3.8 Electrical Power Systems Flashcards

1
Q

3.8.1 AC Power Supplies - Operating

A

One Standby diesel generator shall be FUNCTIONAL

APPLICABILITY: MODES 1 - 5

ACTIONS
A. Fuel volume in required tank ≤ 55,000 gal, restore fuel volume within 14 days
B. Required fuel transfer pump not FUNCTIONAL OR Required Standby Diesel Generator not FUNCTIONAL for reasons other than A, Restore to FUNCTIONAL within 14 days.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

3.8.2 AC Power Supplies - RCS Open

A

Following supplies FUNCTIONAL to support RNS operation:

a. One offsite circuit
b. One standby diesel generator

APPLICABILITY: MODE 5 with RCS open, MODE 6 with upper internals installed, MODE 6 with < 23 feet above the flange

ACTIONS
A. One required AC power supply not functional
A.1 Initiate actions to increase water inventory above the core within 12 hours AND
A.2 Restore required AC power supply to FUNCTIONAL within 72 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

3.8.3 AC Power Supplies - Long Term Shutdown

A

One Ancillary diesel generator shall be FUNCTIONAL

APPLICABILITY: MODES 1 - 6 AND When irradiated fuel assemblies are stored in the SFP

ACTIONS
A. Fuel volume in ancillary diesel generator fuel tank ≤ 600 gal, restore within 14 days
B. Required ancillary diesel generator not FUNCTIONAL, restore within 14 days.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

3.8.4 Non Class 1E DC and UPS System (EDS)

A

Power to DAS automatic actuation functions shall be FUNCTIONAL
APPLICABILITY: Per Table
ACTIONS
————————————————————————————————–
- NOTE -
EDS support for DAS ATWS mitigation functions of reactor trip and turbine trip actuation are only required in MODE 1.
————————————————————————————————–
A. Power to required DAS function not FUNCTIONAL, restore within 14 days.

120 V ± 5%.