T.B. 140 - Elevator Operations at Highrise Incidents Flashcards

1
Q

When the Elevator Emergency Service Switch is switched to “ON” what phase is it in?

A

Phase 1: Recall Phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

To place the elevator in operation on a temporary basis when the entire building is deemed safe for normal use but there is still enough residual smoke to acute the detectors or detectors are malfunctioning, place the switch in the “_______” position.

A

“Bypass”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The 2008 Elevator Code requires a THREE position switch in the lobby. What are the Three positions?

A
  1. ON
  2. OFF
  3. RESET
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

2008 Elevator Code:

To remove the elevators from Phase 1 Emergency Recall Operation the switch SHALL be rotated FIRST to the “_______” position, and then to the “OFF” position.

A

“RESET”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

2008 Elevators Code:

Is there a BYPASS switch or a means to bypass the alarms on this system?

A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Phase II is known as the “________” Phase.

A

“Override”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

An Emergency Service Switch is provided in each elevator car with Phase ___ capability.

A

Phase II

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the THREE positions of the IN CAR key switch?

A
  1. ON
  2. OFF
  3. HOLD
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Turning both switches (Phase I and Phase II) to the “ON” position operates the “_______” Phase.

A

“Override”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When operating elevators in the “Emergency Service,” what TWO features are rendered inoperable?

A
  1. Automatic door open

2. Photo-electric devices

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What type of pressure do you need to OPEN and CLOSE doors in the Override Phase?

A

Continuous pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Override Phase:

When multiple floor buttons have been selected, what floor will the elevator stop at?

A

the CLOSEST floor selected.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What key position is used to maintain the elevator car on the floor where the elevator is currently located and maintain the doors in the OPEN position?

A

“HOLD”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Override Phase:

The key inside the car should be removed when the switch is placed in what position?

A

“HOLD”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

It is imperative that the Elevator Operator should remain in the elevator car and either maintain constant pressure on the “_________” button or activate the “_____” feature or the elevator doors may close.

A

“DOOR OPEN”

“HOLD”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When the Interior elevator key is in the “OFF” position the Emergency Service Mode returns to PHASE __, which will return all the elevators to the LOBBY.

A

Phase I

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Elevator ascent during INVESTIGATIONS or FIREFIGHTING operations shall only be used when the reported location is above the _____ floor.

A

6th floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Firefighters who climb stairs will arrive ______ than those who utilize elevators for locations BELOW the 6th floor.

A

Faster

19
Q

Before using an elevator, the Company Officer should attempt to accurately determine the _________ of the fire or alarm.

A

location

20
Q

Elevators SHALL NOT be taken closer than ____ floors below the reported Fire Floor or lowest indicated Alarm Floor location.

A

TWO floors

21
Q

Under NO circumstances should an elevator not equipped with Emergency Service or a _______ elevator be used. These elevators can only be used if it is determined SAFE by personnel on the desired floor of operation and their use is approved by the ____.

A

Freight

IC

22
Q

Elevators SHALL NOT be taken TO or ABOVE the reported ______ floor.

A

Fire floor

23
Q

If the building is equipped with Split Bank Elevators: DO NOT use the elevator that services the Fire Floor if a Lower Bank of elevators reaches within ____ floors of the Fire Floor.

A

5 floors

24
Q

Elevators that travel through a ______ ______ should be avoided whenever possible.

A

Blind Shaft

25
Q

High Rise Retrofit Ordinance (1989):

All lobby openings for elevator doors shall be protected with a _____ minute automatic closing fire assemblies with magnetic hold open devices for door closure activated by any initiating device located on the floor.

A

45 min.

26
Q

High Rise Retrofit Ordinance (1989):

All elevators open into elevator lobbies which are separated from the remainder of the building, including corridors and other exits, by walls having Fire-Resistive rating of not less than ____ hour.

A

1 hour

27
Q

Before utilizing an Elevator, the SHAFT shall be checked for the presence of what THREE things by using a Flashlight or Thermal Imaging Camera?

A

Smoke
Fire
Water

28
Q

No more than how many personnel with equipment are permitted in an elevator at one time?

A

6 personnel

29
Q

Once assigned as the ELEVATOR OPERATOR, this member shall report to the ______ ________ Officer?

A

Lobby Control

30
Q

Prior to going aloft in an elevator, ALL members SHALL don their _______ and shall be prepared to ____________________.

A

Facepiece

connect their 2nd stage regulator.

31
Q

What piece of equipment SHALL remain in the elevator car with the Elevator Operator?

A

Dry Chem Extinguisher

32
Q

During Phase I operation, if any elevator does NOT recall to the lobby, elevators SHALL NOT be used until ALL elevators are _________ for.

A

accounted

33
Q

Who shall notify the IC of the elevator status?

  1. ________ or
  2. ________
A
  1. Initial Fire Investigation Team or

2. Lobby Control Unit

34
Q

UNACCOUNTED Elevators will require the IC to implement an ______ _______ to determine the location and status of any elevator not returning to its RECALL location and the potential for extrication and rescue.

A

Elevator Group

35
Q

Phase II operation is indicated on the Interior Control Panel as “___” or “_______ ______”.

A

“ON”

“FIREMAN SERVICE”

36
Q

It is imperative for the Elevator Operator to remain inside the car. If the doors CLOSE during PHASE II with no personnel inside, the elevator may be ____ for the duration of the incident.

A

lost

37
Q

On the control panel, If the circular “FIRE SERVICE”, “FIRE HELMET” or “MALTESE CROSS JEWEL” indicator light is Blinking then the cars in that bank should NOT be used due to impending SHUTDOWN because of the _____ Switch activation.

A

Shunt

38
Q

Once the SHUNT SWITCH is activated all operations are _______ and the elevator becomes inoperative.

A

cancelled

39
Q

Phase II Operation:

Elevators WITHOUT a door close button will proceed to the ______ chosen floor if a floor button is held in a depressed position.

A

First

40
Q

If an elevator is going to be used for Ascent, precautionary stops SHALL be made every ___ floors in order to test and confirm that the elevator is operating in Phase II as designed.

A

5 floors

41
Q

Precautionary checks SHALL be made an additional ____ floors below the desired floor of termination.

A

2 floors

42
Q

Members using an elevator for ASCENT should also determine the locations of the _________ in relation to the location of the elevator vestibule by observing the floor plans on Precautionary Stops above the Lobby Level.

A

Stairwells

43
Q

At EACH precautionary stop the the SHAFT shall be observed for the presence of _______, _______, _____.

A

Smoke, Fire, Water

44
Q

The Test of Phase II Operations includes:

  1. Testing the door CLOSE and OPEN buttons
  2. Entering several floor by pushing floor indicator buttons.
  3. Press the “_______” or “_____ _______” button to clear the panel.
  4. Select the desired floor of termination and perform precautionary checks every 5 floors.
A

“RESET” or “CALL CANCEL”