Busbar Protection Flashcards
What is ARC protection
3 Flash light sensors at the CB, Termination, and BB chamber to protect from flashover
33kV panels with ARC protection
ABB
Siemens
Energoinvest
GEC Alstom
Tamco
Merlin Gerin
Koncar
Operation considerations of ARC protection switchgear
Inadvertent operation during earth switch closing so arc prot. to be kept out by DPM
Principle of VEM ARC Protection
- Mechanical protection
- 3 limit switches at Termination, BB chamber, and CB compartment
- Limit switch operated by pressure
Differential principle in BB protection
Kirchhoff’s current law (comparing vector sum of current entering and leaving)
The difference is the magnitude of the fault current
Zone Protection in Busbar
Discriminating Zone
Check Zone
Features of Discriminating Zone
One zone per busbar
Each feeder has a separate CT
Checks vector sum of entering and leaving
Features of check zone
One for the whole busbar
Each feeder has a separate CT
Used to avoid unwanted tripping
When does the Busbar Trip?
When signal is received from both discriminating and check zone
What are the Mechanical Relays in the Network?
Buchholz
Oil Temp.
Winding Temp.
PRV
What are the Electrical Relays in the network?
OC
EF
REF
SBEF
PWP
DIFFERENTIAL RELAY
ARC PROTECTION
SEF
CHECK ZONE
DISCRIMINATING ZONE