Test 1 Flashcards

1
Q
  • 0POP04-AE-0003 Loss of power to 13.8 kV Standby Bus*
    • *

What is a major concern if RCB chillwater is lost to the RCFCs?

A

Could cause RCB Chillwater relief to lift

Could cause low flow trip of RCB Chillers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • 0POP04-RP-0001 Loss of Automatic PZR Pressure Control*
    • *

What conditions would cause you to enter 0POP04-RP-0001 Loss of Automatic PZR Pressure Control?

A

PZR Pressure Controller fails in Auto

PZR pressure control instrument fails

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • 0POP04-TM-0003 Turbine Trip < P-9*
    • *

At what Tavg would the operator place rods in manual?

A

577 ˚F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • 0POP04-CD-0001 Loss of Condensate Flow*
    • *

What must be done if DA Level reaches 30%?

A

Trip the Rx

Go to 0POP05-EO-EO00

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • 0POP04-TM-0003 Turbine Trip < P-9*
    • *

What are the operator actions if the Throttle valves fail to close during a turbine trip?

A

Trip the Rx

Close MSIVs and MSIBs

Go To 0POP05-EO-EO00

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • 0POP04-NI-0001 Nuclear Instrumentation Malfunction*
    • *

If a power range NI fails, the operator must check that P-7, P-8, P-9, and P-10 are in their correct state within 1 hr. If they are not in their correct state, what must the operator do?

A

Enter LCO 3.0.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • 0POP04-RC-0006 Shutdown LOCA*
    • *

When is 0POP04-RC-0006 Shutdown LOCA applicable?

A

MODE 3 < 1000 psig

MODE 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • 0POP04-CW-0001 Loss of Circulating Water Flow*
    • *

If water boxes must be isolated for a loss of circulating water, then what precautions must be followed?

A

Do not isolate both water boxes in the same condenser shell

Do not isolate 11 North and 13 South b/c FW heater high level dumps enter the condenser in those water boxes

  • With a reduction in CW flow isolating a water box will raise CW discharge pressure.
  • CW discharge pressure needs to be maintained at least 3 psig to prevent pump runout.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • 0POP04-RC-0002 RCP Off Normal*
    • *

What RCP Case and Shaft Vibrations would require the operator to trip the RCP?

A

Case Vibration:
≥ 5 mils
≥ 3 mils and rising ≥ 0.2 mils/hr

  • Shaft Vibration:*
  • *≥ 20 mils**
  • *≥ 15 mils and rising ≥ 1 mils/hr**
  • Ensure Rx Tripped
  • Ensure Turbine Tripped
  • Stop affected RCPs
  • Perform 0POP05-EO-EO00
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • 0POP04-OC-0001 Loss of OL-ACW*
    • *

At what motor temperature should the operator secure the affected OL-ACW pump?

A

266 ˚F

Motor insulation starts to degrade.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • 0POP04-RC-0004 SG Tube Leakage*
    • *

What must the operator do if PZR level reaches 17% and PZR level is still lowering?

A

Ensure Rx Tripped

Initiate SI

Perform 0POP05-EO-EO00

Must also take actions if:

  • VCT Level cannot be maintained > 15% with CCP suction aligned to VCT.
  • RCS leakrate exceeds 200 gpm and PZR level is lowering
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • 0POP04-AE-0001 Loss of AC Power*
    • *

If a Class 1E battery is realigned to an operating battery charger in ≤ 15 min AND ≤ 1 battery cell is jumpered, then what must be done to declare it OPERABLE?

A

Verify Operating Battery Charger normal float voltage ≥ 128.5 VDC

Note:
A Class 1E battery is INOPERABLE anytime it is NOT aligned to an operating battery charger.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  • 0POP04-IA-0001 Loss of Instrument Air*
    • *

What would the operator do if Instrument air were lost and VCT level reaches 10%?

A

Re-align suction of CCP to RWST

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
  • 0POP04-RC-0006 Shutdown LOCA*
    • *

When must the operator manually switch to cold leg recirc?

A

RWST < 75,000 gal (14%)
AND
Containment WR Sump Level > 15”

Must also place FHB Exhaust in service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

0POP04-TM-0004 Failure of PT-505/PT-506

Do rods have to be taken to manual if PT-506 fails?

A

Yes

Step 1.0 in 0POP04-TM-0004 places rods in manual regardless of instrument (PT-505/PT-506) or failure (High/Low).

Note:
Step 8.0 has the operator check which instrument failed and then take rods back to auto at US discretion.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q
  • 0POP04-FW-0002 SGFP Trip*
    • *

Operation in what power levels is not permitted with > 1 GV out of service?

A

20 - 75% Power

Could result in rotor damage due to Double Shock Condition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q
  • 0POP04-CR-0001 Loss of Condenser Vacuum*
    • *

What must be done if main turbine vacuum is < 21” Hg?

A

Ensure Rx Tripped

Ensure Turbine Tripped

Perform 0POP05-EO-EO00

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q
  • 0POP04-TM-0005 Fast Load Reduction*
    • *

What are the boration thumbrules to perform a fast load reduction from 100% to 10% RTP at EOL? (16,000 MWD/MTU or 190 ppm boron)

A
  • 100% - 50%:*
  • *191 gal / 10% RTP reduction**
  • 50% - 10%:*
  • *31 gal / 10% RTP reduction**
  • The differential rod worth almost doubles as the ‘C’ control bank inserts; thus, compensating for power defect. Therefore, boron addition values less than 50% decrease sharply.*

Assumptions:

  • 100% RTP
  • Rods in Auto
  • Tavg/Tref ≤ 3 ˚F
  • ≥ 50 steps above RIL

Note:
≈ 5 min - 7 min delay before boration addition is observed in plant response.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q
  • 0POP04-AE-0007 Loss of all AC while on S/D Cooling*
    • *

What are the criteria to verify natural circulation?

A

SG Pressures - Stable or Lowering

RCS Hot Leg Temp - Stable or Lowering

CETs - Stable or Lowering

RCS Cold Leg Temp - Saturation Temp of SG Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q
  • 0POP04-TM-0005 Fast Load Reduction*
    • *

Below what Rx Power level are we able to trip the Rx per 0POP04-TM-0005 Fast Load Reduction?

A

< 10% Rx Power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q
  • 0POP04-AE-0007 Loss of all AC while on S/D Cooling*
    • *

What is the preferred order for re-energizing ESF busses?

A

C-A-B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q
  • 0POP04-AE-0005 Offsite Power System Degraded Voltage*
    • *

What voltage on the north AND south bus would cause you to enter 0POP04-AE-0005 Offsite power system degraded voltage?

A

339 kV

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q
  • 0POP04-RC-0002 RCP Off Normal*
    • *

What must the operator do if all seal cooling is lost to the #1 RCP seal?

A

Trip Rx

Ensure Main Turbine Tripped

Trip affected RCP within 1 minute

Perform 0POP05-EO-EO00

If RCP Seal temp < 230 ˚F:

  • Ensure PDP Recirc Valve 100% open
  • Start PDP
  • Slowly close PDP Recirc Valve to lower seal water bearing temp < 1˚F/min
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q
  • 0POP04-NI-0001 Nuclear Instrumentation Malfunction*
    • *

What are the operator immediate actions if the power range NIs are not functioning properly?

A

Place Rods in Manual

  • *Place LPFRVs in Manual**
  • If being used to feed SG*

Control SGWL between 68% - 74%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
* 0POP04-CC-0001 CCW System Leak* * * * If CCW is lost to the CCP Supplemental Cooler or to the CCP lube oil cooler, how long until CCP failure?
* _Supplemental Cooler:_* * *4 minutes** * _Lube Oil Cooler:_* * *8 minutes**
26
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What must be done if DA Level reaches 40%?
**Start Standby Condensate pump** **Open Discharge valve** * * * Done if the pump requires or does not require venting. * * * *Note: Tripping of a condensate pump and DA level lowering in an uncontrolled manner also have you start condensate pump but only if it does not require venting.*
27
* 0POP04-RC-0006 Shutdown LOCA* * * * When must the operator manually initiate makeup to the AFWST?
**\< 26% (138,000 gal)**
28
* 0POP04-RA-0001 Radiation Monitoring System Alarm Response* * * * Which radiation monitors that, if inoperable, require specific actions per 0POP04-RA-0001 Radiation Monitoring System Alarm Response?
* _8010B:_* * *8090 _OR_ 8091 Functional** * _8011:_* * *Tech Spec 3.4.6.1** * _8050/8051:_* * *HPs set up an alternate monitor in RCB** **8055 _OR_ 8099 Functional**
29
* 0POP04-CW-0001 Loss of Circulating Water Flow* * * * What operator actions are required if the plant is in MODE 1 -2 and no CW pumps are running?
**Ensure Rx Tripped** **Ensure Turbine Tripped** **Perform 0POP05-EO-EO00** * * * 0POP04-CW-0002 Circ Water Piping Breach also has the operator: * Isolate Main Steam * Place on CW pumps in PTL This is in addition to the above actions.
30
* 0POP04-TM-0001 Turbine Load Rejection* * * * If a complete loss of turbine load or two governor valves fail closed with Rx Power \> P-9, what must the operator do?
**Trip the Rx** **Perform 0POP05-EO-EO00** * * * If \< P-9: * Trip the Turbine * Go to 0POP04-TM-0003, Turbine Trip below P-9 * * * *Note: Operation with \> 1 Governor Valve out of service is _NOT_ permissible because Turbine Load would be reduced to \< 75% which is _NOT_ allowable due to possible “double shock” scenarios.*
31
* 0POP04-RA-0003 Loss of RM-11* * * * What is the power supply to RM-11?
**DP0100** ## Footnote * * * Located in EAB 35' Computer Room
32
* 0POP04-CR-0001 Loss of Condenser Vacuum* * * * What are the important values of main condenser vacuum? (i.e. alarms, actuations, ect.)
* _26" Hg:_* * *Condenser Vacuum Low Alarm (≤ 80% power)** **Standby CARS pump starts** * _24" Hg:_* * *Condenser Vacuum Low Alarm (\> 80 power)** * _22" Hg:_* * *C-9** * _21" Hg:_* * *Main Turbine Trip**
33
* 0PGP03-ZO-0041 Primary to Secondary Leakage* * * * When are the N-16 monitors available to detect primary-to-secondary leakage?
**\>25% power** * * * * Between 20% and 25% the N-16 monitors are unreliable. * \< 20% the N-16 monitors do not function.
34
* 0POP04-RC-0002 RCP Off Normal* * * * What RCP #1 Seal leakoff flow would require the operator to trip the RCP?
**\> 6 gpm** * * * * Ensure Rx Tripped * Ensure Turbine Tripped * Stop affected RCPs * Perform 0POP05-EO-EO00 * **Close affected RCP Number 1 Seal leakoff isolation valve between 3 to 5 minutes after stopping RCP.**
35
* 0POP04-FW-0002 SGFP Trip* * * * What must the operator do if Rx Power is ≥ 5% and SGNR Water Level cannot be maintained \< 87.5%?
**Trip Rx** **Perform 0POP05-EO-EO00**
36
* 0POP04-AE-0007 Loss of all AC while on S/D Cooling* * * * How many times can the SG PORVs be stroked with the energy in the accumulators alone?
**1.5 times** ## Footnote * * * Assumes SG PORVs are closed and only opening to 50%.
37
* 0POP04-CW-0001 Loss of Circulating Water Flow* * * * What CW pump motor stator temperature would require the operator to trip the affected CW pump?
**≥ 250 ˚F**
38
* LOT 202.15 SGWLC* * * * How does the SGFPTs control SGWL?
* _Pressure Mismatch:_* * *Actual D/P - Reference D/P** * * * * _Actual D/P:_* * *Feed Pressure (PT-558) - Steam Pressure (PT-557)** * _Reference D/P:_* * *0% - 20% Steam Flow: 65 psid** * *100% Steam Flow: 169 psid** * Goes up linearly from 20% - 100%* * * * * PT-558 (Common Header Feed Pump Discharge Pressure) * PT-557 (MS Equalizing Header) * Same as steam dumps * * * *Note: Steam flow is the selected steam flow channel on CP006.*
39
* 0POP04-RC-0003 Excessive RCS Leakage* * * * What leakage rates would result in an emergency classification?
* _Unusual Event:_* * *Unidentified / Boundary: \> 10 gpm** ## Footnote **Identified: \> 25 gpm** **RCS to outside containment: \> 25 gpm**
40
* 0POP04-RH-0001 Loss of RHR* * * * What must be done if in Cold leg injection is occuring and CETs read \> 200 ˚F?
**Shift to HL Injection** **_OR_** **Start another LHSI pump**
41
* LOT 202.23 OL-ACW* * * * What does OL-ACW cool?
**Main Turbine Lube Oil (2)** **SGFPT Lube Oil (6)** **Generator H2 (1)** **CL-ACW (2)** **RCB Chillers (3)** **MAB Chillers (4)**
42
* LOT 201.14 PZR Pressure & Level* * * * At what pressure will the PORV (PCV-656A) lift when COMS is armed?
* _70 - 200 ˚F:_* * *475 psig** * _220 - 380 ˚F:_* * *660 psig** * * * Uses Auct Low WR TC / PT-404 * * * * Note:* * Normal PORV setpoint is 2335 psig. (B/U pressure channel)*
43
* 0POP04-TM-0003 Turbine Trip \< P-9* * * * Below what Rx power should the operator secure a SGFPT?
**35%**
44
* 0POP04-RP-0004 Failure of RCS Loop RTD* * * * With a single failed Hot Leg RTD, should the Tavg / ∆T channels for that loop be considered inoperable?
**Yes** ## Footnote * * * With a failed Hot Leg RTD the ∆T / Tavg channel should be considered inoperable because QDPS does not accurately calculate Hot Leg temperature automatically with one RTD failed.
45
* 0POP04-FW-0001 Loss of SG Level Control* * * * What must be done if you are on the LPFRVs, they fail to respond in auto or manual, and the MFRVs are not responding?
* _≥ 5% Rx Power:_* * *Trip the Rx** **Perform 0POP05-EO-EO00** * _\< 5% Rx Power:_* * *Reduce power to 3% Rx Power** **Transition to AFW**
46
* 0POP04-RP-0001 Loss of Automatic PZR Pressure Control* * * * What must be done if the PZR spray valves fail to close?
* _Initially:_* * *Ensure all PZR heaters energized** **Monitor PZR pressure** * * * * _Continues to lower:_* * *Ensure Rx Tripped** **Ensure Turbine Tripped** **Stop RCP 1A** **Stop RCP 1D** **If it continues to lower stop all but 1 RCP** **Perform 0POP05-EO-EO00**
47
* LOT 201.14 PZR Pressure & Level* * * * When is COMS required to be armed?
**≤ 350 ˚F** * * * * PCV-655A (Auct Low WR TH / PT-403) * PCV-656A (Auct Low WR TC / PT-404) * * * COMS controller completely independent of master pressure controller. * * * * Note:* * Manually armed on CP004*
48
* 0POP04-RS-0001 Control Rod Malfunction* * * * What conditions require a Rx trip in 0POP04-RS-0001 Control Rod Malfunction?
**Rods in Manual w/ continued rod motion** **More than 1 rod dropped** **S/D required but malfunction prevents controlled S/D**
49
* 0POP04-CV-0004 Loss of Normal Letdown* * * * If RCS temp is \> 350 ˚F and letdown is lost, what must the operator do?
**Close FV-0011** **Ensure FK-0205 is in manual and closed** **Ensure inservice CCP recirc valve is open**
50
* 0POP04-RC-0004 SG Tube Leakage* * * * What must the operator do if the intact or affected SG's level cannot be maintained \> 20% SGNR level?
**Ensure Rx Tripped** **Initiate SI** **Perform 0POP05-EO-EO00**
51
* 0POP04-RS-0001 Control Rod Malfunction* * * * If there is a dropped or misaligned rod, how far must the operators lower power to recover it?
* _No Power Reduction:_* * *Fixed within 1 hr** * _Lower to 75%:_* * *Must Lower to 75% within 2 hrs** **Lowering power to 75% within 1 hr allows you 4 hrs to fix problem prior to reducing power further** * _Lower to 40%:_* * *If power was not reduced to \< 75% within 1 hr**
52
* 0POP04-IA-0001 Loss of Instrument Air* * * * If the IA leakage location can be determined by ICS, then can the US skip ahead in the procedure to isolate the leak?
**Yes, CIP allows US to skip to Step 10.0 to isolate leak**
53
* 0POP04-ZO-0003 Secondary Plant Stabilization* * * * What will cause you to enter 0POP04-ZO-0003 Secondary Plant Stabilization?
**Rx Trip / SI** **MT Turning Gear will not engage (Manual / Auto)** **Failure of MT Turning Gear while rotating Turbine w/ vacuum** **Failure of Bearing Lift System while on Turning Gear under vacuum**
54
* 0POP04-FW-0001 Loss of SG Level Control* * * * How long can a SGFPT be operated at 5500 - 5600 RPM?
**1 hr maximum** * * * Individual SGFP flow shall be greater than 11,000 gpm * D/P across impeller will not be above design.
55
* 0POP04-TM-0005 Fast Load Reduction* * * * What are the boration thumbrules to perform a fast load reduction from 100% to 10% RTP at BOL? (1,000 MWD/MTU or 1,378 ppm boron)
* _100% - 50%:_* * *117 gal / 10% RTP reduction** * _50% - 10%:_* * *2 gal / 10% RTP reduction​** * The differential rod worth almost doubles as the ‘C’ control bank inserts; thus, compensating for power defect. Therefore, boron addition values less than 50% decrease sharply.* * * * Assumptions: * 100% RTP * Rods in Auto * Tavg/Tref ≤ 3 ˚F * ≥ 50 steps above RIL * * * *Note: ≈ 5 min - 7 min delay before boration addition is observed in plant response.*
56
* 0POP04-TM-0003 Turbine Trip \< P-9* * * * If Tavg drops below 567 ˚F during a turbine trip \< P-9, what should the operators do to restore Tavg?
**Secure Steam loads**
57
* 0POP04-RC-0006 Shutdown LOCA* * * * What will cause you to enter adverse containment conditions?
**Containment Pressure ≥ 5 psig** **Containment Radiation ≥ 105 R/hr** **Containment Integrated Radiation ≥ 106 Rads**
58
* 0POP04-CW-0001 Loss of Circulating Water Flow* * * * What CW pump motor motor bearing temperature would require the operator to trip the affected CW pump?
**≥ 200 ˚F**
59
* LOT 202.26 Service / Instrument Air* * * * What happens as IA pressure lowers?
* _122 psig / 119 psig / 116 psig / 113 psig:_* * *Compressors 11 - 13 / 14 Start** * Lead / Standby / Lag / Air Cooled* * _100 psig:_* * *Service Air Isolation Closes** * Reset on ZLP-134 (TGB 29' by compressors 11/12/13)* * _90 psig:_* * *IA to yard Closes** * _88 psig:_* * *Low Power FRVs drift closed** * _80 psig:_* * *IA Dryer Bypass Opens** * Reset by valve* * *Letdown Header Orifice header isolation valves drift Closed** * _67 psig:_* * *MFRVs drift Closed** *_60 psig:_* **Manually Trip the Rx MSIVs drift Closed** * * * Service / IA Air pressure indicated on CP008.
60
* 0POP04-TM-0002 Turbine Monitoring Alarms* * * * What are the turbine trip criteria as laid out in 0POP04-TM-0002 Turbine Monitoring Alarms?
**Rotor Position not between _+40 mils and -40 mils [2/2]_** * *Bearings 1-8 vibration \> _14 mils_** * Load reduction not effective in lowering vibration* * *Bearings 9-10 vibration \> _10 mils_** * Load reduction not effective in lowering vibration* * *Turbine ∆Expansion \> Danger Alarm** * _Must be substantiated by other indications_* **Bearing Metal Temp \> _225 ˚F_**
61
* 0POP04-AE-0007 Loss of all AC while on S/D Cooling* * * * How do operators inform people inside containment to evacuate if power is lost?
**Megaphone** ## Footnote * * * Located in flex locker at EAB 86'
62
* LOT 201.15 RCS Temperature Monitoring* * * * What parameters feed into OT∆T?
**Tavg** **∆T** **Thermal Power** **RCS Flow** **PZR Pressure** * *∆I** * Only used when ∆I exceeds +8%* * * * ∆I and PZR Pressure _NOT_ used for OP∆T.
63
* 0POP04-RP-0002 Loss of Automatic PZR Level Control* * * * What are the immediate actions of 0POP04-RP-0002 Loss of Automatic PZR Level Control?
**Place FK-0205 in Manual** **Adjust FK-0205 to maintain PZR level**
64
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What hotwell level will require you to trip the Rx and perform 0POP05-EO-EO00?
* *0.25 ft** * LI-7007 on CP009*
65
* 0POP04-AE-0001 Loss of AC Power* * * * If power is lost to ESF Train A or Train C and their associated batteries have ≥ 1 cells jumpered, what must the operators do?
**Shed Loads on DP-1201 (Train A) or DP-1204 (Train C) within 30 mins**
66
* 0POP04-TM-0005 Fast Load Reduction* * * * What are the boration thumbrules to perform a fast load reduction from 100% to 10% RTP at MOL? (9,000 MWD/MTU or 873 ppm boron)
* _100% - 50%:_* * *154 gal / 10% RTP reduction** * _50% - 10%:_* * *6 gal / 10% RTP reduction** * The differential rod worth almost doubles as the ‘C’ control bank inserts; thus, compensating for power defect. Therefore, boron addition values less than 50% decrease sharply.* * * * Assumptions: * 100% RTP * Rods in Auto * Tavg/Tref ≤ 3 ˚F * ≥ 50 steps above RIL * * * *Note: ≈ 5 min - 7 min delay before boration addition is observed in plant response.*
67
* 0POP04-AE-0001 Loss of AC Power* * * * What 13.8kV / 4.16 kV busses does 0POP04-AE-0001 _NOT_ cover?
**1K** **1L** **1M**
68
* LOT 201.15 RCS Temperature Monitoring* * * * What are the RCS NR temperature instruments used for?
* _Tavg:_* * *OT∆T** * *OP∆T** * *FW Isolation** * P-4 w/ Tavg - Low (574 ˚F)* * *P-12** * \< 563 ˚F [2/4] Blocks steam dumps* * _Auctioneered High Tavg:_* * *Rod Control** * Indication on CP005 is Auctioneered Low Tavg* * *Steam Dumps** * *PZR Level Control** * _Auctioneered Low Tavg:_* * *C-17** * _Auctioneered High ∆T:_* * *Rod Insertion Limit** * * * 3 in HL (120˚ apart for laminar flow concerns) and 1 in CL per loop. Also has 3 fast response RTDs in CL per loop. * * * * Note:* * 3 HL RTDs are averaged together to give signal. If 1 fails the system will automatically kick it out.*
69
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What must be done if you were to lose all condensate pumps and a condensate pump cannot be restarted?
**Trip Rx** **Ensure Turbine Trip** **Ensure MSIVs and MSIBs closed** **Ensure SUFP in PTL** **Trip SGFPTs** **Trip all FWBPs** **Perform 0POP05-EO-EO00**
70
* 0POP04-AE-0001 Loss of AC Power* * * * What must the operator do if power is lost to a RCP while in MODES 1-2?
**Trip the Rx** **Perform 0POP05-EO-EO00**
71
* 0POP04-FW-0002 SGFP Trip* * * * What are the operator immediate actions for 0POP04-FW-0002 SG Feed Pump Trip?
**Check Required number of SGFPs running** *_RNO:_* * Ensure SU SGFP running* * Start Standby booster pump* * If SU SGFP trips or SGFPT trips w/ SU SGFP running, then if idle (3300 RPM) SGFPT available, ramp up speed* * *Check SGFP Master Speed Controller** * Operable in Auto, PT-557, PT-558, controlling steam flow* *_RNO:_* * Place SGFP Master Speed Controller in Manual and adjust* * If not operable in auto/manual then control with individual controllers*
72
* 0POP04-TM-0003 Turbine Trip \< P-9* * * * When using the steam dumps in steam pressure mode, what is the temperature band that should be maintained?
**572 ˚F - 577 ˚F**
73
* 0POP04-RC-0006 Shutdown LOCA* * * * What must the operator verify if the RHR Temperature control HCVs and RHR HX Bypass valves position indicating lights are not lit?
**Valve Disconnects and Knife Switches are closed**
74
* 0POP04-AE-0004 Loss of power to ≥ 1 4.16 kV ESF Busses* * * * A loss of how many ESF busses would require entry into the emergency plan?
**\< 2 loaded standby DGs** **_AND_** **No other OPERABLE AC sources**
75
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What should be done if you get a SGFPT seal water D/P low alarm in?
* *Take manual control of DA level control valves and throttle closed until all SGFPT low D/P alarms clear.** * (≈ 400 psig - 450 psig)*
76
* 0POP04-AE-0001 Loss of AC Power* * * * If power is lost to all ESF busses, then an operator must be sent to shed the Channel I sequencer. How long does the operator have to perform this action?
**30 mins**
77
* 0PGP03-ZO-0041 Primary to Secondary Leakage* * * * What puts you in action level 1 for primary to secondary leakage?
* _Total Leak Rate (All 4 S/Gs):_* * *≥ 30 gpd** ## Footnote * * * Monitor CARS / BD every 10 mins and N-16 every 15 mins
78
* 0POP04-RA-0003 Loss of RM-11* * * * What two process monitors will the control room not have indication of once RM-11 is lost?
**RT-8041 (TG Sump)** **RT-8042 (CP Discharge)**
79
* 0POP04-RC-0006 Shutdown LOCA* * * * What conditions would require the operator to secure all RCPs per 0POP04-RC-0006 S/D LOCA?
**RCS Subcooling \< 35 ˚F** **PZR Level \< 8%** **#1 Seal D/P \< 220 PSID** **#1 Seal Leakoff - Low**
80
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What must be performed if power changes by ≥ 15% in any 1 hr period?
**Notify chemistry to perform an isotopic analysis of RCS iodine**
81
* LOT 201.30 Offsite Electrical* * * * Procedurally, what is the current rating of the standby transformer windings?
**1621 Amps / Winding** ## Footnote * * * Equivalent to 2 Aux Busses and all 6 ESF busses fully loaded.
82
* 0POP04-AE-0007 Loss of all AC while on S/D Cooling* * * * What CET temperature will have you transition to the SAMGs?
**1200 ˚F** ## Footnote * * * TSC and Emergency Director will be notified at 708 ˚F.
83
* 0POP04-RP-0005 COMS Actuation or Failure* * * * What must the operator do if the PZR is solid and letdown is lost?
**Stop all CCPs** **Stop all RCPs** **Close Seal Injection HCV-0218** **Take Charging FK-0205 to manual and close** **Close Charging Line OCIV (MOV-0025)**
84
* LOT 202.15 SGWLC* * * * How does the MFRVs control SGWL?
* _SG Water Level Mismatch:_* * *2.5 (Actual Level - Program Level)** * _Flow Mismatch:_* * *0.6 (Steam Flow - Feed Flow)** * * * MFRVs are level dominant.
85
* 0POP04-FW-0001 Loss of SG Level Control* * * * What must be done if SGNR level cannot be maintained \< 87.5% SGNR?
* _≥ 5% Rx Power:_* * *Trip Rx** **Go to 0POP05-EO-EO00** * _\< 5% Rx Power:_* * *Reduce power to \< 3% Rx Power** **Ensure MFRV isolated** **Transition to LPFRVs, Preheater bypass Valves, or AFW** * * * * Note:* * We put a guardrail of 85% and 22% on SGWL.*
86
* 0POP04-NI-0001 Nuclear Instrumentation Malfunction* * * * What are your actions if the plant is in MODES 3-5 and both extended range NIs are lost?
**Suspend positive reactivity changes [Immediately]** **Isolate unborated water paths from RMW system to RCS [15 mins]** **Restore 1 channel to OPERABLE [1 hr]** **OR** **Secure unborated water sources [2 hrs] AND Verify SDM [4 hrs and 12 hrs after]**
87
* 0POP04-RA-0003 Loss of RM-11* * * * What radiation detectors are used to detect RCS leakage if RM-11 is lost?
**RT-8010B (FHB / MAB)** **RT-8011 (RCB)**
88
* 0PGP03-ZO-0041 Primary to Secondary Leakage* * * * What puts you in action level 2 for primary to secondary leakage?
* _Leakage from 1 S/G:_* * *75 gpd - 150 gpd** * * * Monitor CARS / BD every 10 min and N-16 every 15 mins. If \> 75 gpm for ≥ 1 hr: * Go to POP04-RC-0004 (SG Tube Leakage) * Be in MODE 3 [24 hrs] * Time starts when ≥ 75 gpd first indicated
89
* 0POP04-AE-0004 Loss of power to ≥ 1 4.16 kV ESF Busses* * * * What is the load restriction on each winding of the emergency transformer?
**2762 KW / winding** * * * * Used in the event of LOOP w/ LOCA. * Aids in keeping ESF bus \> 4.0 kV * * * *Note: If only 1 ESF bus is available and it will be loaded on emergency transformer, then load limit is N/A but must maintain \> 4.0 kV on ESF bus.*
90
* 0POP04-RH-0001 Loss of RHR* * * * What are the different ways an operator can restore RCS inventory to +8 - +11 during a loss of RHR?
**Gravity Drain RWST through idle LHSI pump in idle RHR train** **CCP through normal charging or seals** **LHSI pump**
91
* 0POP04-CV-0004 Loss of Normal Letdown* * * * Is 0POP04-CV-0004 loss of normal letdown entered after a SI?
**No** ## Footnote * * * Only entered if loss of letdown is unexpected.
92
* 0POP04-RC-0003 Excessive RCS Leakage* * * * What must the operators do if VCT level cannot be maintained \> 15% w/ charging pump suction aligned to the VCT?
* _MODES 1-3 w/ RCS pressure \> 1000 psig:_* * *Ensure Rx Tripped** **Initiate Safety Injection** **Go To 0POP05-EO-EO00** * _Other MODES:_* * *Go to 0POP04-RC-0006 Shutdown LOCA** * * * Same actions for: * RCS leakage exceeds 200 gpm and PZR level lowering * PZR level cannot be maintained \> 17% * Containment pressure cannot be maintained \< 3 psig with supplemental purge or cooling
93
* 0POP04-AE-0001 Loss of AC Power* * * * How long does the operator have to restore RCFC cooling (CCW) following a loss of all AC?
**30 mins**
94
* 0POP04-TM-0003 Turbine Trip \< P-9* * * * What are the operator actions if the steam dumps are unavailable during a turbine trip \< P-9?
**Trip the Rx** **Perform 0POP05-EO-EO00**
95
* 0POP04-RP-0001 Loss of Automatic PZR Pressure Control* * * * What is your immediate action if any PZR pressure channel fails high?
**Position the PZR pressure control selector switch to remove failed channel from control**
96
* 0POP04-OC-0001 Loss of OL-ACW* * * * What must the operator do if only 1 condensate pump is running and CL-ACW pump discharge temperature is \> 118 ˚F (Alarms)?
**Place all LPHDs in PTL** **Secure all running condensate pumps**
97
* 0PGP03-ZO-0041 Primary to Secondary Leakage* * * * What puts you in action level 3 for primary to secondary leakage?
***_Leakage from 1 S/G:_*** * _Condition 1:_* * *≥ 75 gpd and ↑ 30 gpd/hr** * Not required be entered for spikes* * _Condition 2:_* * *≥ 75 gpd w/ loss of radiation monitors** * May terminate S/D if Rad monitors restored _and_ \< 75 gpd* * _Condition 3:_* * *\> 150 gpd** * Must be entered for spikes* * * * * Go to POP04-RC-0004 (SG Tube Leakage) * _Condition 1 OR 2:_ ↓50% [1 hr] and Be in MODE 3 [Following 2 hrs] * _Condition 3:_ Be in MODE 3 [6 hrs]
98
* 0POP04-FW-0002 SGFP Trip* * * * When is 0POP04-FW-0002 SGFP Trip APPLICABLE?
**MODES 1-2**
99
* 0POP04-FW-0002 SGFP Trip* * * * What must the operator do if \> 85% Rx Power and \< 2 FWBPs are available?
**Trip Rx** **Perform 0POP05-EO-EO00**
100
* 0POP04-CC-0001 CCW System Leak* * * * What must the operator do if CCW surge tank compartment level is \< 56%?
**Ensure RHR pump for unaffected CCW train in service** **Ensure associated RHR train secured** **Ensure associated CCW pump in PTL**
101
* 0POP04-RP-0004 Failure of RCS Loop RTD* * * * Does the operator have to take rod control to manual if RTD fails low?
**Yes** ## Footnote * * * It doesn't matter the failure, rods must be taken to manual. This is _NOT_ an Immediate Action however.
102
* 0POP04-AE-0001 Loss of AC Power* * * * What must be done if operation of a SG PORV is required and it's associated ESF bus is deenergized?
**Take Manual Control of SG PORV** **Hold Down arrow for ≥ 20 Sec** **Place station blackout bypass switch in bypass**
103
* 0POP04-OC-0001 Loss of OL-ACW* * * * What must the operator do if no OL-ACW pumps are running and cannot be restarted?
**Trip Rx** **Trip Main Turbine** **Perform 0POP05-EO-EO00**
104
* 0POP04-RC-0006 Shutdown LOCA* * * * When must the operator ensure at least 1 HHSI pump and 1 LHSI pump are running per 0POP04-RC-0006 S/D LOCA?
**RCS subcooling \< 35 ˚F** **PZR Level \< 8%** **Containment Pressure \> 3 psig**
105
* 0POP04-RC-0002 RCP Off Normal* * * * What RCP Motor Upper / Lower Radial Bearing temperature would require the operator to trip the RCP?
**≥ 195 ˚F** * * * * Ensure Rx Tripped * Ensure Turbine Tripped * Stop affected RCPs * Perform 0POP05-EO-EO00
106
* 0PGP03-ZO-0041 Primary to Secondary Leakage* * * * What puts you in increased monitoring for primary to secondary leakage?
* _Total Leak Rate (All 4 S/Gs):_* * *≥ 5 gpd and \< 30 gpd** ## Footnote * * * Monitor CARS / BD / N-16 every 12 hrs * * * *Note: ≤ 10% rise in 24 hrs, return to normal monitoring.*
107
* 0POP04-CD-0001 Loss of Condensate Flow* * * * What must be done if a condensate pump trips and another condensate pump cannot be started?
**Commence turbine load reduction to ≤ 50% at ≤ 5% / min**
108
* 0POP04-CW-0001 Loss of Circulating Water Flow* * * * At what condensate polisher inlet temperature should the condensate polishers be bypassed?
**140 ˚F**
109
* 0POP04-NI-0001 Nuclear Instrumentation Malfunction* * * * What are your actions if a SR detector fails?
* _Failed High:_* * *Ensure Rx Tripped** **Go To 0POP05-EO-EO00** * _Failed Low:_* * *Suspend positive reactivity changes**
110
* LOT 201.14 PZR Pressure & Level* * * * At what pressure will the PORV (PCV-655A) lift when COMS is armed?
* _70 - 200 ˚F:_* * *515 psig** * _220 - 380 ˚F:_* * *730 psig** * * * Uses Auct Low WR TH / PT-403 * * * * Note:* * Normal PORV setpoint is ≈ 2335 psig. (Master pressure controller 87.5%)*
111
* 0POP04-FW-0002 SGFP Trip* * * * What must the operator do if Rx Power is \< 5 % and SGNR level cannot be maintained \< 87.5 %?
**Ensure MFW to affected SG isolated** **Reduce power to \< 3%** **Place AFW inservice**
112
* 0POP04-CW-0001 Loss of Circulating Water Flow* * * * What condenser D/T is indicative of a loss of circulating water?
**D/T ≥ 25 ˚F**
113
* 0POP04-RC-0002 RCP Off Normal* * * * What RCP Lower Seal Water Bearing or Seal #1 Inlet temperature would require the operator to trip the RCP?
**≥ 230 ˚F** * * * * Ensure Rx Tripped * Ensure Turbine Tripped * Stop affected RCPs * Perform 0POP05-EO-EO00
114
* 0POP04-RP-0001 Loss of Automatic PZR Pressure Control* * * * What is your immediate action if any PZR pressure channel fails low?
**Place PZR Pressure Controller in manual** **Position the PZR pressure control selector switch to remove failed channel from control**
115
* 0POP04-RC-0002 RCP Off Normal* * * * What RCP Motor Stator Winding temperature would require the operator to trip the RCP?
**≥ 310 ˚F** * * * * Ensure Rx Tripped * Ensure Turbine Tripped * Stop affected RCPs * Perform 0POP05-EO-EO00
116
* 0POP04-TM-0005 Fast Load Reduction* * * * How long can the main turbine exhaust pressure be operated in the restrictive zone of the exhaust pressure limitation curve?
**5 mins** ## Footnote * * * Must be returned to a value outside the restrictive zone or _Rx and turbine must be tripped._
117
* 0POP04-AE-0007 Loss of all AC while on S/D Cooling* * * * What are the time sensitive actions to ensure the Class 1E batteries last 8 hrs?
**De-energize ESF Sequencers (30 mins)** **Initiate FSG04 (Deep Load Shed) (30 mins)** **Complete FSG04 (2 hrs)**
118
* 0POP04-CC-0001 CCW System Leak* * * * What must the operator do once CCW surge tank level lowers to 61.5% and a common header isolation has occurred?
**Ensure Rx Tripped** **Ensure RCPs Tripped** **Go to 0POP05-EO-EO00**
119
* 0POP04-TM-0001 Turbine Load Rejection* * * * If during a down power, Governor valve 2 fails closed, then what must the operator do prior to Governor valve 4 going closed?
**Trip the Rx** **Perform 0POP05-EO-EO00**
120
* 0POP04-RC-0006 Shutdown LOCA* * * * How long does the operator have to restore Spent Fuel Cooling once lost?
**2.5 hrs**
121
* 0POP04-FW-0001 Loss of SG Level Control* * * * What are your immediate actions per 0POP04-FW-0001 Loss of SG Level Control?
* *Check FRVs / LPFRVs responding in Auto** * If not take to manual and adjust SG WL to 68% - 74%* * *Check SGFP speed controllers responding in Auto** * Place Master / Individual SGFP speed controllers in manual and adjust SG WL to 68% - 74%*
122
* 0POP04-AE-0007 Loss of all AC while on S/D Cooling* * * * What must SG pressure be in order to use the TDAFW pump?
**\> 150 psig**
123
* LOT 202.15 SGWLC* * * * How does the LPRVs control SGWL?
* _SG Water Level Mismatch:_* * *Actual Level - Program Level** * _PR NI Compensation:_* * *Auctioneered High NI** * * * Low Power Feed Reg Valves are level dominant.
124
* 0POP04-RP-0002 Loss of Automatic PZR Level Control* * * * What must the operator do if PZR level is \> 70% and FCV-0205 is not controlling?
**Close Charging OCIV MOV-0025 _OR_ Close Charging Loop A / C Isolations** *(MOV-0003/MOV-0006)*
125
* 0POP04-ZO-0003 Secondary Plant Stabilization* * * * If systems necessary to support condenser vacuum are unavailable, then what must the operators do?
* *Close MSIVs and MSIBs** * Use safety related handswitches followed by non-safety on CP006* ## Footnote **Take all non-running CARS pump local switches to OFF** **Open Vacuum Breakers** **Secure all CARS pumps** **Ensure Hood Spray in MOD position** **Stop S/U SGFP** **Secure gland seal** **Secure Aux Steam** **If in MODE 5, open CP Bypass (MOV-0132)**
126
* LOT 202.23 OL-ACW* * * * What are the starting permissives and auto starts for the OL-ACW pumps?
* _Auto Start:_* * *System Pressure - Low (68 psig)** * Downstream of the strainer* * *Trip of Running Pump** * _Starting Permissives:_* * *Seal Water Pressure ≥ 18 psig [Unit 1 ONLY]** * Will not trip pump* * * * *Note: Pressure indicator on CP009 is pressure downstream of strainer _NOT_ pump discharge pressure.*