Economizer exercise quiz Flashcards

1
Q

What is an economizer?

A

uses the cooler temperatures outside to provide cooling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Why use an economizer?

A

free cooling without using compressor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

what is the code requirement for an HVAC system?

A

to meet required outdoor air to space

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

what must happen to opperate the economizer?

A

call for cooling through economizer logic controller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

what will the conditions have to be in for the compressor to energize?

A

when outdoor air is above enthalpy set point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

what temperature mixed air temperature should be maintained and when will the dampers begin to modulate?

A

55F, when temp goes below 55F damper on economizer will modulate closed and mix with return air to maintain 55F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

what must be energized to bring the compressor on in economizer mode?

A

y2 signal to the unit that allows compressor to turn on

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

what is recomended for the economizer to work properly? and why?

A

minimum 2-stage thermostat to function properly, you need another signal to turn on mechanical cooling to help economizer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

what is a major cause of economizer problems?

A

economizer not being properly set up

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Describe:
1. ExH -

 2. Min Pos - 
3. DCV Max & DVC set -
 4. ABCD Enthalpy setpoint -
A
  1. setting controls at what point power exhaust energizes
  2. when terminals receive 24v the dampers will open to minimum position to bring in outside air
  3. potentiometers to position dampers in response to an input from the co2 sensors
  4. By region and preference is where set point should be. determines what position economizer will allow free cooling
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

when is the exhaust mode used?

A

with a power exhaust

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

what is the porpose of the time delay in exhaust mode and how long is it?

A

so exhaust fan does not put building into a negative pressure. About 45 sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

what must the thermostat be calling for in order to start the minimum position?

A

fan switch to “ON” G is energized

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

what is the mixed air temperature formula?

A

(OAT x OA%) x (RAT x RA%) = MAT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

what is the MAT if you require 20% fresh air if OAT is 85°F and RA is 71°F?

A

(85 x 20) x (71 x 80) = 73.8F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

what is used whith the IAQ setting?

A

co2 detector

17
Q

where should the answer from 16 be located?

A

in the space or building

18
Q

when is the freeze protection enabled?

A

OAT below 45F

19
Q

explain why freeze protection is required when useing an economizer?

A

if temp drops below 45F, risk of air blowing on water lines could cause freezing

20
Q

what is the relationship between humidity and temperature?

A

as humidity goes up, temperature goes down

21
Q

what is the porpose of the discharge sensor?

A

to maintain a 55F discharge or mixed air into the space

22
Q

what are the terminals is the discharge thermostat hooked up to? (Honeywell logic module)

A

T & T1

23
Q

how do youtest the mixed air/discharge sensor?

A

attach ohmmeter to 2 wires on sensor and check the chart

24
Q

what is imporyant to check on the enthalpy sensor?

A

polarity So and S+

25
Q

how many mA should you read if the temperature is 80°F 60% Relative humidity?

A

slightly over 8ma

26
Q

what tools are required to test the enthalpy sensor?

A

psychrometer and DC ammeter

27
Q

what two terminals do youmeasure between when testing the enthalpy sensor?

A

to S on the sensor and the negative lead to either the wire or S on the controller

28
Q

what should be happening if you do not see voltage on terminals TR1 - 4?

A

outdoor damper should be open and compressor #1 should be running

29
Q

when will you see power at TR & TR1, whats the voltage?

A

should have 24v anytime the blower is running

30
Q

wher is Y1 connected to on the module and what does it tell the economizer to do?

A

terminal 1 is Y1 into the module, looks to see if OA is suitable for cooling

31
Q

if T to T1 are open and a jumper accross So to + what shoul you see on a single enthalpy economizer?

A

LED is on and outside air damper closes to a minimum position

32
Q

if the damper is closeing instead of opening what should you check if useing a belimo motor?

A

check switch on motor to ensure you have proper rotation

33
Q

during a regular maintenance what should you pay attention to, to prevent a failure of cooling operations?

A

electrical connections if loose or corroded

34
Q

if the economizer fails, what terminals do you jumper to bring on mechanical cooling?

A

R and Y2