3-1-14 Transformers —Connections Flashcards

1
Q

The primary side of a three transformer wye-delta bank is always grounded.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When connecting a three-transformer wye-delta bank for 120/240-volt 4-wire service, it is critical to leave the grounding straps in place on all transformers.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The primary neutral must be tied firmly to the __?__ or else high voltages may occur on the secondary side.

A

system neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If a customer’s demand for power at a new plant is 450 kilowatts, most likely three __?__transformers would be used to serve the load.

A

167 kVA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

One delta primary is 13,800 volts. Of those listed below, another delta primary is __?__.

A

2400

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If a customer requests 277/480 volts, 3-phase, 4-wire, only __?__ volt transformers can be used.

A

277

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

On a two transformer bank supplying 120/240 volts, 3-phase, 4-wire, the transformer that does not supply the 120/240 volts is called the __?__.

A

power pot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An open wye-delta bank has a kVA rating of __?__ of the two transformers.

A

86.6%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If a 100-kilovolt-ampere transformer fails in a 300-kilovolt-ampere bank, the bank can be reconnected to an open wye-delta if the customer’s load is less than __?__.

A

173 kVA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When connecting a 3-phase transformer bank to an open-wye-delta the primary neutral also carries the full load current.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The phantom voltage that might be read between the three secondary phases and ground of a 240 ungrounded bank is __?__.

A

138

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If a CSP transformer is used in a three transformer bank as the lighter transformer and the CSP’s secondary breaker opens (trips), it will cause unequal voltages on the single-phase loads.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Unlike the wye-delta connection, there is no third harmonic voltage in a __?__ connection.

A

delta-delta

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The basic rule for connecting three-transformer coils in a delta is __?__ markings from each coil are connected together.

A

unlike

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The voltage of the winding (coil) is __?__ of the voltage between conductors in a wye connection.

A

58%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When using symbols to represent transformer banks, the first symbol is always the secondary connection.

A

False

17
Q

The 3-phase capacity of any three transformer bank is always three times the rating of the __?__ transformer in the bank.

A

smallest

18
Q

If a 3-phase bank contains a 75-kilovolt-ampere and two 50-kilovolt-ampere transformers, the capacity of the bank is __?__.

A

150 kVA

19
Q

An open-delta bank contains one 75-kilovolt-ampere and one 50-kilovolt-ampere transformer, the bank’s 3-phase capacity is __?__.

A

86.6 kVA

20
Q

Whenever you encounter a transformer, be sure to consult the __?__ for connection information.

A

nameplate

21
Q

The type of transformer with a single coil connected in series with the load is the __?__.

A

autotransformer

22
Q

The most common use of the autotransformer is __?__.

A

in a street light ballast

23
Q

On a wye-delta transformer bank connection, if the star point has been floated and there is a 3-phase motor load, the loss of one primary phase can cause high voltages on the secondary circuit.

A

True