Minimum building sewer pipe diameter
4”
Minimum size of the main building cleanout
4”
Minimum roof flashing size
20x20
The portion of a fixture drain between the trap weir and the vent pipe fitting
Trap Arm
The pipe that connects a trap serving a fixture to another part of the drainage system
Fixture Drain
Minimum trap seal depth
38mm (50mm Acid)
Minimum trap arm length
2 pipe diameters
Minimum fall on a trap arm
1 pipe diameter
Minimum trap arm length of a 3” or larger floor drain tied to a building drain
18”
Maximum change of direction on a trap arm
135º
Maximum change of direction on a toilet trap arm
225º
Maximum vertical drop and horizontal run on toilet
1m (39”) drop, 3m (10’) run
Minimum roof penetration pipe diameter
4”
Every building in which plumbing is installed shall have one main vent that is not less than __________ in diameter.
3”
Maximum change of direction between cleanouts
45º