If an individual 30 amp branch circuit feeds a single non-motorized equipment receptacle, then the receptacle amperage must be which of the following:
a. 20
b. 30
c. 40
d. None of the above
b. 30
Conductors run in parallel raceways must have equipment grounding conductors which are which of the following:
a. Run in individual raceways
b. Supported every 6 inches
c. Run in parallel in each raceway
d. Protected from excessive temperature
c. Run in parallel in each raceway
A surge arrester of less than 1000 volts nominal shall have a ground connecting conductor which is no smaller than which of the following sizes:
a. 8.0 sq mm
b. 5.5 sq mm
c. 3.5 sq mm
d. 2.0 sq mm
d. 2.0 sq mm
When there is more than one nominal voltage system in the building, ungrounded feeder conductors must be which of the following:
a. Connected through a transfer switch
b. Separately identified
c. Run in individual conduits
d. Identified using the same color
b. Separately identified
Single-point grounding is allowed at the source of a separately derived system when which of the following conditions exists:
a. A separate equipment grounding conductor is provided at each building and enclosure
b. The neutral is insulated and isolated from earth, except at one location
c. An equipment grounding conductor is run with the phase conductors
d. All of the above
d. All of the above
The permitted identification of a size 14.0 sq mm or smaller insulated grounded conductor is which of the following:
a. A continuous white outer finish
b. Three yellow stripes down the length of a green insulated conductor
c. One blue stripe on a gray insulated conductor
d. All of the above
a. A continuous white outer finish
Branch circuits shall not be derived from autotransformers unless which of the
following exist:
a. The grounded conductor is protected from access by unauthorized personnel.
b. The autotransformer operates at less than 600 volts nominal.
c. The circuit supplied has a grounded conductor that is electrically
connected to a grounded conductor from the system that supplies the
autotransformer.
d. All of the above
c. The circuit supplied has a grounded conductor that is electrically
connected to a grounded conductor from the system that supplies the
autotransformer.
A two-wire AC circuit with two ungrounded conductors is permitted to be tapped
from ungrounded conductors of circuits that have which of the following:
a. Two switching devices
b. An automatic multi-pole switch
c. A grounded neutral conductor
d. None of the above
a. Two switching devices
The minimum size of an equipment grounding conductor used to ground
equipment with an automatic over current device rated at 20 amps in the circuit
ahead of the piece of equipment is which of the following:
a. 2.0 sq mm copper
b. 3.5 sq mm copper
c. 5.5 sq mm copper
d. 8.0 sq mm copper
b. 3.5 sq mm copper
Electrical systems that are grounded must meet which of the following
requirements:
a. Be connected to the earth in a way that limits the voltage caused by line
surges
b. Be connected to the earth in a manner that will stabilize the voltage to the
earth during normal operation
c. Both of the above
d. Either of the above
c. Both of the above
An electric 9 kW range shall have a minimum branch circuit size of which of the
following:
a. 15 amps
b. 20 amps
c. 30 amps
d. 40 amps
d. 40 amps
In a separately derived system, the TVSS shall be connected in which of the
following manners:
a. To each ungrounded connector
b. Outdoors, in an easily accessible location
c. To the corner grounded delta
d. To the load side of the first overcurrent device
d. To the load side of the first overcurrent device
A TVSS device shall not be installed under which of the following conditions:
a. On an impedance grounded system
b. If the TVSS is less than the maximum continuous phase-to-phase power
frequency that exists at the point of application
c. On circuits in excess of 600 volts
d. All of the above
d. All of the above
A 125 volt single-phase kitchen counter receptacle must meet which of the
following requirements:
a. Have ground-fault interruption protection
b. Be a maximum of 20 amps
c. Be a minimum of 15 amps
d. All of the above
d. All of the above
A surge arrestor may be installed under which of the following conditions:
a. On an impedance grounded system
b. On a service less than 1000 volts with a grounding electrode for the service
c. Either of the above
d. None of the above
b. On a service less than 1000 volts with a grounding electrode for the service
An impedance grounded neutral system is permitted to be installed if which of the
following conditions is met:
a. If installed to serve a line-to-neutral
b. If installed outside in an easily accessible location
c. Ground detectors are installed on the system
d. None of the above
c. Ground detectors are installed on the system
Multi-wire branch circuits are permitted to supply which of the following:
a. Only line-to-line neutral loads
b. Only one piece of utilization equipment
c. Both of the above
d. None of the above
c. Both of the above
The minimum size of an equipment grounding conductor used to ground
equipment with an automatic overcurrent device rated at 40 amps in the circuit
ahead of the piece of equipment is which of the following:
a. 8.0 sq mm copper
b. 8.0 sq mm aluminum
c. 5.5 sq mm aluminum
d. 5.5 sq mm copper
d. 5.5 sq mm copper
The size of the sole connection of a grounding electrode conductor connected to
a concrete-encased electrode shall not be required to be which of the following:
a. Larger than 2.0 sq mm copper
b. Connected to an electrode encased by at least 50 mm of concrete
c. Both of the above
d. None of the above
a. Larger than 2.0 sq mm copper
For a 30 amp receptacle connected to a 30 amp branch circuit supplying two or
more outlets, the total cord-and-plug load may not exceed which of the following
sizes:
a. 24 amps
b. 16 amps
c. 15 amps
d. 12 amps
a. 24 amps