1
Q

If a customer’s demand is for 450-kilowatt, 480-volt, 3-wire, each transformer in the bank must supply __?__ of the load.

A

150 kW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When paralleling single-phase transformers, if the impedance is more than __?__ from one transformer to another, dangerous overloading of one of the transformers will occur.

A

7.5%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

There is no flexibility in selecting transformers to perform a particular job.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If a customer requests a 240-volt, 3-phase, 3-wire service, transformers rated __?__ or 120/240 volts can be used.

A

240/480 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

In an open bank with a delta connected secondary, the transformer with the ground at X2 is called the __?__ transformer.

A

lighter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A three-transformer wye-delta bank can be connected as an open-wye-open-delta, but the kVA rating of the bank will be reduced to __?__ of the original bank.

A

57.7%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A 240-volt, 3-phase, 3-wire service cannot be supplied by using two 120/240-volt transformers connected as an open-wye-open-delta bank.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If a three transformer wye-delta bank is connected to open wye-open delta, and the primary bus neutral is left floating, __?__ of the phase to ground voltage will be present on the wire.

A

50%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If a transformer bank is connected 480 or 240 3-phase, 3-wire delta, a __?__ voltage can be measured between the phases and ground under certain circumstances.

A

phantom

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In order to provide 3-phase, 3-wire service from three transformers, all neutral straps must be removed from the transformers.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

In a 120/240, 3-phase, 4-wire service, C phase is normally called the __?__.

A

wild leg

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The formula for calculating the kVA that is being drawn off a single transformer is kVA=__?__.

A

VI /1000

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

On a three-transformer bank connected 120/240 4-wire, 3-phase, the lighter transformer carries __?__ of the single phase load.

A

2/3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

According to this lesson, a CSP transformer should not be used as the lighter transformer in a three transformer bank supplying a 120/240 4-wire, 3-phase service because if the CSPs secondary breaker opens, the neutral will become isolated.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If two transformer fuses open on a 7,200/12,470, three transformer bank that has the primary bus floated, the voltage on the bus will be __?__.

A

7200 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When using three 120/240 volt transformers to supply a 120/208 3-phase, 4-wire service, the internal secondary leads must be reconfigured.

A

True

17
Q

The delta-delta connection is also called the star-star connection.

A

False

18
Q

One disadvantage of the __?__ connection is that third harmonic currents are allowed to flow.

A

wye-delta

19
Q

With the wye grounded on a three transformer, wye-delta bank, the bank will act as a(n) __?__ bank if one primary phase is lost.

A

open wye - open delta

20
Q

Transformer banks with an ungrounded primary are prone to ferroresonance.

A

True

21
Q

Single transformers used in a 277/480 bank have only one secondary coil that is rated at 480 volts.

A

False