Test 5 Flashcards
If excessive amounts of metal in or on a building become energized and could be subject to personal contact, which of the following will provide additional safety measures:
a. Adequate bonding and grounding
b. Bonding
c. A bonding jumper
d. None of the above
a. Adequate bonding and grounding
An outlet for specific appliances, including laundry equipment, must be located within how many mm of the appliance:
a. 2000 mm
b. 900 mm
c. 1800 mm
d. 1000 mm
c. 1800 mm
Upon completion of construction or the conclusion of the purpose for which it was installed, temporary wiring shall be removed within which of the following time frames:
a. 31 days after an event
b. 60 days after the conclusion of an event or construction
c. 90 days after the completion
d. Immediately
d. Immediately
A traveling cable shall be allowed to run without using a raceway under which of the following conditions:
a. The distance from the first point support does not exceed 6 feet.
b. The conductors are grouped and taped together.
c. The conductors are in their original sheath.
d. All of the above
d. All of the above
Conductors that supply a fire pump motor must have a rating not less than ___ percent of the sum of the fire pump motor’s full load current and ____ percent of any associated fire pump accessory equipment:
a. 80, 100
b. 125, 100
c. 115, 125
d. 100, 100
b. 125, 100
The antenna for a satellite system must be grounded to which of the following
a. Interior metal water piping system, within 5 feet from its point of entrance
b. The building or structure grounding electrode system
c. An accessible means external to the building
d. All of the above
d. All of the above
Type UF cable shall be used for which of the following applications:
a. Concrete encased
b. Direct buried
c. Service entrance cable
d. None of the above
b. Direct buried
Service disconnect means shall clearly indicate which of the following:
a. The minimum and maximum voltage rating
b. If it is in the open or closed position
c. Both of the above
d. None of the above
b. If it is in the open or closed position
The total connected load in watts of three electric heaters rated 1000 watts and 1100 watts at 120 volts and 800 watts at 240 volts is:
a. 2417 watts
b. 2900 watts
c. 3100 watts
d. 5800 watts
a. 2417 watts
A continuous load is one in which the maximum current is expected to continue for at least which of the following:
a. 24 hours, non-stop
b. 12 hours or more
c. 6 hours or more
d. 3 hours or more
d. 3 hours or more
When installing rigid metal conduit (RMC), there cannot be more than the equivalent of four quarter bends (360 degrees) between which of the following:
a. Conduit bodies
b. Outlet boxes
c. Junction boxes
d. All of the above
d. All of the above
A nonmetallic wireway is not permitted in which of the following locations unless it is specifically marked otherwise:
a. Where the wireway would be exposed to sunlight
b. Where subject to corrosive vapors
c. In wet locations
d. All of the above
a. Where the wireway would be exposed to sunlight
Feeders that contain a common neutral are permitted to supply which of the following:
a. One, two or three sets of 3-wire feeders
b. Two sets of 4-wire feeders
c. Two sets of 5-wire feeders
d. All of the above
d. All of the above
Disregarding any exceptions, a conductor rated 56 amperes shall be protected by a fuse sized at which of the following:
a. 60 amp
b. 50 amp
c. 30 amp
d. 20 amp
a. 60 amp
Light and power systems conductors 600 volts or less may occupy the same enclosure only when all of the conductors meet which of the following requirements:
a. All of the conductors are insulated.
b. All conductors are insulated to meet the maximum temperature rating for the enclosure.
c. All conductors are insulated for the maximum voltage applied to any conductor in the enclosure.
d. None of the above
c. All conductors are insulated for the maximum voltage applied to any conductor in the enclosure.
Nine 8.0 sq mm THHN copper conductors in a conduit at 30 degrees C have a maximum allowable ampacity of which of the following:
a. 33 amperes each
b. 38.5 amperes each
c. 55 amperes each
d. 66 amperes each
b. 38.5 amperes each
The minimum individual amperes for two hot, ungrounded feeder circuit conductors running to a commercial building that has a general lighting load of 50,000 volt amperes, supplied by a single phase, 240 volt feeder circuit is closest to which of the following:
a. 208 amperes
b. 217.39 amperes
c. 228 amperes
d. 480 amperes
d. 480 amperes
Disregarding any exceptions, a copper-clad aluminum conductor used for overhead services must be at least which of the following sizes:
a. 3.5 sq mm
b. 5.5 sq mm
c. 8.0 sq mm
d. 14.0 sq mm
d. 14.0 sq mm
A multi-wire branch circuit that supplies more than one device on the same yoke in a dwelling unit must be protected by which of the following:
a. One fuse
b. Two single-pole circuit breakers that are tied together
c. Two single-pole circuit breakers that operate independently
d. One single-pole non-fused disconnect
b. Two single-pole circuit breakers that are tied together
Which of the following receptacles may be connected to small appliance circuits:
a. A garage ceiling receptacle for a garage door opener
b. A living room receptacle for a television set
c. A receptacle in the kitchen for an electric clock
d. None of the above
c. A receptacle in the kitchen for an electric clock