4th step SSQ Flashcards
- What is the equation for determining a transformer’s turns ratio?
Np- Number of turns on the primary
Ns- Number of turns on the secondary
Vp- Voltage on primary
Vs- Voltage on secondary
Reference: 2nd step transformer theory and design
- Determine the turns ratios for the following single-phase transformers.
a. 16 kV to 120 V
b. 16 kV to 240 V
C 12 kV to 120V
d. 12 kV to 240V
A.133:1
b.66:1
C.100:1
d.50:1
Reference: 2nd step transformer theory and design
What are the two polarities a transformer can have?
Additive and subtractive.
Single-phase transformer nameplates indicate whether its polarity is additive or subtractive. Polarity indicates the relative direction of current flow through the transformer. Polarity is determined by looking at the “polarity bushing” (H1) on the transformer, and its relation to the X1 bushing. When H1 and X1 are on the same side, it is considered subtractive polarity. When H1 and X1 are on opposite sides, it is considered additive polarity. With standard markings, if the direction of current flow is from H1 to H2, the current flow will be in the direction of X2 to X1.
Reference: 2nd step transformer polarity
What is the purpose of a transformer tap changer?
To raise or lower secondary voltage by changing the turns ratio
Taps on transformers allow the turns ratio to be changed over a small range. This gives some flexibility for adjusting the operating voltage of the transformer. Each tap changes the turns ratio by some small amount, typically 2.5%. The taps consist of terminals, linkages or similar devices.There are two types of tap changers: no load tap changer and load tap changer. No load tap changers require the transformer to be de-energized, so there is a short interruption in customer service while the taps are changed. Load tap changers provide the ability to change taps while the transformer is energized and without interrupting the flow of current through the transformer and to the customer.
Reference: 2nd step Transformer Design and Theory
How is rotation checked/determined?
At the customers panel using a phase sequence indicator, from L to R (RWB) attach clips to customer’s phases.
Reference: 4th Step Vectoring Training Manual
What is the maximum weight allowable for a closed-delta 300 kVA transformer bank on a 50-foot wood pole using a transformer mounting bracket? What is the minimum diameter pole for this application?
4,250 Ibs.
H2 class
11 inch minimum diameter.
Reference: DAP Table AP 106-1, and AP 132-1 Note 7
What is the maximum weight allowable for a 2-single phase transformer bank (open delta) hung on a wood pole using a transformer bracket?
1,600 Ib total weight limit.
Reference: DOH, Figure AP 122-1
Describe the AC electrical characteristic of impedance.
Impedance opposes the flow of electrical current in an AC circuit. It is made up of two components: resistance and reactance. Since reactance is at a 90-degree angle to resistance, resistance and reactance are added with vectors in order to calculate impedance.
Reference: 4th Step Ohm’s Law and Power Formulas Training Manual
When - and why - is the wye leg tied, on the primary side of a 4 kV bank?
Open Wye banks (2 transformers) shall be connected to the system neutral.
Closed Wye- delta banks (3 transformers) - Wye-Delta you float
shall not be connected to the system neutral. When wiring a delta secondary, the delta is left open to check that voltage is less than 20 volts. Recall that a disadvantage of wye-wye connected transformers is that they do not trap third harmonics. Therefore, the wye must be connected to the neutral until the delta voltage is checked and then the delta is closed to provide a path to circulate the 3rd harmonic currents. After the delta is closed, the wye connection is floated
Tied for checking voltage.
Wye- Wye banks (3 transformers) Wye-Wye you tie
A disadvantage of wye-wye connected transformers is that they do not trap third harmonics. This will be discussed in more detail in the Voltage Problems training module. Because all harmonic voltages are in-phase, it results in phase currents that do not cancel in a wye. Therefore, there is no path for the 3rd harmonic currents when the wye is floated When the wye point is connected to the system neutral, it provides a path for the in-phase 3rd harmonic currents. Because these currents are additive, they add and can cause high unnecessary neutral currents
It is tied to get rid of the third harmonics
Reference: 2nd step transformer delta vs wye
What is a high leg? How is it identified?
A high leg is the secondary phase with the highest phase to ground voltage.As required by the National Electric Code, the high phase (power leg) must be prominently identified by orange markings on the cable or bus.
Reference: DOH, T 454 Note 4
In a three-phase circuit, what is a grounded leg? Where is it located in the customer’s panel?
A grounded leg is a phase that has been grounded. It is generally located in the middle position in the customer’s panel.
When and why is rotation checked?
The need for a phase sequence meter is to identify the rotation of a three phase source and to ensure that the equipment can be reconnected to the source with the proper rotation. Before taking a piece of equipment out of service, the rotation should be checked and recorded. Then, after the work has been completed, the rotation should be rechecked before the equipment is re-energized.
Reference: 4’ Step Vectoring Training Manual
How is improper rotation corrected
Without disturbing the high-leg, swap any two phases.
Reference: 4’ Step Vectoring Training Manual
If two 10 kVA transformers are wired in an open-delta configuration - for 3-phase power - what would be the available kVA?
20 kVA x0.86 = 17.2 available kVA.
Reference: 4’ Step Wiring Three-Phase Banks Training Manual
What are the thumb rules for determining amps per kVA for the following secondary voltages?
a. 120 V single-phase
b. 240 V single-phase
480 V single-phase
d. 240 V three-phase
e.480 V three-phase
f.208 V three-phase
a. x8
b. x4
c. x2
d. x2.4
e. x1.2
f. x 2.8
Reference: pocket manual
What is TS-5, and when is it used?
2.1 Applicability
This procedure shall be used to field-test all newly installed and relocated overhead transformers, and all overhead transformers with blown fuses.
1.0 purpose
This procedure outlines the requirements for in-place field-testing of overhead transformers. It is to be used for:
* Newly installed or relocated transformers
* Re-energizing existing transformers with blown fuses
* CP transformers with tripped overload breakers
Reference: DOM, TS-5 1.0
When applying TS-5 to newly installed/relocated transformers, how are the transformer secondaries grounded (prior to energization).
For grounded secondaries, connect the secondary ground. For ungrounded secondaries, temporarily install a solid ground on the low side at any of the phase connections or the neutral. (The intent is to ensure enough fault-current to blow the test fuse for a primary to secondary fault.)
Reference: DOM, TS-5 4.1
Distribution Apprentice Lineman OJT
When are clearances required?
Clearances are required to work on de-energized generating station or substation apparatus or equipment which is normally energized above 600 volts.
Clearances are required to work on de-energized lines or line sections above 600 volts.
Reference: APM Rule 105
When are no-test orders required?
No Test Orders (definition DOM)
For hazardous line construction work, Edison makes available “No Test Orders” (NTO) to every foreman. Once NTO’s are issued, if the line relays, it will not be tested until contact is made with the foreman they were issued to and he cancels his NTO
DOM SOB 314
A No Test Order is a formal statement issued and recorded under a prescribed procedure, by an authorized person to a qualified person, declaring that in case certain specified energized distribution line(s) or substation equipment of 33 kV or below become de-energized, said equipment shall not be re-energized, by any method, until the No Test Order has been released by the person to whom the No Test Order was issued.
The purpose of the No Test Order is to provide a formal procedure by which a qualified person could request and receive a guarantee that a line or equipment shall not be re-energized when the nature of the work is such that the re-energizing would be hazardous to personnel.
APM 233-No Test Orders shall be taken during Distribution arc flash hazardous work activities that could cause an Arc Flash when either working at MAD or within the Arc Flash Boundary (AFB). When performing Rubber Gloving or Hot Sticking
Reference: SOB 314 and APM Rule 233
Why is it important that the correct size fuse be used in distribution circuits? What could result from installing a fuse that is either too weak or too heavy?
Fuses which are too weak may blow out during normal operating current loads. Fuses which are too heavy may fail to protect associated transformers (or other equipment).
Reference: 4thStep Fuses Theory and Operation Training Manual
What are current transformers (CTs) and potential transformers (PTs)? What are their typical applications in distribution circuits?
CTs are transformers which reduce high currents to safe levels for relay protection and metering services.
PTs are transformers which reduce high voltage levels to safe levels for equipment operation and metering services.
Reference: 4th Step Metering Theory and Operation Training Manual
How is a PT typically connected in a 2400 V application, and what is the typical turns ratio for this PT?
2400 V PTs are normally phase-to-ground connected.
The typical turns ratio is 20:1.
Reference: 4th Step Metering Theory and Operation Training Manual
What is the load on the following transformer (120/240 V, 10), given the following data:
VA = IxE
VA = (20 A +30 A) x 120 V = 6000 VA or 6 kVA.
Reference: 4th Step V, I, and P Relationships Training Manual
What is the load on the following transformer bank (120/240 V, 30), given the following data:
VA=I x E x 1.73
VA= 117A x 240V x 1.73
VA= 48,636
kVA=48.6
Reference: 4’ Step V, I, and P Relationships Training Manual