What is the simplest way to view power in a three phase system?
By analyzing it as 3 - single phase circuits.
Why does ST = VL•IL•31/2 hold true for a wye connected load?
Because IΦ = IL &
VL = VΦ • 31/2.
Why does ST = VL•IL•31/2 hold true for a delta connected load?
Because VΦ = VL &
IL = IΦ • 31/2.
What is the unit of measurement for reactive power?
The Voltampere reactive;
VAr.
What is the unit of measurement for active power?
Watts;
W.
What is the definition of power factor?
The ratio of true power to apparent power.
Is a 3Φ motor normally balanced?
Yes, it does not require a wye neutral.
Typically, are there many ways to calculate circuit power in a balanced circuit?
Yes, You can calculate for one phase and multiply by 3, use the line values formula or add horizontal and vertical components for the whole circuit.
Can you use the line value formula for power in an unbalanced 3 Φ delta load?
No, the horizontal and vertical values must be summed separately.
What is an example of a normally unbalanced load?
A 3 Φ 120/208V panelboard.
Which load connection uses more power? wye or delta.
Delta uses three times the power that wye does;
However the components connected in wye need only be rated for phase voltage.
Can a delta connected load be shown both as a rectangle and a triangle?
Yes, generally you can use your preference.