T or F The polarity mark of a CT must be on the load side of the installation.
Answer : True
T or F A separate bonding conductor is not required with flexible metal conduit.
Answer: True
T or F Cable tray systems have to be bonded at least every 20 meters.
Answer : False
Rule 12-2208 (1) 15 m
High voltage, from the standpoint of the CEC, is voltage :
A.) over 600 V
B.) over 750 V
C.) between 2,400 and 69,000V
D.) over 1000 V
Answer: B over 750
All medium-voltage cables above ___________ Volts are required to have insulation.
A.) 750
B.) 1000
C.) 2000
D.) 5000
Answer: D.5000V
Insulation-level ratings on medium voltage cables are mainly classified as .
Answer: 100 and 133 %
The most common form of relay protection is ?
Answer : overcurrent
Which table in the CEC provides information on the rating of HV fuses for transformer?
Answer: Table 50
Which table provides information as to the minimum spacing distances between HV fuses assembled in the field?
Answer : Table 35
Under a fault condition, the maximum voltage rise on all parts of the station grid should not exceed .
Answer: 5000V
What is the minimum vertical ground clearance for a 15KV open line conductors?
Answer: 61 m
T or F Isolating Switch ok to use to interrupt current ?
Answer: False
T or F can OL heaters be ahead of power contacts ?
Answer: False
T or F light fixtures must have a bonded cover.
Answer: True 10-904 (6)
T or F can 3 #3’s be protected by 125 A overcurrent device.
Answer: False 14-104 (a)