Trench Encasements, Backfill, and Compaction Flashcards
Trench load design for all types of pipe is based on stable bedding and firm foundations.
True
Asphalt and concrete overlays will crack and pose future problems if the base of the trench is not stable.
True
Full concrete encasement should be three inches on the top, bottom, and sides of the conduits.
True
Conduit is subject to temperature rise as the concrete cures. The temperature rise may cause the conduit to expand slightly and this should be compensated for by pouring the concrete from the center of the run, thereby allowing the free end to expand.
True
What are the three types of concrete?
Normal
High early strength
Sulfate-resisting
High early strength Portland cement should be used for all concrete construction when it is necessary to remove forms and open structures to traffic after the concrete has been placed.
True
What is the most common reason for cable failure in direct buried cable?
stones pressing against the cable
Backfill should be free of large stones (three inches in any dimension or larger should not be permitted), nor should frozen or muddy soil, organic material, clods, trash, or any object that may cause a void to form in the backfill be allowed.
True
To avoid damage to conduits, mechanical tampers should not be used until conduit configurations have been covered with at least 12 inches of hand-tamped backfill.
True
Backfilling and tamping alongside conduits should be performed in two-inch thick layers until level with the top of the conduit or duct configurations
True
Trenches should be compacted to
90%
Top 6” compacted to 95%
Class ? concrete is normally used for conduit base or top protection.
2A
Class 2 concrete is normally used for trench encasement and should have a compressive strength at ? seven days after the pour.
2,000 psi
The type of Portland cement that may be used during low temperatures is ? .
high early strength
Rebar is never used to reinforce an encasement because it will interfere with the electromagnetic field around the cables.
False