Test 1 Flashcards
- 0POP04-AE-0003 Loss of power to 13.8 kV Standby Bus*
- *
What is a major concern if RCB chillwater is lost to the RCFCs?
Could cause RCB Chillwater relief to lift
Could cause low flow trip of RCB Chillers
- 0POP04-RP-0001 Loss of Automatic PZR Pressure Control*
- *
What conditions would cause you to enter 0POP04-RP-0001 Loss of Automatic PZR Pressure Control?
PZR Pressure Controller fails in Auto
PZR pressure control instrument fails
- 0POP04-TM-0003 Turbine Trip < P-9*
- *
At what Tavg would the operator place rods in manual?
577 ˚F
- 0POP04-CD-0001 Loss of Condensate Flow*
- *
What must be done if DA Level reaches 30%?
Trip the Rx
Go to 0POP05-EO-EO00
- 0POP04-TM-0003 Turbine Trip < P-9*
- *
What are the operator actions if the Throttle valves fail to close during a turbine trip?
Trip the Rx
Close MSIVs and MSIBs
Go To 0POP05-EO-EO00
- 0POP04-NI-0001 Nuclear Instrumentation Malfunction*
- *
If a power range NI fails, the operator must check that P-7, P-8, P-9, and P-10 are in their correct state within 1 hr. If they are not in their correct state, what must the operator do?
Enter LCO 3.0.3
- 0POP04-RC-0006 Shutdown LOCA*
- *
When is 0POP04-RC-0006 Shutdown LOCA applicable?
MODE 3 < 1000 psig
MODE 4
- 0POP04-CW-0001 Loss of Circulating Water Flow*
- *
If water boxes must be isolated for a loss of circulating water, then what precautions must be followed?
Do not isolate both water boxes in the same condenser shell
Do not isolate 11 North and 13 South b/c FW heater high level dumps enter the condenser in those water boxes
- With a reduction in CW flow isolating a water box will raise CW discharge pressure.
- CW discharge pressure needs to be maintained at least 3 psig to prevent pump runout.
- 0POP04-RC-0002 RCP Off Normal*
- *
What RCP Case and Shaft Vibrations would require the operator to trip the RCP?
Case Vibration:
≥ 5 mils
≥ 3 mils and rising ≥ 0.2 mils/hr
- Shaft Vibration:*
- *≥ 20 mils**
- *≥ 15 mils and rising ≥ 1 mils/hr**
- Ensure Rx Tripped
- Ensure Turbine Tripped
- Stop affected RCPs
- Perform 0POP05-EO-EO00
- 0POP04-OC-0001 Loss of OL-ACW*
- *
At what motor temperature should the operator secure the affected OL-ACW pump?
266 ˚F
Motor insulation starts to degrade.
- 0POP04-RC-0004 SG Tube Leakage*
- *
What must the operator do if PZR level reaches 17% and PZR level is still lowering?
Ensure Rx Tripped
Initiate SI
Perform 0POP05-EO-EO00
Must also take actions if:
- VCT Level cannot be maintained > 15% with CCP suction aligned to VCT.
- RCS leakrate exceeds 200 gpm and PZR level is lowering
- 0POP04-AE-0001 Loss of AC Power*
- *
If a Class 1E battery is realigned to an operating battery charger in ≤ 15 min AND ≤ 1 battery cell is jumpered, then what must be done to declare it OPERABLE?
Verify Operating Battery Charger normal float voltage ≥ 128.5 VDC
Note:
A Class 1E battery is INOPERABLE anytime it is NOT aligned to an operating battery charger.
- 0POP04-IA-0001 Loss of Instrument Air*
- *
What would the operator do if Instrument air were lost and VCT level reaches 10%?
Re-align suction of CCP to RWST
- 0POP04-RC-0006 Shutdown LOCA*
- *
When must the operator manually switch to cold leg recirc?
RWST < 75,000 gal (14%)
AND
Containment WR Sump Level > 15”
Must also place FHB Exhaust in service.
0POP04-TM-0004 Failure of PT-505/PT-506
Do rods have to be taken to manual if PT-506 fails?
Yes
Step 1.0 in 0POP04-TM-0004 places rods in manual regardless of instrument (PT-505/PT-506) or failure (High/Low).
Note:
Step 8.0 has the operator check which instrument failed and then take rods back to auto at US discretion.
- 0POP04-FW-0002 SGFP Trip*
- *
Operation in what power levels is not permitted with > 1 GV out of service?
20 - 75% Power
Could result in rotor damage due to Double Shock Condition.
- 0POP04-CR-0001 Loss of Condenser Vacuum*
- *
What must be done if main turbine vacuum is < 21” Hg?
Ensure Rx Tripped
Ensure Turbine Tripped
Perform 0POP05-EO-EO00
- 0POP04-TM-0005 Fast Load Reduction*
- *
What are the boration thumbrules to perform a fast load reduction from 100% to 10% RTP at EOL? (16,000 MWD/MTU or 190 ppm boron)
- 100% - 50%:*
- *191 gal / 10% RTP reduction**
- 50% - 10%:*
- *31 gal / 10% RTP reduction**
- The differential rod worth almost doubles as the ‘C’ control bank inserts; thus, compensating for power defect. Therefore, boron addition values less than 50% decrease sharply.*
Assumptions:
- 100% RTP
- Rods in Auto
- Tavg/Tref ≤ 3 ˚F
- ≥ 50 steps above RIL
Note:
≈ 5 min - 7 min delay before boration addition is observed in plant response.
- 0POP04-AE-0007 Loss of all AC while on S/D Cooling*
- *
What are the criteria to verify natural circulation?
SG Pressures - Stable or Lowering
RCS Hot Leg Temp - Stable or Lowering
CETs - Stable or Lowering
RCS Cold Leg Temp - Saturation Temp of SG Pressure
- 0POP04-TM-0005 Fast Load Reduction*
- *
Below what Rx Power level are we able to trip the Rx per 0POP04-TM-0005 Fast Load Reduction?
< 10% Rx Power
- 0POP04-AE-0007 Loss of all AC while on S/D Cooling*
- *
What is the preferred order for re-energizing ESF busses?
C-A-B
- 0POP04-AE-0005 Offsite Power System Degraded Voltage*
- *
What voltage on the north AND south bus would cause you to enter 0POP04-AE-0005 Offsite power system degraded voltage?
339 kV
- 0POP04-RC-0002 RCP Off Normal*
- *
What must the operator do if all seal cooling is lost to the #1 RCP seal?
Trip Rx
Ensure Main Turbine Tripped
Trip affected RCP within 1 minute
Perform 0POP05-EO-EO00
If RCP Seal temp < 230 ˚F:
- Ensure PDP Recirc Valve 100% open
- Start PDP
- Slowly close PDP Recirc Valve to lower seal water bearing temp < 1˚F/min
- 0POP04-NI-0001 Nuclear Instrumentation Malfunction*
- *
What are the operator immediate actions if the power range NIs are not functioning properly?
Place Rods in Manual
- *Place LPFRVs in Manual**
- If being used to feed SG*
Control SGWL between 68% - 74%
- 0POP04-CC-0001 CCW System Leak*
- *
If CCW is lost to the CCP Supplemental Cooler or to the CCP lube oil cooler, how long until CCP failure?
- Supplemental Cooler:*
- *4 minutes**
- Lube Oil Cooler:*
- *8 minutes**
- 0POP04-CD-0001 Loss of Condensate Flow*
- *
What must be done if DA Level reaches 40%?
Start Standby Condensate pump
Open Discharge valve
Done if the pump requires or does not require venting.
Note:
Tripping of a condensate pump and DA level lowering in an uncontrolled manner also have you start condensate pump but only if it does not require venting.
- 0POP04-RC-0006 Shutdown LOCA*
- *
When must the operator manually initiate makeup to the AFWST?
< 26% (138,000 gal)
- 0POP04-RA-0001 Radiation Monitoring System Alarm Response*
- *
Which radiation monitors that, if inoperable, require specific actions per 0POP04-RA-0001 Radiation Monitoring System Alarm Response?
- 8010B:*
- *8090 OR 8091 Functional**
- 8011:*
- *Tech Spec 3.4.6.1**
- 8050/8051:*
- *HPs set up an alternate monitor in RCB**
8055 OR 8099 Functional
- 0POP04-CW-0001 Loss of Circulating Water Flow*
- *
What operator actions are required if the plant is in MODE 1 -2 and no CW pumps are running?
Ensure Rx Tripped
Ensure Turbine Tripped
Perform 0POP05-EO-EO00
0POP04-CW-0002 Circ Water Piping Breach also has the operator:
- Isolate Main Steam
- Place on CW pumps in PTL
This is in addition to the above actions.
- 0POP04-TM-0001 Turbine Load Rejection*
- *
If a complete loss of turbine load or two governor valves fail closed with Rx Power > P-9, what must the operator do?
Trip the Rx
Perform 0POP05-EO-EO00
If < P-9:
- Trip the Turbine
- Go to 0POP04-TM-0003, Turbine Trip below P-9
Note:
Operation with > 1 Governor Valve out of service is NOT permissible because Turbine Load would be reduced to < 75% which is NOT allowable due to possible “double shock” scenarios.
- 0POP04-RA-0003 Loss of RM-11*
- *
What is the power supply to RM-11?
DP0100
Located in EAB 35’ Computer Room
- 0POP04-CR-0001 Loss of Condenser Vacuum*
- *
What are the important values of main condenser vacuum? (i.e. alarms, actuations, ect.)
- 26” Hg:*
- *Condenser Vacuum Low Alarm (≤ 80% power)**
Standby CARS pump starts
- 24” Hg:*
- *Condenser Vacuum Low Alarm (> 80 power)**
- 22” Hg:*
- *C-9**
- 21” Hg:*
- *Main Turbine Trip**
- 0PGP03-ZO-0041 Primary to Secondary Leakage*
- *
When are the N-16 monitors available to detect primary-to-secondary leakage?
>25% power
- Between 20% and 25% the N-16 monitors are unreliable.
- < 20% the N-16 monitors do not function.
- 0POP04-RC-0002 RCP Off Normal*
- *
What RCP #1 Seal leakoff flow would require the operator to trip the RCP?
> 6 gpm
- Ensure Rx Tripped
- Ensure Turbine Tripped
- Stop affected RCPs
- Perform 0POP05-EO-EO00
- Close affected RCP Number 1 Seal leakoff isolation valve between 3 to 5 minutes after stopping RCP.
- 0POP04-FW-0002 SGFP Trip*
- *
What must the operator do if Rx Power is ≥ 5% and SGNR Water Level cannot be maintained < 87.5%?
Trip Rx
Perform 0POP05-EO-EO00
- 0POP04-AE-0007 Loss of all AC while on S/D Cooling*
- *
How many times can the SG PORVs be stroked with the energy in the accumulators alone?
1.5 times
Assumes SG PORVs are closed and only opening to 50%.
- 0POP04-CW-0001 Loss of Circulating Water Flow*
- *
What CW pump motor stator temperature would require the operator to trip the affected CW pump?
≥ 250 ˚F
- LOT 202.15 SGWLC*
- *
How does the SGFPTs control SGWL?
- Pressure Mismatch:*
- *Actual D/P - Reference D/P**
- Actual D/P:*
- *Feed Pressure (PT-558) - Steam Pressure (PT-557)**
- Reference D/P:*
- *0% - 20% Steam Flow: 65 psid**
- *100% Steam Flow: 169 psid**
- Goes up linearly from 20% - 100%*
- PT-558 (Common Header Feed Pump Discharge Pressure)
- PT-557 (MS Equalizing Header)
- Same as steam dumps
Note:
Steam flow is the selected steam flow channel on CP006.
- 0POP04-RC-0003 Excessive RCS Leakage*
- *
What leakage rates would result in an emergency classification?
- Unusual Event:*
- *Unidentified / Boundary: > 10 gpm**
Identified: > 25 gpm
RCS to outside containment: > 25 gpm
- 0POP04-RH-0001 Loss of RHR*
- *
What must be done if in Cold leg injection is occuring and CETs read > 200 ˚F?
Shift to HL Injection
OR
Start another LHSI pump
- LOT 202.23 OL-ACW*
- *
What does OL-ACW cool?
Main Turbine Lube Oil (2)
SGFPT Lube Oil (6)
Generator H2 (1)
CL-ACW (2)
RCB Chillers (3)
MAB Chillers (4)
- LOT 201.14 PZR Pressure & Level*
- *
At what pressure will the PORV (PCV-656A) lift when COMS is armed?
- 70 - 200 ˚F:*
- *475 psig**
- 220 - 380 ˚F:*
- *660 psig**
Uses Auct Low WR TC / PT-404
- Note:*
- Normal PORV setpoint is 2335 psig. (B/U pressure channel)*
- 0POP04-TM-0003 Turbine Trip < P-9*
- *
Below what Rx power should the operator secure a SGFPT?
35%
- 0POP04-RP-0004 Failure of RCS Loop RTD*
- *
With a single failed Hot Leg RTD, should the Tavg / ∆T channels for that loop be considered inoperable?
Yes
With a failed Hot Leg RTD the ∆T / Tavg channel should be considered inoperable because QDPS does not accurately calculate Hot Leg temperature automatically with one RTD failed.
- 0POP04-FW-0001 Loss of SG Level Control*
- *
What must be done if you are on the LPFRVs, they fail to respond in auto or manual, and the MFRVs are not responding?
- ≥ 5% Rx Power:*
- *Trip the Rx**
Perform 0POP05-EO-EO00
- < 5% Rx Power:*
- *Reduce power to 3% Rx Power**
Transition to AFW
- 0POP04-RP-0001 Loss of Automatic PZR Pressure Control*
- *
What must be done if the PZR spray valves fail to close?
- Initially:*
- *Ensure all PZR heaters energized**
Monitor PZR pressure
- Continues to lower:*
- *Ensure Rx Tripped**
Ensure Turbine Tripped
Stop RCP 1A
Stop RCP 1D
If it continues to lower stop all but 1 RCP
Perform 0POP05-EO-EO00
- LOT 201.14 PZR Pressure & Level*
- *
When is COMS required to be armed?
≤ 350 ˚F
- PCV-655A (Auct Low WR TH / PT-403)
- PCV-656A (Auct Low WR TC / PT-404)
COMS controller completely independent of master pressure controller.
- Note:*
- Manually armed on CP004*
- 0POP04-RS-0001 Control Rod Malfunction*
- *
What conditions require a Rx trip in 0POP04-RS-0001 Control Rod Malfunction?
Rods in Manual w/ continued rod motion
More than 1 rod dropped
S/D required but malfunction prevents controlled S/D
- 0POP04-CV-0004 Loss of Normal Letdown*
- *
If RCS temp is > 350 ˚F and letdown is lost, what must the operator do?
Close FV-0011
Ensure FK-0205 is in manual and closed
Ensure inservice CCP recirc valve is open
- 0POP04-RC-0004 SG Tube Leakage*
- *
What must the operator do if the intact or affected SG’s level cannot be maintained > 20% SGNR level?
Ensure Rx Tripped
Initiate SI
Perform 0POP05-EO-EO00