Unit 5: Box and Raceway Sizing Flashcards

Interpret NEC box fill calculations, determine required box and raceway sizes, and verify compliance with installation requirements.

1
Q

Fill in the blank:

In Class II, Division 1 locations, where pendant mounted luminaires are suspended by rigid metal conduit (RMC) or intermediate metal conduit (IMC) and a means for flexibility is not provided, the conduit stems shall have a length of not more than ________.

A

12 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

All hydromassage bathtub metal piping systems and all grounded metal parts in contact with the circulating water associated with the bathtub shall be bonded together using a solid copper bonding jumper not smaller than ________.

A

8 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

Where power-limited fire alarm (PLFA) circuit conductors pass through a wall or floor, the conductors shall be protected by a metal raceway or nonmetallic conduit up to a height of at LEAST ________ above the floor, unless other means of protection is provided.

A

7 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

Luminaires installed in exposed or concealed locations under metal-corrugated sheet roof decking shall be installed and supported so there is not less than ________ clearance from the lowest surface of the roof decking to the top of the luminaire.

A

1 ½ in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

Transformers with ventilation openings shall be installed so the ventilating openings are not blocked by walls or other obstructions. The required clearances shall be ________.

A

clearly marked on the transformer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

Where a one-family or two-family dwelling unit has a three (3) car attached garage, the NEC® requires a MINIMUM of ________ 125-volt, single-phase, 15- or 20-ampere receptacles to be installed in the garage.

A

three

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

With respect to messenger-supported service-drop conductors and open overhead wiring operating at 0 to 750 volts to ground, the MINIMUM vertical clearance that must be maintained from the base of a swimming pool diving board and the conductors is ________.

A

22 ½ feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Determine the MINIMUM required size 75 deg. C rated conductors permitted to be used to supply a demand load of 200 amperes where provided with a 208Y/120-volt, 3- phase 4-wire, electrical system. Consider all four (4) conductors to be current-carrying and the ambient temperature is 120 deg. F.

A

400 kcmil

200 amperes (load)/ .75 (temp. cor.) x .8 (adj. factor) = 200 = 333 amperes/ .6
Size 400 kcmil conductors with an ampacity of 335 amperes
should
be selected from Table 310.16.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

A metal junction box to be installed will contain the following conductors:

  • three - size 6 AWG ungrounded conductors
  • three - size 6 AWG grounded conductors
  • one size 8 AWG grounding conductor
  • three - size 12 AWG ungrounded conductors
  • three - size 12 AWG grounded conductors
  • one - size 12 AWG grounding conductor

The junction box is required to have a volume of at LEAST ________.

A

46.50 cubic in.

6 AWG ungrounded conductors - 3 x 5.00 cu. in. = 15.00 cu. in.
6 AWG grounded conductors - 3 x 5.00 cu. in. = 15.00 cu. in.
8 AWG grounding conductor - 1 x 3.00 cu. in. = 3.00 cu. in.
12 AWG ungrounded conductors - 3 x 2.25 cu. in. = 6.75 cu. in.
12 AWG grounded conductors - 3 x 2.25 cu. in. = 6.75 cu. in.
12 AWG grounding conductor - 1 x -0- cu. in. = -0- cu. in.
TOTAL = 46.50 cu. in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fill in the blank:

In regard to permanently installed swimming pools, where necessary to employ flexible connections to a pool pump motor, ________ shall be permitted as the wiring method(s).

I. UF cable
II. liquidtight flexible metal conduit (LFMC)

A

II only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

In regard to legally required standby systems, transfer switches shall be ________ and marked for emergency system or legally required standby use and approved by the authority having jurisdiction.

A

automatic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

In commercial vehicle repair garages, lamps and lampholders for fixed lighting located over lanes through which vehicles are commonly driven, shall be located not less than ________ above the floor level, unless the luminaires are of the totally enclosed type.

A

12 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Determine the maximum permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 10 hp, 208-volt, 3-phase, squirrel cage, Design B, continuous-duty motor. Assume the motor will start at this setting and exceptions are not applicable.

A

77.0 amperes

FLC of 10 hp motor = 30.8 amperes x 250% = 77 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of approved materials that have a MINIMUM fire-resistance rating of ________.

A

3 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

At a truck plaza, every electrified truck parking space intended to provide an electrical supply for transport refrigerated units (TRUs), shall be equipped with a ________ receptacle outlet.

I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire
II. 60 ampere, 208-volt, 3-phase, 3-pole, 4-wire

A

either I or I

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the MAXIMUM distance allowed to support intermediate metal conduit (IMC) from a junction box, where structural members do not readily permit fastening?

17
Q

Fill in the blank:

All signs provided with electric power shall be installed at a height of not less than _______\__ above areas accessible to vehicles unless protected from physical damage.

18
Q

Fill in the blank:

Photovoltaic equipment shall be provided with isolating devices or equipment disconnecting means in circuits connected to equipment at a location within the equipment, or within sight and within ________ of the equipment.

19
Q

Determine the MAXIMUM standard size inverse time circuit breaker permitted for branch circuit, short-circuit, and ground-fault protection for a 50 hp, ac motor, when given the following related information.

  • continuous-duty
  • induction type
  • 3-phase, 480-volt
  • Design L
  • nameplate rating 62 amperes
A

250 amperes

FLC of 50 hp motor = 65 amperes x 400% = 260 amperes

20
Q

Fill in the blank:

In general, on the load side of the point of grounding of a separately derived system such as a transformer, a grounded conductor is not permitted to be connected to ________.

A

any of these

21
Q

Fill in the blank:

The life safety branch of the essential electrical system of a health care facility shall provide power to ________.

I. automatic doors used for building egress
II. illumination of electrical equipment rooms

22
Q

Fill in the blank:

Intrinsically safe apparatus, associated apparatus, and other equipment shall be installed ________.

A

in accordance with the control drawings

23
Q

Fill in the blank:

The grounded conductor of a 3-phase, 3-wire, delta service shall have an ampacity not less than ________.

A

that of the ungrounded conductors

24
Q

Fill in the blank:

Where a 150 kVA service transformer has a 480Y/277- volt, 3-phase primary and a 208Y/120- volt, 3-phase secondary, the full-load ampere rating on the primary side of the transformer is ________.

A

180 amperes

I = kVA x 1,000/E x 1.732
= 150 x 1,000/480 x 1.732
= 150,000/831.36
= 180.32 amperes

25
# Fill in the blank: Direct-buried cables or conductors located in a trench below 2 inch thick concrete or equivalent shall have a MINIMUM cover requirement of \_\_\_\_\_\_\_\_.
18 in.