Good source of supply air begins with a reliable _________
compressor
Once the supply air leaves the compressor it passes through the refrigerated ___ ____ and next through the _____ station and out to each of the thermostats
air dryer, filter station
The tank of the compressor condenses water and must be drained using an _____ drain
auto
Hot moist air leaving the comp must be dehumidified using a refrigerated ___ dryer
air
Filter station cleans the air with a _____ and PRV ______ main air pressure to correct pressure
filter, reduces
Filter in filter station removes ____ and debris
dust
PRV reduces pressure coming from ________ to proper working pressure (100psig to 18psig)
compressor
Pneumatic controls are _________ modulating
inherently
Inherently modulating means the controls _____ air to modulate amount of heat required
bleed
Pneumatic controls that are inherently modulating are able to replace heat proportionate to ____ ____
heat loss
Controller modulated output:
- output called ____ line pressure
- output modulates between 3 and ___psig
- branch
2. 3 and 13psig
How does a thermostat modulate it’s output?
A bleed device known as nozzle-flapper assembly
- As temperature varies, the ______ force varies and corresponding pressure is calibrated to vary between 3 and 13psig
- Same pressure in branch line going to actuator, bimetal flapper assembly is configured to increase or decrease as temp falls
flapper