RPI Flashcards
State the T.S. allowable Rod Deviation
12 steps, T.S. 3.1.3.1
State the accuracy of DRPI
+/- 4 steps. This accuracy changes when either A or B data cabinet component fails
State what gives a Rod Deviation alarm
Any shutdown rod ≤ 210 steps or
Any two rods in the same control bank ≥ 12 steps apart
Signals the system rod deviation alarm (1,R,2) and D7753
State T.S. 3.1.3.1 (Group Height) LCO and Action
All full-length shutdown and control rods shall be OPERABLE and positioned within +/-12 steps of their group step counter demand position
MODE:1 and 2
A: With one or more full-length rods inoperable because of being immovable as a result of excessive friction or mechanical interference or known to be untriplable, determine that the SHUTDOWN MARGIN is within the limits specified in the COLR within 1 hour and be in HOT STANDBY within 6 hours
State what gives Central Control Failure
Lit to indicate CCC disagrees with both of the other two CCCs and been automatically disconnected from the system
State what gives Urgent Alarm
Flashing to indicate at least one rod position is unknown. Affected rod(s) indicated by GW and Rod Bottom position
State what gives Data A/B failure
Flashing to indicate that the “A/B” position information is invalid for at least one rod. Affected Rod(s) indicated by GW.
State what gives general warning alarm
Flashing to indicate affected rod with DATA A/B FAILURE, or URGENT ALARM