- T. F. Ambient temperature correction factors are applied when above above 30 degree C.
True
- T. F. The maximum allowable ampacity of a run of #4 NS90 aluminum triplex is 120 amps.
Table 36A. 4-004 (4)
Answer: False 125 Amps
- T. F. Service conduit embedded in not less than 50mm (2”) of concrete shall not be considered inside the building. As per Section 6.
6-208 (raceways or cables containing consumer’s service conductors shall be located outside building unless they are
(A) embedded in and encircled by not less than 50 mm of concrete or masonry where permitted by Section 12
(B) directly buried in accordance with Rule 6-300 and located beneath a concrete slab not less than 50 mm thick
- T. F. A three-way switch is not considered a disconnecting means
Rule 2-304 Disconnection
(2) Three-way or four-way switches shall not be considered a disconnection means.
Answer : True
- T. F. A 16 kW range in a residential occupancy shall be supplied by a minimum of #6 copper conductors. (75 Degree temperature rating)
Rule 8-300 Branch Circuits supplying electric ranges.
(1) (b) 8 kw plus 40 % of the amount by which the rating of the range exceeds 12 kw . So 9600 Watts / 240 volts
=40 Amps now Table 2 ampacities 50 Amps is good for a No.8 awg
Answer : False
- T. F. Consumer’s service includes the wiring from the service box to the utility’s transformer.
Service, Consumer’s definitions -
All that portion on the consumer’s installation from the service box or it’s equivalent up to and including the point at which the supply authority makes connection.
Answer : True
- T. F. The marking of electrical equipment is required to include the date of manufacture.
Rule 2-100 Marking of equipment
Answer : False
- T F. number 14 AWG is the smallest conductor size for a lighting branch circuit.
8.
- T. F. The current carrying capacity of 6 #6 RW90 XPLE copper conductors, installed in the same reaceway,feeding 2 - 3phase circuits is 75 amps.
Table 2 No. 6 can carry up to 65 Amps from the 75 C now derate with table 5C 0.80 x 65 = 52 Amps .
Answer : False
- T. F. The bond screw in an outlet box may be used for bonding connection and box support.
Rule 10-904 Bonding conductor connection to circuits and equipment . (3) The bonding connection shall be secured to every metal box by means of a bonding screw that shall be used for no other purpose.
Answer : False
- T. F. Table 16 is used for determining the grounding conductor size for residential services.
11.
- T. F. Generally, system ground may be spliced.
Rule 10-806 Installation of system grounding conductors (1.) The grounding conductor for a system ground shall be without joint or splice throughout its length, except in the case of busbars, thermit-welded joints, compression connectors applied with a compression tool compatible with the particular connector, or whereas it is necessary to control the effects of stray earth current, devices specifically approved for Connection in series with the grounding conductor.
Answer: True
- T. F. Bonding conductor connections which depend on solder shall not be used.
Rule 10-904 Bonding conductor connection to circuits and equipment (2) Connections that depend upon solder shall not be used.
Answer: True
- T. F. A #12 aluminum is the smallest size aluminum conductor that can be used for a branch circuit.
?
- T. F. Tech cable may be buried to a minimum depth of 450 mm without mechanical protection in area subject to vehicular traffic.
False table 53 600 mm