TB 174 Hose Testing Flashcards
_________ shall ensure that all rubber lined, single-jacketed hose, double-jacketed hose, by-pass hose, soft suction hose and synthetic nitrile “all rubber” hose (2” high-rise, pigtails and3”Ladder Pipe) be tested annually using fire apparatus pumps.
Station Commanders
All hard suction hose and 2-1/2” high pressure high-rise hose shall be tested?
annually during Annual Pump Test by the Test Pit Engineer.
Firefighting hand lines (1”, 1-1/2”, 1-3/4”, 2-1/2”) shall be changed _______ when damp or dirty.
within 24 hours
Station Commanders who identify hose that is in need of replacement due to excessive wear or the ten year service life has been reached, shall contact the ________
Equipment Engineering Unit at the Supply and Maintenance(S&M) Division for assistance.
Single-jacketed synthetic nitrile rubber lined hose: 4” supply shall be tested at _____.
250 PSI.
Double-jacketed rubber lined hose: 1”, 1-1/2”, 1-3/4”and2-1/2” shall be tested at ____.
400 PSI
Single-jacketed thermal plastic lined: (brush hose) shall be tested at _____ PSI on ______ or _______ surfaces.
300
grass or light fuel bed surfaces.
The pressure shall be raised at a rate not greater than __ psi per second until the service test pressure is reached. Maintain the appropriate test pressure for __ minutes.
15 psi
5
Members shall never stand directly within __‘in front of the free end of the hose, closer than __’ on either side of the hose, or ______ a hose in the test area.
15’
15’
Straddle
At the conclusion of the test, the Station Commander shall make a journal entry in the ___ and complete and forward the _____ Annual Hose Test Record.
F-2
F-129