions of use and also under abnormal conditions likely to arise in service
- Arcing effects
- Classifications by type, size, voltage, current capacity, and specific use
- Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment.
Listed or labled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:
True or False
True
- 3 Examination, Identification, Installation, and Use of Equipment
- 3(B)
Installation of Use.
Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.
Conductors shall be ____ unless otherwise provided.
Copper
110
Requirements for Electrical Installations.
110.5
Conductors.
Conductors normally used to carry current shall be of copper unless otgherwise provided in this Code. Where the conductor material is not specified, the material and the sizes given in this Code shall apply to copper conductors. Where other materials are used, the size shall be changed accordingly.
Conductor sizes are expressed in American Wire Gauge (AWG) or ____.
Circular Mils.
110
Requirement for Electrical Installations.
110.6
Conductor Sizes
Conductor sizes are expressed in American Wire Gauge (AWG) or in circular mils.
Wiring shall be installed so that the completed system will be free from ____, other than as required or permitted elsewhere in the Code.
Short Circuits, Ground Faults, and connections to the earth.
110
Requirement for Electrical Installations
110.7
Wiring Integrity
Completed wiring installations shall be free from short circuit, ground fault, or any connections to ground other than as required or permitted elsewhere in this Code.
Only wiring methods recognized as ___ are included in this Code.
Suitable
Suitable
110
Requirements for Electrical Installations
110.8
Wiring Methods
Only wiring methods recognized as suitable are included in this Code. The recognized methods of wiring shall be permitted to be installed in any type of building or occupancey, except as otherwise provided in this Code.
Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment.
True or False
True
110
Requirement for Electrical Installations.
110.9
Interrupting Rating
Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment.
Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted.
The ___ of a circuit shall be selected and coordinated to permit the circuit protective devices to clear a fault without extensive damgae to the electrical components of the circuit.
Overcurrent protective devices, total circuit impedance, component short circuit current ratings.
110
Installation Requirements for Electrical Installations
110.10
Circuit Impedance and Other Characteristics
The overcurrent protective devices, the total impedance, the component short circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical components of the circuit.
Unless identified for use the operating enviroment, no conductors or equipment shall be ____ having a deteriorating effect on the conductors or equipment.
Located in damp or wet locations, exposed to fumes, vapors, or gases, exposed to excessive temperatures.
110
Requirements for Electrical Installations
110.11
Deteriorating Agents
Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment: or where exposed to excessive temperatures.
Some cleaning and lubricating compounds can cause sever deterioration of many ____ materials used for insulating and structrual applications in equipment.
True or False
True
110
Requirements for Electrical Installations.
110.11 Deteriorating Agents.
FPN No. 2 : Some cleaning agents and lubricating compounds can cause severe deterioration of many plastic materials used for insulating and structural applications in equipment.
The NEC requires that electrical work be ____.
Installed neat and workmanlike manner
110
Requirements for Electrical Installations
110.12 Mechanical Execution of Work.
Electrical equipment shall be installed in a neat and workmanlike manner.
Accepted industry workmanship practices are described in ANSI/NECA 1-2006, Standard and Practices for Good Workmanship in Electrical Contracting, and other ANSI approved installation standards.
True or False
True
110
Requirement for Electrical Installations
110.12
Mechanical Execution of Work
FPN: Accepted industry practices are described in ANSI/NECA 1-2006, Standard for Practices for Good Workmanship in Electrical Contracting, and other ANSI- approved installation standards
Unused opening other than those intended for the operation of equipment, intended for mounting purposes, or permitted as part of the design for listed equipment shall be _____.
Effectively closed to afford protection substantially equivalent to the wall of the equipment.
110
Requirements for Electrical Installations
- 12(A)
- 12
Mechanical Execution of work
(A) Unused Opening.
Unused opening, other than those intended fo the operation of equipment, those intended for mounting purposes, or those permitted as part of the design for listed equipment, shall be closed to afford protection substantially equibalent to the wall of the equipment.
Internal parts of electrical equipment, including ____, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues.
Bus bars, wiring terminals, insulators, and other surfaces.
110
Requirement for Electrical Installations
- 12(B)
- 12
Mechanical Execution of Work
(B) Integrity of Electrical Equipment and Connections.
Internal parts of electrical equipment, including bus bars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials suchs as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipemtn such as parts that are broken; bent; cut; or deteriorated by corrosion, checmical action, or overheating.
Electrical equipment that depends on ___ for cooling of exposed surfaces shall be installed so that airflow over such surfaces is not prevented by waslls or by adjacent installed equipment.
Natural circulation of air and convection principles.
110
Requirements for Electrical Installations
- 13(B)
- 13 Mounting and Cooling of Equipment
(B) Cooling
Electrical equipment that depends on the natural circulation of air and convection principles for cooling of exposed urfaces shall be installed so that room airflow over such surfaces is not prevented by walls or by adjacent installed equipment.