AOIT '24 April Flashcards

1
Q

Robust Barrier

A

Physical barrier that can prevent access to a protected component, room, or area that requires human action to move in order to gain access to the protected component, room, or area

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

Posted Protected Equipment

A

Equipment or components, normally in the protected train or pathway, that has been provided a physical barrier to control entry or prevent inadvertent manipulation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

New EH skid Power Supply

A

PP-70 via MCC-4 (electrostatic filter)
PP-38 via MCC-4 (aux filter skid power)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

New EH skid Trips

A

Pressure transducer failure
90pisg ICB vessel
D/P >50 in mechanical vessel
Motor overload (can be reset by button)
Leak detection relay closes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Can both EH skids be in service at the same time?

A

No, only one or the other

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

EDG speed setting calculation

A

Speed setting indicator + speed setting

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

FWH’s heat FW how much?

A

~50 degrees per FWH

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

FWHs raises FW from what temp to what temp?

A

~99 to 435 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Safety Injection Valves that receive a signal during a SI?

A

SI-867 A/B BIT Inlets
SI-870 A/B BIT outlets
SI-841 A/B BIT Recirc
SI-865 A/B/C Accumulator Outlets
RHR-744 A/B RHR cold leg injection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

H2 and N2 PCV valves to VCT?

A

PCV-118 for H2 and PCV-119 for N2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

N2 flow path to accumulators?

A

PCV-937 (>630)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

RWST level for swap? and considered empty?

A

27%
9%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How much water has to be in the Containment sump for recirc to be in place?

A

1.5 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

SI modes

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

RWST level band and Boron Concentration?

A

ITS 1950-2400ppm
Admin 2000-2350ppm
Level 27% to 92.5% (hi and lo alarms)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

SFP level band and Boron Concentration

A

ITS >1500ppm
Admin 2050-2600ppm
Level 36’ 2.5” to 37’ 5/8”

16
Q

Nitrogen pump power supply?

A

MCC-1

17
Q

Ambient Air Vaporizer

A

Turns liquid N2 to gas