TB #54 HAZARDOUS/ILLEGAL MEZZANINES Flashcards
A FULLY SPRINKLERED BUILDING MUST HAVE SPRINKLERS INSTALLED ABOVE AND BENEATH ANY MEZZANINE
TRUE/FALS
TRUE
WHEN THE TOTAL AREA OF ANY MEZZANINE FLOOR EXCEEDS _____% OF THE TOTAL FLOOR AREA IN THAT ROOM, IT SHALL BE CONSIDERED AS CONSTITUTING AN ADDITIONAL “STORY” IN THE BUILDING.
33 1/3%
THE CLEAR HEIGHT ABOVE OR BELOW A MEZZANINE FLOOR CONSTRUCTION SHALL BE NOT LESS THAN __ FEET.
7FT
THERE SHALL BE NOT MORE THAN __ LEVELS OF MEZZANINES IN A ROOM.
2
THE AGGREGATE AREA OF MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ___ OF THE AREA OF THE ROOM IN WHICH THEY ARE LOCATED.
1/3
THE SIDE OF THE MEZZANINE WHICH IS OPEN TO THE ROOM SHALL BE UNOBSTRUCTED EXCEPT FOR COLUMNS, POSTS AND PROTECTIVE WALLS, OR RAILINGS NOT MORE THAN ___” IN HEIGHT
42”
PARTITIONING MAY BE INSTALLED, PROVIDED THE AGGREGATE FLOOR AREA OF THE ENCLOSED SPACE DOES NOT EXCEED __% OF THE AREA OF THE MEZZANINE OR HAVE AN OCCUPANT LOAD EXCEEDING __, WHICHEVER IS GREATER
10%, 10
2 EXITS SHALL BE PROVIDED FROM MEZZANINES HAVING AN OCCUPANT LOAD OF MORE THAN 10 OR WHEN THE AREA OF THE MEZZANINE EXCEEDS _____ SQUARE FT, WHICHEVER IS THE MORE RESTRICTIVE.
2,000 SQUARE FT