Code Questions 4 th Year Flashcards

1
Q

T or F The polarity mark of a CT must be on the load side of the installation.

A

Answer : True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

T or F A separate bonding conductor is not required with flexible metal conduit.

A

Answer: True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

T or F Cable tray systems have to be bonded at least every 20 meters.

A

Answer : False

Rule 12-2208 (1) 15 m

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

High voltage, from the standpoint of the CEC, is voltage :

A.) over 600 V
B.) over 750 V
C.) between 2,400 and 69,000V
D.) over 1000 V

A

Answer: B over 750

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

All medium-voltage cables above ___________ Volts are required to have insulation.

A.) 750
B.) 1000
C.) 2000
D.) 5000

A

Answer: D.5000V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Insulation-level ratings on medium voltage cables are mainly classified as .

A

Answer: 100 and 133 %

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The most common form of relay protection is ?

A

Answer : overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which table in the CEC provides information on the rating of HV fuses for transformer?

A

Answer: Table 50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Which table provides information as to the minimum spacing distances between HV fuses assembled in the field?

A

Answer : Table 35

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Under a fault condition, the maximum voltage rise on all parts of the station grid should not exceed .

A

Answer: 5000V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the minimum vertical ground clearance for a 15KV open line conductors?

A

Answer: 61 m

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

T or F Isolating Switch ok to use to interrupt current ?

A

Answer: False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

T or F can OL heaters be ahead of power contacts ?

A

Answer: False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

T or F light fixtures must have a bonded cover.

A

Answer: True 10-904 (6)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

T or F can 3 #3’s be protected by 125 A overcurrent device.

A

Answer: False 14-104 (a)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Servicebox in a bus shelter. Gives some minimal lighting load of about 3-4 amps you need a minimum service conductor of?

A

Answer: #8 AL 6-302 (4)

17
Q

House Calc
46’x 38’ w full basement
12 kw Range , 6 Kw Dryer, 4.5 kw Hwtr, 6 kw sauna , 12A/120V oil furnace

A

Answer:
Calculated Service demand : 94.27 Amps

Min ampacity of service conductors 100 Amps
Min Main breaker Size : 100 Amps
Min Rw90 Aluminum Conductors #2 AL ( table 39 5% Rule)
Min Conduit size : 27 using table 10 A
Min circuit breaker spaces: 24

18
Q

You are changing a defective receptacle in a hospital where there is a brown conductor and an Orange conductor connected to the nickel-plated terminal. What do you do ?

A

Answer: Install new receptacle and reconnect the same way.

19
Q

A circuit contains only 240 V mogul base, incandescent lamps may have a max wattage of ?

A

Answer: (.8x40x240) = 7680 W

20
Q

Oil filled motor starters contain up to ________ L of oil in the group before having to be installed In a vault .

A

Answer: 138 L Rule : 26-012 (3)

21
Q

A 3 phase 200 KVA oil filled transformer rated 575/120/208

used for a lighting load . Secondary fused at 125% What is max overcurrent permitted on primary ?

A

Answer : 603 Amps

22
Q

A paint mixing room for auto body shop is classed as a .?

A

Answer : Class 1 ,ZoneII Rule : 20-302-3

23
Q

What are the max number of lighting branch circuits allowed before a distribution panel is required to be installed ?

A

Answer : 2 - single phase

3 - 3 phase Rule: 14-110