TB 174 HOSE TESTING PROCEDURES Flashcards
1 inch single jacket (brush) tested @?
300psi
1 1/2 inch single jacket(brush) tested @?
300psi
1 inch double jacket tested at?
400psi
1 1/2 inch double jacket tested at?
400psi
1 3/4 inch hose tested at?
400psi
2 1/2 inch double jacket hose tested at?
400psi
2 1/2 inch & 4 inch bypass/ suctions tested at?
300psi
2 inch single jacket nitrile rubber(high rise) hose tested at?
300psi
2 1/2 inch single jacket nitrile rubber (high rise pigtail) tested at?
300psi
3 inch single jacket nitrile rubber (ladder pipe) hose tested at?
300psi
4 inch single jacket nitrile rubber (supply hose) hose tested at?
250psi
1 inch booster hose reel (OES type 3) hose tested at?
300psi
Who shall ensure all hose is tested in station by fire pump apparatus?
Station commander
When are hard suction and 2 1/2 inch high pressure high rise hose tested?
Annually at annual pump test by test pit engineer
When shall new hose be tested after receiving?
Within 24 hours of receiving
Hose that has been stored for longer than 1 year shall be what before put back into service?
Shall be tested before put back into service
When hose is damp or dirty how long after shall it be changed?
Within 24 hours
Fabric jacketed supply lines including by-pass and suctions shall be changed when?
Weekly or more frequently when damp or dirty
Hose shall be loaded into apparatus in such way that ______ can circulate under the hose to eliminate or reduce growth of mildew in the hose jacket or rust and or corrosion in hose bed?
Air
Hose shall be kept out of ___ when stored?
Direct sunlight
Hose shall be reloaded with sufficient regularity to prevent?
Prevent damage and the setting of permanent folds in rubber lining
Who identifies if hose is in need of replacement due to excessive wear or the ten year service life has been reached?
Station commander
Dirty hose shall be washed with?
Clear cold water. 5-10% solution concentrated soap
Nozzles shall be opened how much to prevent water hammer and damage to the pump when testing hose?
Cracked
How do you identify damaged hose?
With black tape around damaged area and F-175 tag
What’s the max feet a hose line can be tested?
300 feet
When testing hose connect to on or offside of the panel and what is the clearance?
Off side panel (no gate wye)and 15 feet clearance from nozzle and hose
How do you increase pressure during hose test?
Gradually raised to 45psi and gradually increase by 15psi per second
When testing hose consider testing in volume or pressure?
Volume
What documentation is to be filled out after hose test?
F station commander fills out F-2 and F-129 if forward to hose test record