650 & 653 - P1 (50Q) Flashcards
A 10” nozzle is to be hot tapped into the first course of an in-service aboveground storage tank. What must the minimum shell thickness be in order to install this nozzle?
3/8”
A peripheral seal of an internal floating roof shall be designed to accommodate _____ inches of local deviation between the floating roof and the shell.
+/- 4
A new above ground storage tank has its bottom and second course plates constructed of ASTM A516 GR 60 steel that is thicker than 1 inch. How much of the vertical shell welds must be radiographed?
Complete radiography of each vertical seam is required.
When visually examining a weld of an aboveground storage tank, the frequency of surface porosity in the weld must not exceed one cluster (one or more pores) in any _____ inches of length and the diameter of each cluster must not exceed 3/32 inch.
4
When changing the operating temperature of an atmospheric storage tank to above 200F, all the requirements of:
API Standard 650, Appendix M shall be considered.
For tanks greater than 200’ in diameter, the design method to be used is known as:
The variable design point method.
The joint efficiency of a riveted lap joint with one rivet row is:
0.45
The minimum thickness of a tank bottom as calculated by the deterministic method of calculation shall be a minimum of _____ inches at the next inspection period (when the tank bottom / foundation design has a means to provide detection and containment of a bottom leak).
0.05”
What is the maximum acceptable weld undercutting of vertical butt joint of a reconstructed tank?
1/64”
A 65’ diameter tank by 32’ high is to be checked for settlement. How many settlement points are required around the periphery?
8 points
The space between the outer periphery of the roof and the tank shell of an external floating roof tank shall be sealed by a flexible device that provides:
A reasonable close fit to the shell surfaces.
A reconstructed tank course made from ¾” plate is welded with a low hydrogen rod. The welder undercuts a horizontal butt weld to a depth of 0.02” and he reinforces the weld with a 0.20” cap. Is it acceptable and why?
The weld is unacceptable because of the excess reinforcement and excess undercut.
The correct manual welding rod that must be used to make Hot Taps or for reconstruction of above ground storage Tanks.
E7018
The new nameplate for a reconstructed API 653 tank shall be placed:
Adjacent to existing nameplate.
Radiographs for reconstructed tanks shall be:
Retained for at least 1 year.
It is not necessary to consider the possibility of brittle fracture of a tank if the following exists. The tank shell thickness is:
Less than/equal (=) ½”, the tank operates over 60F or the membrane stress of the tank is below 7000psi.
Welds do not need a welder identification if
Roof plate welds and flange-to-nozzle neck welds.
Roof plates of an aboveground storage tank shall be repaired or replaced if the average thickness of the plates have corroded to:
Less than 0.09” in any 100 square inch area.
If the requirements of a jurisdiction are more stringent than the requirements of API 653, then the requirements of:
The jurisdiction shall govern.
Aboveground storage tanks are primarily inspected to:
Ensure the safety and integrity of the tanks.