Temperature Indication Flashcards
State control functions used from WR Temperature Instruments
WR Th: A train LTOP: A Hot 405
WR Tc: B Train LTOP: B Cold 403
State how to calculate Delta-T
NR Th gets averaged (3 instruments per loop)
and subtracted from NR Tc
State how to calculate AveTave
NR Th gets averaged (3 instruments per loops)
Thave gets averaged with NR Tc for Tave
Each loops Tave gets averaged together for AveTave
State Protective and control functions Tave feeds into
OT-Delta T
OP-Delta T
Low Tave (557) with P-4 gives FWI
Low-Low tave (550) gives P-12 (2/4) - SD block
Auc Low Tave (553) C-16
AveTave feeds (Rod Control, Steam Dumps, PZR Level)
State the Protective and control functions Delta T feeds into
RIL- Auc High Delta-T
OT-Delta-T
OP-Delta-T
Discuss how OP-Delta-T changes as Tave Changes
If Tave increases then the OP-Delta-T setpoint Decreases
No change if Tave decreases
Discuss how OT-Delta-T Changes as Tave Changes
If Tave increases, then OT-Delta-T setpoint Decreases
If Tave Decreases, then OT-Delta-T setpoint Increases