T or F The polarity mark of a CT must be on the load side of the installation.
Answer : True
T or F A separate bonding conductor is not required with flexible metal conduit.
Answer: True
T or F Cable tray systems have to be bonded at least every 20 meters.
Answer : False
Rule 12-2208 (1) 15 m
High voltage, from the standpoint of the CEC, is voltage :
A.) over 600 V
B.) over 750 V
C.) between 2,400 and 69,000V
D.) over 1000 V
Answer: B over 750
All medium-voltage cables above ___________ Volts are required to have insulation.
A.) 750
B.) 1000
C.) 2000
D.) 5000
Answer: D.5000V
Insulation-level ratings on medium voltage cables are mainly classified as .
Answer: 100 and 133 %
The most common form of relay protection is ?
Answer : overcurrent
Which table in the CEC provides information on the rating of HV fuses for transformer?
Answer: Table 50
Which table provides information as to the minimum spacing distances between HV fuses assembled in the field?
Answer : Table 35
Under a fault condition, the maximum voltage rise on all parts of the station grid should not exceed .
Answer: 5000V
What is the minimum vertical ground clearance for a 15KV open line conductors?
Answer: 61 m
T or F Isolating Switch ok to use to interrupt current ?
Answer: False
T or F can OL heaters be ahead of power contacts ?
Answer: False
T or F light fixtures must have a bonded cover.
Answer: True 10-904 (6)
T or F can 3 #3’s be protected by 125 A overcurrent device.
Answer: False 14-104 (a)
Servicebox in a bus shelter. Gives some minimal lighting load of about 3-4 amps you need a minimum service conductor of?
Answer: #8 AL 6-302 (4)
House Calc
46’x 38’ w full basement
12 kw Range , 6 Kw Dryer, 4.5 kw Hwtr, 6 kw sauna , 12A/120V oil furnace
Answer:
Calculated Service demand : 94.27 Amps
Min ampacity of service conductors 100 Amps
Min Main breaker Size : 100 Amps
Min Rw90 Aluminum Conductors #2 AL ( table 39 5% Rule)
Min Conduit size : 27 using table 10 A
Min circuit breaker spaces: 24
You are changing a defective receptacle in a hospital where there is a brown conductor and an Orange conductor connected to the nickel-plated terminal. What do you do ?
Answer: Install new receptacle and reconnect the same way.
A circuit contains only 240 V mogul base, incandescent lamps may have a max wattage of ?
Answer: (.8x40x240) = 7680 W
Oil filled motor starters contain up to ________ L of oil in the group before having to be installed In a vault .
Answer: 138 L Rule : 26-012 (3)
A 3 phase 200 KVA oil filled transformer rated 575/120/208
used for a lighting load . Secondary fused at 125% What is max overcurrent permitted on primary ?
Answer : 603 Amps
A paint mixing room for auto body shop is classed as a .?
Answer : Class 1 ,ZoneII Rule : 20-302-3
What are the max number of lighting branch circuits allowed before a distribution panel is required to be installed ?
Answer : 2 - single phase
3 - 3 phase Rule: 14-110