Training Session Flashcards
Communication of Line Differential
Optical Fibre
Communication of PWP
Metallic pilot wire cable
Disadvantages of PWP
Length of the line (short or very long 20km) due to stabilization of looping resistance
When does CB trip due to PWP faulty?
When enough current is flowing through the cable to reach the threshold limit of the CT in the PWP to trip the CB
How is Guard Relay connected to PWP
Guard relay is connected in series with the PWP via NO/NC contacts
Why does Source CB only trip when Guard Relay with PWP
Load end guard relay does not see the fault current, hence only the source trips
Name and fault current rating of HRC fuse
Back up fuse, 3 times max load current
11 kV feeder BCU/BCPU CT ratio and Accuracy classes
BCPU(5P15) + Metering ratio(0.2S-FS5): 400/1 A
BBD + BBC(PX): 3200/ 1 A
How many CTs are connected in the secondary side of IDT in BMP stations
6
What is the ratio of CTs connected in the secondary of IDT?
3200/1 A
What is the new maximum short circuit current in the network?
31.2 kA/3s
What is the current maximum short current in the busbar?
25kA/3s
Will U/F protection operate when BCU fails?
U/F will not operate as it is within the BCU.
Indication of negative sequence on relay
I2
Type of CT used for EFI
Core balance CT