April 90 questions Flashcards
NEC 2008 questions
The feeder conductor ampacity shall not be less than that of the service-entrance conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of _____ or less.
55 Amps
215.2(A)
215 Feeders
(A) Ampacity relative to service conductors
THe feeder conductor ampacity shall not be less than that of the service conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of 55 amperes or less.
The vertical clearance from ground level over a residential driveway for overhead service conductors not subject to truck traffic and are less than 300 volts to ground shall be ____ ft.
12 ft.
230 Services
- 24(B)(2)
- 24 Clearances
(B)Vertical Clearnce for Service-Drop Conductors
(2)12 ft.- over residential property and driveways, and those commercial areas not subject to truck traffic where the voltage does not exceed 300 volts to ground
In health care facility, receptacles and attachment plugs in a hazardous (classified) location within anesthetizing area shall be listed for use in Class I, Group ____.
Fixed in place X-Ray Equipment properly supplied by a branch circuit rated at not over ____ amperes shall be permitted to be supplied through a suitable attachment plug cap and hard service cable or cord
30 amperes
660 X-Ray Equipment
- 4(A)
- 4 Connection to Supply Circuit
(A) Fixed and Stationary Equipment Fixed and stationary X-Ray equipment shall be connected to the power supply by means of a wiring method meeting the general requirements of this Code, Equipment properly supplied by a branch circuit not rated over 30 amperes shall be permitted to be supplied through a suitable attachment plug cap and hard-service cable or cord.
For switchbords that are not totally enclosed, a space of ___ or more shall be provided between toe top of the switch board and any combustile ceiling.
36 inches (3 feet)
408
Switchboards and Panelbords
- 18(A)
- 18 Clearances
(A) From Ceiling
For other than a totally enclosed switchboard, a space not less than 3 feet shall be provided between the top of the switchboard and any combustible ceiling, unless a noncombustible shield is provided between the switchboard and the ceiling.
Indoor electrical vehicle charging sites, unless specifically listed for the purpose and location, the coupling means of the electric vehicle supply equipment shall be stored or located at a height of not less than ____ and not more than 4 ft.
18 inches
625 Electric Vehicle Charging system
- 29(B)
- 29 Indoor sites.
(B) Height
Unless specifically listed for the purpose and location, the coupling means of the electric vehicle supply equipment shall be stored or located at a height of not less than 18 inches and not more then 4 feet above the floor level
In patient care areas, the grounding terminals of all receptacles and all noncurrent-carrying conductive surfaces of fixed electric equipment _____, _____, _____ shall be connected to an insulated copper equipment grounding conductor.
likely to become energize
operating at 100 volts
subject to personal contact
517.13(B)
517 Health Care facitlities
517.13 Grounding of receptacles and fixed electrical equipment in patient care areas
(B)Insulated Equipment Grouding conductor
The grounding terminals of all receptadcles and all non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts, shall be connected to an insulated copper equipment grounding conductor.
For cord and plug connected electric vehicle supply equipment is used, the interrupting device of a listed personnel protection system shall be provided and shall be located in the power supply cable not more than ____ from the attachment plug.
12 inches
625 Electric Vehicle Charging System
625.22 Personnel Protection System
…. Where cord-and-plug connected electric vehicle supply equipment is used, the interrupting device of a listed personnel protection system shall be provided and shall be an integeral part of the attachment plug or shall be located in the power supply cable not more than 12 in. from the attachment plug.
Grounding requirements for a central vaccum shall have accesible?
Accesible non-current carrying metal parts of the central vaccum outlet assembly shall be connected to an equipment grounding conductor
422 Appliances
- 15(C)
- 15 Central Vaccum Outlet Assemblies
The maximum total voltage drop on branch-circuit conductors is _____ percent.
3 percent
210
Branch Circuits
- 19(A)(1)
- 19 Conductors - Minimum Ampacity and Size.
(A)
Branch Circuits Not More Than 600 Volts
(1) General
Conductors of branch circuits shall be sized to allow for a maximum voltage drop of 3 percent at the last outlet supplying light, heat or power and the maximum voltage drop allowable for feeders and branch circuit combined shall not exceed 5 percent.
Where it is impracticable to locate the service head above the point of attachment, the service head location shall be permitted not farther than _____ from the point of attachment.
24 inches
230 Service Nyc Amendment
- 54(B) Exception
- 54 Overhead Service Locations.
(B) Service Heads Above Service-Drop Attachement
Exception
Where it is impracticable to locate the service head above the point of attachemnt, the service head location s_hall be permitted not farther than 24 inches from the point of attachment._
Lighting systems covered by Article 411 shall have a power supply rated not more than ___ and not more than 30 Volts.
25 Amps
411 Appliances
411.2 Definitions
Lighting Systems Operating at 30 Volts or Less.
A lighting system consisting of an isolating power supply, the low-voltage luminaires, and associated equipment that are identified for use. The output circuits of the power supply are rated for not more than 25 amperes and operate 30 volts (42.4 volts peak) or less under all load conditions.
How many receptacle outlets are permitted on a 20 A, 120 V circuit in a commercial building?
120*20
______
180
= 13.333
13 receptacles
In New York City for services not rated over 600 Volts, you can use Type ____ cable as long as the cabl is enclosed in a threaded metallic conduit.
Type SE Cable
338 NYC Amendment
Service-Entrance Cable; Type SE and USE
- 10(A)
- 10 Uses Permitted
(A) Service Entrance Condutors
Where installed as service entrance conductors, Type SE cable shall be enclosed in a threaded metallic conduit.
How many receptacles are required within the perimeter of a balcony, deck, or porch with a usable area of less than 20 Sq. feet.
One(1)
210
Branch circuits
- 52(E)(3)
- 52 Dwelling Unit Receptacle Outlets
(E)Outdoor Outlets
(3) Balconies, Decks, and Porches.
Baclonies, Decks, and porches shall have at least one receptacle outlet installed within the perimeter of the balcony, deck, or porch. The receptacle shall not be located more than 6 1/2 feet above the balcony, deck, or porch surface.
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of ____ from windows that are designed to be opened, doors, porches, stairs, fire escapes, or similar locations.
3 Feet
230 Services
- 9(A)
- 9 Clearances on Buildings
(A) Clearances
Service conductors installed as open conductors or multiconductor cable without an overall jacket shall have a clearance of not less than 3 Feet from windows that are designed to be opened, doors, porches, stairs, fire escapes, or similar locations.
What electrical equipment room requires 2 means of egress?
Network Compartments
110
Requirements for Electrical Installations
- 26(H) NYC Amendment
- 26
Space About Electrical Equipment
(H) Network Compartments
All Network Compartments shall have at least 2 means of access. Each door shall access an area that leads to legal exit.
Fuses and circuit breaker shall be permitted to be connected in parrallel where they are _______ in paralllel and listed as a unit.
Factory Assembled
240 Overcurrent Protections
240.8 Fuses or Circuit Breakers in Parallel.
Fuses and circuit breakers shall be permitted to be connected in parallel where they are factory assembled in parlallel and listed as a unit. Individual fuses, circuit breakers, or combinations thereof shall not otherwise be connected in parallel.
Nonmetallic cables must be fastened ___ inches to enter the top of surface-mounted cabinets,cutout boxes, and meter socket enclosures through nonflexible raceways, the race ways shall not penetrate a structural ceiling and the minimum lenght of the raceway shall be ___ and maximum length shall be?
12 inches(fastened in place)
18 inches(min. raceway)
10 ft(max. raceway)
312 Cabinets, cutout boxes, and meter socket enclosures.
- 5(C) exception
- 5 Cabinets, cutout boxes, and meter socket enclosures.
(C)Cables
Exception:
Cables with entirely nonmetallic sheaths shall be permitted to enter the top of a surface-mounted enclosure through one or more nonflexible raceways not less than 18 inches, and not more than 10 feet. in length, provided all of the following coniditions are met
(a)Each cable is fastened within 12 inches measured along the sheath, of the the outer end of the raceway.
At least ____125 V, single phase, 15 A or 20 A, duplex with a ground fault circuit interrupter receptacle shall be provided in each elevator amchine room and elevator machinery space.
One
620 Elevators
- 23(C)
- 23 Branch circuits for machine room or control room/machinery space or control space lighting and receptacle(s)
(C) Duplex receptacle
At least one 125 volt, single phase, 15 or 20 ampere duplex receptacle shall be provided in each machine room or control room and machinery space or control space.
As per New York City NEC in addition to the number of branch circuits required in a dwelling unit an individual branch circuit shall be provided for each ____ receptacle.
Air Conditioner
210 Branch Circuits
- 11(C)(4)
- 11 Branch Circuits Required
(C) Dwelling Units
2011 NYC ammendment
(4) Air Conditioning Branch CIrcuit.
In addition to the number of branch circuits required by other parts of this section, an _individual branch circui_t shall be provided _for each air-conditioning receptacle_ requiered by 210.52(I)
Conductors are considered outside a building whe they are buried under not less than
2 Inches
230 Services
- 6(1)
- 6 Conductors Considered outside the building
(1) Where installed under not less than 2 inches of concrete beneath a building or other structure
Supply service drops of 0-750 volts running above and parallel to communications service drops shall have a seperation of?
12 inches
800 Communication circuits
- 44(A)(4)
- 44 Overhead communications wires and cables
(A)On poles and In-Span
(4)Clearance
Supply service drops of 0-750 volts running above parallel to communications service drops shall have a minimum seperation of 12 inches at any point in the span…..
Open conductors installed outside shall be seperated from open conductors of other circuits or systems by not less than ____.
225 Outside Branch Circutis and Feeders
- 14(C)
- 14 Open- Conductor Spacings
(C) Seperation from Other Circuits.
Open conductors shall be seperated from open conductors of other circuits or systems by not less than 4 inches.
Which flexible cable is allowed to be used for a Electric Vehicle Charging Station 300 Volts?
EVJ
Table 400.4
In health care facilities, patient bed receptacles located in general care areas shall be supplied by at least ___ branch circuits which are permitted to originate from two sepearate transfer switches on the emergency system.
2 (TWO)
517
Health Care Facilities
- 18 (A) Exception 3
- 18 General Care Areas
(A) Patient Bed Locations
Exception 3
A general care paitent bed location served from two seperate transfer switches on the emergency system shall not be required to have circuits form the normal system.
Type ____ Fuse adapters shall be designed so that once inserted in a fuseholder they cannot be removed.
Type S
240 Overcurrent Protection
- 54(C)
- 54 Type S Fuses, Adapters, and Fuseholders.
(C) Nonremovable. Type S adapters shall be designed so that once inserted in a fuseholder, they cannot be removed.
Where angle or U pulls are made, the distance between each raceway entery inside the box and the largest opposite wall of the box shall not be less than _____times the trade size of the largest in a row.
6 Times
314
Outlet, Device, Pull and Junction Boxes, Conduit Bodies, Fittings, and Handholes
- 28(A)(2)
- 28
Pull and Junction Boxes and Conduit Bodies.
(A) Minimum Size
(2)
Angle of U Pulls, or Splices.
Where splices or where angle or U pulls are made, the distance between each raceway entry inside the box and the opposite wall of the box shall not be less than six times the trade size of the largest raceway in a row.
New York City Department of Buildings approved manufacturer wiring methods shall be used only for ______
General lighting circuits above an accesible hung ceiling or wehre no finished ceiling exists.
ARTICLE 604 NYC Amendment
Manufactured Wiring Systems
SECTION 604.1
Subsection 604.1(A) – Add a new subsection 604.1(A) to read as follows:
(A) General. All such wiring systems shall be approved by the department, and shall comply with the installation requirements of this code in addition to the standards listed below. Each manufactured wiring system manufacturer shall add the following to its installation instructions:
(1) With the electrical permit application for each installation, or any subsequent modification thereof, the licensed electrician shall include a diagram or specification sheet clearly defining the boundaries where the wiring method will be installed.
(2) Manufactured wiring systems shall not be used for emergency exit signs or emergency lighting.
(3) Such wiring shall be used only for general lighting circuits above an accessible hung ceiling or where no finished ceiling exists.
For a portable motor rated at _____ hp or less, the controller shall be permitted to be an attachment plug and receptacle.
(Portable Motor) 1/3 horsepower or less
430
Motors, Motor circuits, and controllers
- 81(B)
- 81 Portable Motor of 1/3 Horsepower or less
For a portable motor rated at 1/3 horsepower or less, the controller shall be permitted to be an attachment plug and receptacle.
A 125 volt, single phase, 15 or 20 ampere rated outlet shall be installed at an accessible location for the servicing of heatin, air conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within ____ of the heating, air conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
25 Feet
210 Branch Circuits
210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet.
A 125 Volt, single phase, 15 or 20 ampere rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air conditioning,and refrigeration equipment. The receptacle shall not be connected to the load side of the equipment disconnecting means.
A seperate ____ shall supply the elevator hoistway pit lighting and receptacle. The required lighting and or sump pump shall not be connected to the load side of a ground-fault circuit interrupter.
Branch Circuit
620.24(A)
620 Elevators, dumbwaiters, escalators, moving walks, platform & stairway chairlifts
620.24 Branch circuit hoistway pit lighting and receptacles
(A) Seperate branch circuit. A seperate branch circuit shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter.
Indoor antenna lead-ins shall not be run nearer than ____ to conductors of other wiring systems in the premises.
2 inches
810
Radio and Television Equipment
- 18(B)
- 18 Clearances _ Recieving Stations
(B) Antennas and Lead-ins - Indoors
Indoor antennas and indoor lead-ins shall not be run nearer than 2 inches to conductors of other wiring systems.
What is the maximum voltage drop from Service point to last overcurrent device in a dwelling unit?
4 percent
215
Feeders
- 2(A)(1) exception 3 NYC Amendment
- 2 Minimum Rating and Size.
(A) Feeders Not More than 600 Volts
(1) General
Exception 3
For residential occupancies and portions of the electircal system of mixed use building serving exclusively residential occupancies, the maximum voltage drop from service point to the last overcurrent device shall not exceed 4 percent and the total maximum voltage drop to the last outlet shall not exceed 5 percent.
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with conductors of Class 1 or electric light or power conductors, unless ____.
unless seperated by a barrier
725
Class 1, Class 2, Class 3 Remote Control, Signaling, and Power-Limited Circuits
- 136(B)
- 136 Seperation from Electic Light, Power, Class 1, and Medium-Power Network-Powered Broadband Communications Cables.
(B) Seperated by Barriers.
Class 2, Class 3 circuits shall be permitted to be installed together with the conductors of electric light, power, Class 1, and medium power network-powered broadband communications circuits where they are seperated by a barrier