3-1-14 Transformers —Connections Flashcards
The primary side of a three transformer wye-delta bank is always grounded.
False
When connecting a three-transformer wye-delta bank for 120/240-volt 4-wire service, it is critical to leave the grounding straps in place on all transformers.
False
The primary neutral must be tied firmly to the __?__ or else high voltages may occur on the secondary side.
system neutral
If a customer’s demand for power at a new plant is 450 kilowatts, most likely three __?__transformers would be used to serve the load.
167 kVA
One delta primary is 13,800 volts. Of those listed below, another delta primary is __?__.
2400
If a customer requests 277/480 volts, 3-phase, 4-wire, only __?__ volt transformers can be used.
277
On a two transformer bank supplying 120/240 volts, 3-phase, 4-wire, the transformer that does not supply the 120/240 volts is called the __?__.
power pot
An open wye-delta bank has a kVA rating of __?__ of the two transformers.
86.6%
If a 100-kilovolt-ampere transformer fails in a 300-kilovolt-ampere bank, the bank can be reconnected to an open wye-delta if the customer’s load is less than __?__.
173 kVA
When connecting a 3-phase transformer bank to an open-wye-delta the primary neutral also carries the full load current.
True
The phantom voltage that might be read between the three secondary phases and ground of a 240 ungrounded bank is __?__.
138
If a CSP transformer is used in a three transformer bank as the lighter transformer and the CSP’s secondary breaker opens (trips), it will cause unequal voltages on the single-phase loads.
True
Unlike the wye-delta connection, there is no third harmonic voltage in a __?__ connection.
delta-delta
The basic rule for connecting three-transformer coils in a delta is __?__ markings from each coil are connected together.
unlike
The voltage of the winding (coil) is __?__ of the voltage between conductors in a wye connection.
58%