Who issues permits for approved of domestic LP gas systems
Station personnel issue all permits and conduct maintenance inspections
Who issues permits for commercial and industrial LP gas systems
Regional fire prevention unit for vessels having less than 1200 gallons
Who issues permits for LP gas systems 1200 gallons or more
Petro Chem unit of fire prevention
What happens to all permits issued for LP gas installations
One copy is sent to the jurisdictional Firestation one copy sent to petro chemical unit
What is the signage requirement for all LP gas tanks over 60 gallons in capacity
Danger flammable liquid and no smoking or open flame permitted in 3 inch red letters on a white background on two sides
What must be placed on all stationary above ground LP gas tanks
NFPA 704 Placard
What are the requirements for protections for above ground LP gas tanks
Must be protected from vehicle damage by guard post concrete filled schedule 40 steel 4 inches or 6 inches for truck traffic 3 feet concrete footing 15 inches or more in diameter 5 feet above ground level 4' or less spacing 5' or more from tank
What is the distance from Street sidewalk or property line for stationary LP storage tanks
Not less than 10 feet for tanks 125 to 500 gallons and
25 feet for tanks 501 gallons or more
Who is responsible for maintenance inspections of LPG containers and commercial and industrial systems
Station personnel in occupancies they are responsible for
How far does weeds grass brush trash and other combustible materials need to be from LPG tanks or containers
No less than 10 feet away
Who is responsible for the inspection of production studio And soundstages
Fire prevention division
What is the 4 foot line on sound stage and studios
An exit Aisle and shall be maintained clear of all obstructions at all times
What are the requirements for a 4 foot line
A painted yellow line 3 inches wide on the floor 4 feet from the wall extending around the entire perimeter of the interior of the building with lettering every 10 feet that says "exit way do not block"
What is the maximum travel distance to an exit at soundstage or studio
150 feet to an exit
What is required on a soundstage or studio if special-effects using fire or explosives will be used
A fire safety officer or advisor