060201a Water Distribution Flow and Water Heaters Flashcards
What is the reason for having a recirculation line on a hot water distribution line?
To supply hot water to the furthest fixtures immediately
Ballcock valves come in all shapes and sizes. What is the most important factor about them?
They must be of the anti-siphon type
Installing a check valve on a water service near the house shut-off valve…
Creates a closed water system
Psi and time limit for testing a water distribution system?
100 psi for 2 hours
Maximum pressure at the fixture in a water distribution system?
550 kPa (80psi)
A meter bypass must be installed if the meter is…
Larger than 1 1/4”
Minimum water service pipe?
3/4”
Best form of backflow prevention?
Air gap (2x spout diameter no less than 1”)
An air break must be a minimum of…
1 pipe diameter or minimum 1”
Ideal test for potable water lines?
Water test (100 psi for 2 hours)
Max lead content when soldering water distribution lines?
0.2%
Minimum amount of shut offs when constructing a bypass?
3
A recirculation line is required when the run of pipe exceeds _____ or _____.
30 metres or 4 stories
In buildings other than single family or multi family dwellings these should be placed on every fixture, or at least located to isolate the water serving that room?
Isolation valve
Expansion tanks are required on these kind of water distribution systems?
Closed system