an assembly comprising porous insulation material with a metal outer jacket
Cladding
Cladding:
Nameplates and stampings on equipment shall be left permanently visible and, If impractical ,,,,,, plate shall be fixed on the outside of the cladding
a second
Cladding:
All pipe and equipment which require acoustic cladding shall have been adequately protected against ,,,,,, before cladding starts.
Corrosion
Cladding:
During installation, the materials shall be protected with ,,,,, after each day’s application
weatherproof sheeting
Insulation materials:
Material to be in contact with the surface being clad shall not cause it to ,,,, under normal site conditions.
corrode
Insulation materials:
On stainless surfaces operating above 70 C, the chloride content of the insulation shall not exceed
,,,,,, and should be used in conjunction with a suitable barrier paint which does not contain ,,,, in a metallic form
50ppm
zinc
Insulation materials:
On aluminium surfaces other than jacket material, the chloride content of the insulation shall not exceed ,,,,, and the alkalinity shall be in the pH range of ,,,,
25ppm
7 to 8.5
Metal jacket material:
Aluminium coated mild steel shall have an aluminium coating which does not contain more than ,,,, % magnesium
6%
Insulation banding strip:
banding strip shall be the same material as the ,,,, and
have a minimum width of ,,,,mm. and If self-adhesive tape is used for insulation banding, the tape to shall be with a minimum width of ,,,,,
jacket
12
50mm
Mastic sealants:
Mastic sealants shall be suitable for use at temperatures in the range ,,,, oC to ,,,,,, oC with occasional increases up to ,,,,, oC.
–20 oC to 50 oC
80 oC
Cladding of pipe:
Pipe shall be covered, as far as possible, with preformed sections of insulation cut and profiled to fit
and secured at ,,,,, intervals with banding strip
450mm
Cladding of pipe:
The insulation shall be covered by a ,,,,,
metal jacket
Cladding of pipe:
Jacket sheets shall be ,,,,, around the insulation
a snug fit
Cladding of pipe:
Jacket sheets shall have minimum ,,, longitudinal and ,,,, circumferential lapped joints which shall be arranged to shed water
25mm
25mm
Cladding of pipe:
A clearance of approximately ,,,,,,shall be provided between the jacket and the branch and this annulus shall be filled with ,,,,,
6mm
mastic.