3-1-15 Troubleshooting Three-Phase Banks Flashcards

1
Q

A three-transformer bank serves a mixed single- and 3-phase load at 120/240 volts. Clip on amp meter readings on the secondary are: a phase=195, b phase=175, c phase=105. The total kVA bank load is __?__. (Round the final answer to one decimal place.)

A

65.7 kVA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In a secondary connected delta, winding current multiplied by __?__ is equal to line current.

A

1.73

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The best way to calculate total bank load on a delta bank is to calculate individual transformer loads and add them together.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

After determining which transformer is bad in a 3-phase bank, there are __?__ things you should check for on the nameplate before calling for a new transformer.

A

4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Three 37.5-kilovolt-ampere transformers connected as a 3-phase bank have a full load capacity rating of __?__ at 240 volts. (round off)

A

271 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The formula kVA X 1,000 divided by line to line voltage X 1.73 is used to calculate full load current __?__.

A

per phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If a faulted transformer is cleared and the remaining two transformers are connected as an open-wye-open delta, the bank only has __?__ capacity of the original bank.

A

58%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Calculating load checks on an open delta bank is the same as calculating load checks on a closed delta bank.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If a faulted transformer is cleared and the remaining two transformers are connected to open-wye-open-wye, the bank has __?__ capacity of the original bank.

A

50%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In an open wye-open delta bank, you have an inside the delta winding current reading of 286 amperes. The bank is providing service at 480 volts. The kVA loading of each transformer is __?__.

A

137.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Two factors this lesson points out that might account for a low voltage at a customer’s meter are bad connectors and the __?__.

A

distance of the service drop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When troubleshooting a transformer bank, the transformer that does not produce secondary voltage is always the bad one and needs replacing.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If two 25-kilovolt-ampere transformers are connected into an open-wye-open delta bank, the total bank capacity would be __?__.

A

43.5 kVA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When checking a 3-phase bank, the problem may be that someone installed primary side fuses that are too small.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A transformer rated at 75 kilovolt-amperes can carry __?__ at 240 volts.

A

312.5 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Overloaded transformer banks can cause __?__ to/for the customer.

A

voltage fluctuations

17
Q

The common connection point on a 3-phase wye connected bank is also called the __?__.

A

star point

18
Q

The formula to calculate an individual transformer load in kVA is kVA= __?__.

A

current I x E /1000

19
Q

Bank capacity is __?__ of total nameplate capacity in an open wye-open wye bank.

A

75%

20
Q

Current and voltage checks are an integral part of analyzing circuit problems.

A

True

21
Q

One procedure this lesson points out to go through when trying to find a bad transformer in a 3-phase bank has __?__ steps.

A

6