What is an economizer?
uses the cooler temperatures outside to provide cooling
Why use an economizer?
free cooling without using compressor
what is the code requirement for an HVAC system?
to meet required outdoor air to space
what must happen to opperate the economizer?
call for cooling through economizer logic controller
what will the conditions have to be in for the compressor to energize?
when outdoor air is above enthalpy set point
what temperature mixed air temperature should be maintained and when will the dampers begin to modulate?
55F, when temp goes below 55F damper on economizer will modulate closed and mix with return air to maintain 55F
what must be energized to bring the compressor on in economizer mode?
y2 signal to the unit that allows compressor to turn on
what is recomended for the economizer to work properly? and why?
minimum 2-stage thermostat to function properly, you need another signal to turn on mechanical cooling to help economizer
what is a major cause of economizer problems?
economizer not being properly set up
Describe:
1. ExH -
2. Min Pos - 3. DCV Max & DVC set - 4. ABCD Enthalpy setpoint -
- setting controls at what point power exhaust energizes
- when terminals receive 24v the dampers will open to minimum position to bring in outside air
- potentiometers to position dampers in response to an input from the co2 sensors
- By region and preference is where set point should be. determines what position economizer will allow free cooling
when is the exhaust mode used?
with a power exhaust
what is the porpose of the time delay in exhaust mode and how long is it?
so exhaust fan does not put building into a negative pressure. About 45 sec
what must the thermostat be calling for in order to start the minimum position?
fan switch to “ON” G is energized
what is the mixed air temperature formula?
(OAT x OA%) x (RAT x RA%) = MAT
what is the MAT if you require 20% fresh air if OAT is 85°F and RA is 71°F?
(85 x 20) x (71 x 80) = 73.8F