Installing Cable in Underground Vault or Manhole Flashcards

1
Q

Cables should be sealed with paraffin or shrink wrap caps when? Why?

A

When left overnight or for more than eight hours.
Prevent moisture from entering the cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Cables should be ? in a manner which will prevent the cable from ? at the point where it enters the manhole or vault.

A

Supported
Kinking

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If a manhole is to have the cable looped between the entrance and the exit, the cable should circle the manhole at least ?

A

360 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where manholes are not to be looped, the cable should be routed on the walls ?

A

with the longest distance between points of entry and exit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Cables should be arranged to avoid ?

A

interference with duct or worker entrances into the manhole.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Cables should be routed in a manner that will allow adequate room for bending and terminating the cables.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Cables must be supported in a way that will not result in cable weight being placed on the termination point.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Cable bending radius is to be at least ? the cable diameter.

A

12 times

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Cables should not be directly fastened to support channels with wire or plastic ties.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Cables should be secured to racks with ? or mounted on a heavy-duty nonmetallic multi-mount cable support.

A

porcelain insulators and clamps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At least two racks should be installed in parallel on each manhole wall. The cable should not be supported by just one rack support in the manhole.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

At least one spare hook should be installed at each cable rack position for future cable installations.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Cable racks should be secured to the walls of the manhole with 3∕8 inch-16 drop-in anchors with a rated pullout working capacity of at least 2,100 pounds.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Bolts installed in vaults and manholes should be made of 303 stainless steel, rated for use in underground devices.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The ? is the only part of a power cable that can take a fairly high pulling tension.

A

core conductor(s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When pulling in cable using a wire-mesh grip with a swivel eye, the pulling tension is usually less than ? .

A

1,000lbs

17
Q

One way a duct can be checked for proper diameter and obstructions is to ? through the conduit.

A

pull a flexible steel mandrel

18
Q

If a cable is required to make a smooth low-friction 90° turn in a vault, a ? or lip-roller block would be used.

A

quadrant

19
Q

A weak link installed at the pulling eye acts as a mechanical fuse and breaks apart before a cable is overstretched during pulling operations.

A

true

20
Q

Depending on the jurisdiction, underground utility vaults (manholes) more than ? deep are considered to be an enclosed space.

A

4’

21
Q

To avoid an explosion caused by a spark, before removing the cover, remote probes are used to test the atmosphere of an enclosed space for oxygen deficiency, ? and vapors.

A

flammable gases

22
Q

When a blower is used to provide fresh air in an enclosed space such as a manhole, a blower with a capacity of ? cfm or greater is used.

A

1,000

23
Q

Historically, about 60% of fatalities involving confined spaces occur when ? .

A

attendants perform a rescue

24
Q

An impending fault is indicated when a cable in a vault has abnormalities such as oil or compound leaking, broken cable sheaths, hot localized surface temperatures, or swollen splices. When energized cables show symptoms of these types, the cable should be ? before anyone works in the vault.

A

de-energized

25
Q

When ventilating a vault (manhole) with a blower, the space should be ventilated for at least ? before entering.

A

5 min