Westinghouse Ch. 1 & 2 Flashcards

1
Q

The device designation 52Y indicates the device is a?

A

Circuit breaker anti-pump auxiliary.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The accepted industry standard for showing relay contacts on circuit diagrams is to show the contacts in the position they assume when the relay is…

A

De-Energized.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Protective relay zones of protection are overlapped to?

A

Avoid leaving unprotected areas.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A high speed relay is defined as a relay that has an operating time which does not exceed?

A

3 to 5 Cycles

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Open circuits on power systems occur more frequently than short circuit faults. True or False.

A

False.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The circuit diagram usually gives the following three items of information about currents and voltages: location, direction, and polarity. It does not include what?

A

Magnitude.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

In a potential transformer the voltage drop from the polarity to the non-polarity marked terminals on the primary side is substantially in phase with the voltage drop from the polarity to the non-polarity marked terminals on the secondary side. True or False.

A

True.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A high current arc (in excess of 100 amperes) in the air has a nearly constant drop of around _____ volts per foot.

A

400

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The ground and the neutral point on a three phase system are by definition the same point. True or False

A

False.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The current flowing out at the polarity marked terminal on the secondary side of a current transformer is substantially in phase with the current flowing in at the polarity marked side or terminal on the primary. True or False?

A

True.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The term symmetrical components refers to a mathematical method of reducing any unbalanced three phase set of vectors into three _____ systems.

A

Balanced.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A well designed protective relay system should provide three basic operational characteristics. What are they?

A

Reliability.
Selectivity.
Speed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly